Field glossary · component
Tracer wire
Tracer wire makes a buried route locatable by providing a conductor to which a locating transmitter can connect. Specify its conductor, insulation, splice system and accessible terminals as one locating circuit. In Copperhead's telecom specification, both trench and bore products are 12 AWG, but their minimum break loads are 450 and 1,150 pounds respectively. Turnover needs route tracing as well as the correct wire; a continuity reading does not establish surface traceability.
A conductor run with a nonmetallic duct bank so it can be located from the surface later
Open-trench wire and bore wire carry different mechanical ratings
Copperhead's telecommunications specification, version 8.5.21, calls for 12 AWG copper-clad steel wire with a minimum 450-pound break load and 30-mil HDPE insulation for open-trench or duct-blown installation. For directional drilling or boring, it specifies 12 AWG copper-clad steel with a minimum 1,150-pound break load and 45-mil insulation. The same wire gauge does not establish the same installation duty.
The bore product's specified break load is about 2.56 times the open-trench product's, while its insulation is 1.5 times as thick. Those ratios explain why a substitution based only on '12 gauge' misses material differences. Break load describes a failure threshold; it is not an instruction to pull the installed wire at that force. Keep the selected product's installation limits with the pull plan.
A locating circuit needs accessible connections and a return path
Copperhead's specification requires sealed direct-burial connectors that prevent exposed conductor and excludes nonlocking friction-fit or taped connections. It also requires grounding at dead ends and stubs in its specified system. A splice that conducts on installation day can lose that usefulness after moisture reaches an unsealed joint.
Radiodetection's RD8200 manual describes direct connection to a nonenergized conductive utility using a red lead at the target and a black lead at the ground connection. The accessible tracer terminal and the return path therefore form part of the locating arrangement. A buried wire end with no reachable connection point leaves the locator without the intended interface.
The duct-bank guide covers the buried assembly. Add the tracer access-point identifiers to that record so the next locate does not begin by guessing which terminal follows which duct route.
Acceptance requires a traced route, not just continuity
Copperhead's telecom specification requires actual tracing with typical 512 Hz locating equipment after rough grading and again before final acceptance; it expressly rejects continuity testing as a substitute. Treat those as requirements of that named specification, rather than a gauge-based rule covering every utility. A DC continuity result establishes an electrical path between test points, while the locate demonstrates the recovered route.
At a main with two service branches, log a locate from each labeled branch access point and compare the recovered route with the as-built. A strong main-line response leaves the two branches unproven. Include the transmitter connection, frequency, endpoint labels and any untraceable section in the turnover record used for later utility locating.
Sources checked
Also defined as
- Plumbing: A continuous insulated copper wire laid along a plastic service so the buried line can be found with a locator, with accessible terminations
- Paving: A continuous conductor laid with plastic pipe so the line can be located later