ANVILFIELD Try FieldOS

Field glossary · measurement

CUE

Carbon usage effectiveness (CUE) puts operational emissions on an IT-energy basis: 520,000 kg CO2e over 1,000,000 IT kWh is 0.52 kg CO2e/IT kWh. Identify the emissions species, reporting period and energy boundary with that result. PUE multiplied by an electricity factor reproduces CUE only when that factor covers the facility’s energy supply; onsite fuel and mixed electricity sources need their own emissions accounting.

Carbon usage effectiveness, carbon per unit of IT energy, in kg CO2e per kWh; carbon factor times PUE

Used across 2 Anvilfield field guides, most in Datacenter.
Updated

Build the emissions numerator from its energy sources

ISO/IEC 30134-8:2022 defines CUE for the use phase of a data center’s life cycle. Its scope is operational emissions, so the metric does not replace a life-cycle inventory of construction materials and equipment manufacture.

Use CUE = sum of energy-source emissions / IT kWh. For an electricity-only site consuming 1,300,000 kWh against 1,000,000 IT kWh, a factor of 0.40 kg CO2e per supplied kWh produces 520,000 kg CO2e and CUE 0.52 kg CO2e/IT kWh. Fuel burned onsite adds to the numerator on the selected reporting basis; it cannot disappear behind a grid-only factor.

Convert an eGRID factor before multiplying

EPA publishes eGRID output emission rates in pounds per megawatt-hour, so multiplying the printed rate directly by kilowatt-hours introduces both a mass-unit and an energy-unit error. Convert lb/MWh to kg/kWh by multiplying by 0.4535924 and dividing by 1,000, using NIST’s pound conversion.

A reported factor of 900 lb CO2e/MWh becomes 0.4082 kg CO2e/kWh. At PUE 1.30, that yields approximately 0.531 kg CO2e per IT kWh for the electricity-only calculation. Keep CO2 and CO2e columns distinct: CO2e includes the selected treatment of other greenhouse gases.

Keep the inventory year and factor purpose visible

EPA’s eGRID guidance recommends matching historical inventory years with the corresponding eGRID data year when completing several years together. A changed factor can move CUE even when site energy performance stays constant.

EPA identifies nonbaseload rates as estimates for emissions displaced by changes in marginal generation. Allocate ongoing electricity consumption with the appropriate average factor instead. Put the region, data year, emissions species and accounting method beside CUE in the sustainability metrics record, so a later reviewer can reproduce the numerator.

Distinctions

PUE
PUE tracks infrastructure energy overhead. CUE also reflects the emissions intensity assigned to that energy.
Total carbon emissions
A falling ratio can accompany rising emissions when IT energy grows. Report the numerator as well as CUE.

Frequently asked questions

Is CUE dimensionless?

No. Preserve the mass-per-energy unit and identify whether the mass is CO2 or CO2e.

Can renewable electricity change CUE without changing PUE?

Yes. Changing the assigned electricity emissions factor changes the carbon numerator while the measured facility-to-IT energy ratio stays the same.

Sources checked

Also defined as

  • Carbon Usage Effectiveness, carbon emitted per unit of IT energy, in kg CO2 per kilowatt-hour

Where this shows up

Next step: Build a facility list

Back to the full field glossary