Field calculator
ASHRAE 62.1 ventilation rate calculator
Outdoor air for ventilation is sized two ways at once: enough for the people and enough for the space itself, and ASHRAE 62.1 adds them. The breathing-zone outdoor airflow Vbz equals the per-person rate Rp times the number of people Pz, plus the per-area rate Ra times the zone area Az. Enter the four values. Typical office numbers are about 5 cfm per person and 0.06 cfm per square foot, but the correct rates come from the occupancy-category table in the standard, which varies a lot by space type (classrooms, gyms, labs, and patient rooms are all different). The result is the breathing-zone requirement. To get the zone outdoor airflow you divide by the zone air distribution effectiveness Ez, which is around 0.8 when warm air is supplied from the ceiling and up to 1.0 with good mixing, so poor distribution means more outdoor air. At an air handler serving several zones, the multiple-spaces equation and the system ventilation efficiency adjust the total again, usually downward but never below any single zone's need. Use the rates, effectiveness values, and full procedure from the adopted edition of ASHRAE 62.1, and confirm the design with the mechanical engineer.
Result
ASHRAE 62.1 breathing-zone outdoor air: Vbz = Rp × Pz + Ra × Az, the people-based rate (Rp per person times the number of people Pz) plus the area-based rate (Ra per square foot times the zone area Az). Enter the four values; typical office figures are about 5 cfm per person and 0.06 cfm per square foot, but the right numbers come from the occupancy-category table in the standard. The result is the breathing-zone outdoor airflow. To get the zone outdoor airflow you divide by the zone air distribution effectiveness Ez (around 0.8 for ceiling supply of warm air, up to 1.0 for good mixing), and at the air handler serving several zones the multiple-spaces equation and the system ventilation efficiency reduce the total further. Use the rates, effectiveness values, and procedure from the adopted edition of ASHRAE 62.1, and confirm the design with the mechanical engineer.
anvilfield.com/calculators/ashrae-ventilation-rate-calculator · Free field calculators and FieldOS. A planning estimate, verify against the code, the manufacturer, and the engineer of record.
More HVAC calculators
When a district budgets classroom ventilation upgrades, PorchRocket's Bid Control flags the capital plan so your estimating desk sees the work ahead of the bid.
Ventilation rate FAQ
How does the ventilation rate calculation work?
Outdoor air for ventilation is sized two ways at once: enough for the people and enough for the space itself, and ASHRAE 62.1 adds them. The breathing-zone outdoor airflow Vbz equals the per-person rate Rp times the number of people Pz, plus the per-area rate Ra times the zone area Az. Enter the four values. Typical office numbers are about 5 cfm per person and 0.06 cfm per square foot, but the correct rates come from the occupancy-category table in the standard, which varies a lot by space type (classrooms, gyms, labs, and patient rooms are all different). The result is the breathing-zone requirement. To get the zone outdoor airflow you divide by the zone air distribution effectiveness Ez, which is around 0.8 when warm air is supplied from the ceiling and up to 1.0 with good mixing, so poor distribution means more outdoor air. At an air handler serving several zones, the multiple-spaces equation and the system ventilation efficiency adjust the total again, usually downward but never below any single zone's need. Use the rates, effectiveness values, and full procedure from the adopted edition of ASHRAE 62.1, and confirm the design with the mechanical engineer.
What does the ventilation rate result mean?
ASHRAE 62.1 breathing-zone outdoor air: Vbz = Rp × Pz + Ra × Az, the people-based rate (Rp per person times the number of people Pz) plus the area-based rate (Ra per square foot times the zone area Az). Enter the four values; typical office figures are about 5 cfm per person and 0.06 cfm per square foot, but the right numbers come from the occupancy-category table in the standard. The result is the breathing-zone outdoor airflow. To get the zone outdoor airflow you divide by the zone air distribution effectiveness Ez (around 0.8 for ceiling supply of warm air, up to 1.0 for good mixing), and at the air handler serving several zones the multiple-spaces equation and the system ventilation efficiency reduce the total further. Use the rates, effectiveness values, and procedure from the adopted edition of ASHRAE 62.1, and confirm the design with the mechanical engineer.