HVAC
Dedicated outdoor air system (DOAS) field guide for HVAC
Dry the ventilation air to a low dewpoint, let a parallel system carry the room sensible load, recover the exhaust energy, and prove the supply dewpoint in the field.
Direct answer
A dedicated outdoor air system, DOAS, treats ventilation air separately from the building's recirculating space-conditioning system. Its airflow and supply humidity ratio must meet the assigned ventilation and moisture loads; cold supply also contributes sensible cooling. Select and commission the system from the approved ventilation schedule, psychrometric conditions, recovery equipment and controls. A DOAS arrangement does not by itself establish that every room's latent load is covered.
On this page
What a DOAS is, and why ventilation gets its own unitWhat problem does a DOAS solve?How is a DOAS different from a regular HVAC system?The parallel sensible systemDoes a DOAS need energy recovery?Neutral supply versus cold supplyDewpoint control and reheatField example: a DOAS load splitHow much moisture and room cooling can 2,000 cfm handle?Controls: constant volume, demand ventilation, and CO2How much outdoor air does a DOAS deliver?How do you size outdoor airflow for a commercial DOAS?Why the energy code keeps pushing DOASWhich codes and editions govern a commercial DOAS in 2026?DOAS in high-density and high-load buildingsCommissioning a DOASMaintaining it once it is in serviceWhat belongs in a commercial DOAS service contract?What to documentCommon mistakesField checklistStandards and referencesUnits, terms, and conversionsMethodologyOpen the related tool for the calculation, checklist, or packet.
BlowerCFMAirflow and commissioning checks for HVAC work.FieldOS by AnvilfieldOffline-first FieldOS for job photos, proof packets, property memory, calculations, teams, billing, and owner-ready reports.Key takeaways
- A DOAS conditions only the ventilation outdoor air, drying it to a low dewpoint to carry the latent load while a parallel system handles room sensible.
- Control and commission a DOAS on supply dewpoint, not supply temperature, because dewpoint determines whether the air can absorb space moisture.
- A common DOAS supply dewpoint target is 50 to 55 degrees, but the design engineer and project spec set the actual number.
- ASHRAE 90.1 often requires energy recovery on 100 percent outdoor air, with a common trigger of 5,000 cfm supply at 70 percent or more outdoor air and roughly 50 percent minimum enthalpy effectiveness.
- Cold supply is usually more efficient than neutral; reheating dehumidified air to room temperature throws away the sensible cooling already paid for.
What a DOAS is, and why ventilation gets its own unit
A dedicated outdoor air system treats ventilation outdoor air separately from recirculating space conditioning. It can filter, cool, dehumidify, heat and recover energy according to the selected equipment. A parallel system handles the room load remaining after the DOAS contribution. Document the division of sensible and latent duty rather than assigning it from the equipment label.
That split is the whole idea. In a conventional setup, a single rooftop unit or air handler mixes a little outdoor air into a lot of return air and tries to do everything at once: cool the room, heat the room, and dehumidify the fresh air, all off the same coil and the same thermostat. A DOAS pulls the ventilation job out and gives it dedicated equipment that can be controlled on humidity instead of temperature.
You see DOAS on schools, offices, labs, healthcare, multifamily, and any building where the ventilation rate is high and the indoor humidity matters. It pairs naturally with energy recovery on the outdoor air and with parallel sensible systems like fan coils, chilled beams, VRF, or radiant. The Anvilfield ERV commissioning guide and the economizer and demand-control ventilation guide cover the pieces that bolt onto it.
- DOAS
- Dedicated outdoor air system, equipment that treats ventilation outdoor air separately from recirculating space conditioning
- Latent load
- The moisture load, the energy needed to remove water vapor from the air, separate from temperature
- Sensible load
- The temperature load, the heat that changes air temperature without changing its moisture content
What problem does a DOAS solve?
Ventilation and room moisture loads can persist when the sensible cooling demand falls. A thermostat-only sequence can then stop cooling before sufficient moisture has been removed. That is a control and selection problem, not proof that every mixed-air system is incapable of humidity control.
A DOAS provides a separate ventilation-air conditioning path. Select supply airflow and humidity ratio to cover the assigned outdoor and room moisture loads at the required operating conditions. Humidity controls, compressor modulation and reheat must work through the expected part-load range.
A properly designed mixed-air system with humidity controls can also manage part-load moisture. Trane's supply-dewpoint analysis shows why matching the supply dewpoint to the room target leaves little capacity for room-generated moisture. Check the mass balance before treating parallel terminals as sensible-only equipment.
How is a DOAS different from a regular HVAC system?
A mixed-air unit conditions outdoor and return air together. A DOAS treats the ventilation stream separately, allowing ventilation and moisture control to be coordinated independently of room temperature demand. Occupants, processes and infiltration also create moisture loads; outdoor air is not automatically the only or largest source.
Because the humidity rides in on the fresh air, a properly designed DOAS can take on essentially all of the space latent load plus a slice of the sensible, leaving the parallel sensible-only system to make up the rest of the temperature load. The two systems can then be sized for what each actually does, instead of one oversized box trying to cover the worst-case of both at once. That right-sizing is where the efficiency comes from.
The practical consequence on the job is that you commission a DOAS on dewpoint, not on supply temperature alone. Both mixed-air and DOAS arrangements must meet the project's temperature, humidity and ventilation requirements. A DOAS is judged by whether the air it delivers is dry enough to absorb the building's moisture across the whole year, including the mild wet days when the sensible system is barely running.
The parallel sensible system
Select the parallel system for the load remaining after the DOAS contribution. Sensible-only chilled beams or radiant cooling require their surfaces to remain above the room dewpoint under the specified operating conditions. A DOAS label does not guarantee dry operation; verify moisture capacity, infiltration control and shutdown responses.
The common choices each have a fit. Fan coils are the workhorse, cheap and familiar, and they tolerate a little residual moisture. Four-pipe fan coils give you simultaneous heating and cooling across zones. VRF gives tight zoning and good part-load efficiency and pairs cleanly with a DOAS for the ventilation it cannot provide on its own. Chilled beams and radiant panels run with no moving parts in the space and stay quiet, but they live or die on the DOAS holding the dewpoint, because condensation on a chilled beam is a ceiling stain and a callback.
The choice is a design decision driven by the building, the zoning, and the budget, not a default. What matters in the field is that the parallel system is matched to the residual sensible load after the DOAS contribution, and that its surface temperatures stay above the space dewpoint the DOAS is maintaining.
| Parallel sensible option | Where it fits | Watch for |
|---|---|---|
| Fan coil units | Most buildings, tolerant of residual moisture | Condensate drains, filter and coil cleaning |
| VRF / VRV | Tight zoning, good part-load efficiency | Refrigerant volume, needs DOAS for ventilation |
| Chilled beams (active/passive) | Quiet, no in-space moving parts | Surface above space dewpoint or it sweats |
| Radiant ceiling or floor | Comfort, low noise, high-temp water | Slow response, condensation risk if DOAS slips |
Does a DOAS need energy recovery?
A DOAS treats the outdoor ventilation stream, so suitable exhaust-air recovery can reduce its conditioning duty. An enthalpy exchanger transfers both sensible heat and moisture. Check exhaust suitability, leakage, frost control and the adopted energy-code requirements before selecting the arrangement.
Apply the adopted energy-code recovery requirements using the actual climate zone, airflow, outdoor-air fraction, operating hours, recovery metric and exceptions. The code edition and project determine the requirement. Do not use a single airflow or outdoor-air percentage as a universal trigger or exemption.
On the latent-heavy job, the enthalpy wheel is doing real work on the moisture, not just the temperature. The Anvilfield ERV commissioning guide covers how to balance the two airstreams, control frost, hold cross-contamination down, and prove the measured effectiveness against the AHRI 1060 rating instead of inferring the wheel is recovering what the schedule claims.
Verify exhaust-air suitability, leakage and frost operation separately. Compare field recovery measurements at conditions appropriate to the rated metric. An exchanger's laboratory rating is distinct from the performance of the installed complete ventilation system.
Neutral supply versus cold supply
After dehumidification, select the supply dry-bulb temperature from zone loads and distribution requirements. Cold supply retains useful sensible cooling. Neutral supply adds reheat toward the selected room condition, reducing that cooling contribution. The parallel system must carry the load remaining at the actual delivered temperature.
Cold supply retains sensible cooling from the dehumidification process and reduces the remaining room cooling load. Neutral supply reheats that air when required by the zone or distribution strategy. Compare part-load operation, heat recovery, fan energy and zoning in the selected system rather than declaring a universal energy winner.
Neutral still has its place. It simplifies control where the parallel system must own all the zoning, and it avoids dumping cold air into spaces that cannot diffuse it well. The trade is comfort and zoning flexibility against the reheat energy. Make the call on the building, then commission to whichever strategy the design actually chose, because a cold-supply design balanced as if it were neutral will overcool or overheat.
| Strategy | Supply condition | Effect on the parallel system | Energy |
|---|---|---|---|
| Neutral | Reheated to near room temperature | Carries the remaining load after the reheated-air contribution | Evaluate reheat source and operating sequence |
| Cold | Near the coil leaving temperature | Carries reduced sensible, DOAS helps cool | Retains useful sensible cooling where the zones need it |
Dewpoint control and reheat
Select supply humidity ratio and dewpoint from the airflow, room humidity target and moisture load. Dry-bulb temperature alone does not establish moisture-removal capacity. The supply air must carry enough room moisture at the selected airflow, in addition to the outdoor-air conditioning duty.
Reheat enters because the air coming off a coil cold enough to hit that dewpoint can be colder than you want to deliver, especially on a neutral-supply design or during low sensible load when cold air would overcool the space. The trap is paying twice: cooling the air down with the compressor, then heating it back up with a separate energy source. New gas or electric heat for reheat is the wasteful version and the energy code restricts it.
Hot-gas reheat recovers heat from the refrigeration circuit; a wrap-around heat pipe can transfer heat between entering and leaving air. An enthalpy recovery exchanger exchanges heat and moisture between separate supply and exhaust streams. These are different arrangements with different controls and energy consequences. Apply the adopted reheat provisions and selected equipment sequence.
The energy code does not impose one universal DOAS discharge temperature across all systems. Check the applicable provision and exceptions. Trane's hot-gas-reheat newsletter describes humidity-control arrangements and their code context, including mixed-air dehumidification at low sensible load.
Field example: a DOAS load split
Anvilfield's DOAS research compares 2,000 cfm supplied to a 75°F room at 50% relative humidity. The cold-supply case uses 53°F dry bulb and a 50°F dewpoint. The lower supply humidity ratio provides room moisture capacity; the temperature difference provides sensible cooling.
The neutral-supply case reheats the same dry air to 73°F. Anvilfield analysis finds 47,520 Btu/h of room sensible cooling from cold supply and 4,320 Btu/h after that reheat. The parallel system carries the remaining room sensible load in each case.
Supply dry bulb and moisture content perform different jobs. Match both with airflow and the room loads when selecting the unit and balancing the parallel terminals.
| Research-case item | Value |
|---|---|
| Ventilation airflow | 2,000 cfm |
| Room dry bulb / relative humidity | 75°F / 50% |
| Supply dewpoint | 50°F |
| Cold-supply dry bulb | 53°F |
| Neutral-supply dry bulb | 73°F |
How much moisture and room cooling can 2,000 cfm handle?
Anvilfield research calculates 9,000 lb/h of dry-air flow for the ventilation case. The supply stream absorbs 14.4 lb/h of room moisture. The outdoor-air coil condensate calculation is 66.6 lb/h, or 7.99 gal/h. Those quantities describe different parts of the moisture balance.
Anvilfield analysis gives 47,520 Btu/h, or 3.96 tons, of room sensible cooling with cold supply. Reheating that air from 53°F to 73°F transfers 43,200 Btu/h into the supply stream. Select the refrigeration coil from its full entering-to-leaving duty rather than treating the room contribution as total coil capacity.
| Quantity | Result |
|---|---|
| Room moisture pickup | 14.4 lb water/h |
| Outdoor-air coil condensate | 66.6 lb/h, or 7.99 gal/h |
| Room sensible contribution | 47,520 Btu/h, or 3.96 tons at 12,000 Btu/h per ton |
| Reheat from 53°F to 73°F | 43,200 Btu/h of air heating |
Anvilfield analysis separates outdoor coil condensate, room moisture pickup, sensible cooling and reheat.
- Compare the 14.4 lb/h room pickup with the calculated occupant, infiltration and process moisture load.
- Select the outdoor-air coil from entering and leaving conditions, recovery performance and manufacturer data. The 3.96 tons is room cooling contribution, not total coil capacity.
- Verify low-load compressor modulation and condensate disposal against the actual equipment selection.
Controls: constant volume, demand ventilation, and CO2
The simplest DOAS runs constant outdoor air volume whenever the building is occupied: a fixed cfm of fresh air, dried to the supply dewpoint, every hour the schedule says people are in. It is easy to balance, easy to verify, and the right choice where occupancy is steady and predictable. The cost is that you condition full design ventilation even when the building is half empty.
Demand-controlled ventilation cuts that waste by modulating the outdoor air to the people actually present, usually inferred from CO2. As the space fills and CO2 rises, the DOAS brings in more fresh air. As it empties, the airflow backs off and so does the conditioning energy. On a DOAS the outdoor air rate is the whole job, so DCV acts directly on it, but it has to be set so the airflow never drops below the per-area ventilation floor the code still requires with the space empty.
Use the adopted ventilation standard and approved sequence for sensor accuracy, location, minimum airflow and failure response. CO2 reflects occupancy only where the space's sources and control method support that inference. Check non-occupant sources before using it to command ventilation.
How much outdoor air does a DOAS deliver?
A DOAS delivers the ventilation outdoor air rate the building is required to provide, which comes from ASHRAE Standard 62.1 for most commercial and institutional work, or the IMC where that is the adopted code. The rate is not a single number. The 62.1 ventilation-rate procedure adds a per-person component and a per-area component, so a crowded space like a classroom carries a high rate and a sparse one like a warehouse carries a low one, and the total is summed across the spaces the unit serves.
The reason the DOAS handles this so cleanly is that it delivers the ventilation air directly, at a known volume, instead of hoping a mixed-air unit pulls in enough outdoor air through a damper that drifts. You can measure the outdoor airflow at the unit and prove it against the design, which is exactly what 62.1 and most commissioning scopes ask you to document.
On the job, the outdoor air rate is the first thing to verify and the easiest to get wrong. A DOAS balanced low starves the building of fresh air and fails the ventilation requirement quietly. Balanced high, it wastes energy conditioning air nobody needs and can pressurize the building. Measure it, record it against the design rate per space, and confirm the standard and edition the project was designed to.
How do you size outdoor airflow for a commercial DOAS?
Anvilfield's office ventilation analysis gives 500 cfm from the people component and 600 cfm from the area component, totaling 1,100 cfm at the breathing zone. Use the approved room classification and schedule to establish the actual project inputs.
Anvilfield research calculates 1,100 cfm with zone air-distribution effectiveness of 1.0 and 1,375 cfm at 0.8, a 25% increase. Resolve the heating and cooling arrangements, then account for other zones, exhaust, transfer air and pressure control. Verify branch delivery as well as the unit total.
| Office example component | Outdoor airflow |
|---|---|
| People | 500 cfm |
| Area | 600 cfm |
| Breathing zone | 1,100 cfm |
| Zone supply, Ez = 1.0 | 1,100 cfm |
| Alternate mode, Ez = 0.8 | 1,375 cfm |
Why the energy code keeps pushing DOAS
The reason DOAS shows up on more drawings every cycle is the energy code, not fashion. ASHRAE 90.1 and the IECC have tightened the rules around ventilation energy, reheat, and energy recovery, and a decoupled system answers all three at once. It conditions only the air that has to be conditioned, it recovers the exhaust energy on that air, and it avoids the simultaneous-heating-and-cooling waste that a single mixed-air unit falls into at part load.
High-performance and low-energy building targets sharpen the case. Once a project is chasing a stretch code, a green-building standard, or a net-zero energy goal, the part-load humidity and reheat losses of a conventional system become the loads you can no longer afford. Decoupling lets the designer size each system tight, run the sensible system at efficient water temperatures, and recover energy on the ventilation, which is where the modeled savings come from.
What this means for the field is that a DOAS is usually carrying a compliance path, not just comfort. If the unit is not delivering its design outdoor air, not recovering at its rated effectiveness, or burning new heat for reheat, the building may be out of step with the energy model it was permitted on. Commission it like the energy case depends on it, because it does.
Which codes and editions govern a commercial DOAS in 2026?
Edition check, November 5, 2026: ASHRAE lists Standard 62.1-2025 and Standard 90.1-2025 as published editions. Publication does not change the permit basis. Record the adopted mechanical code, energy code or referenced 90.1 edition, local amendments and approved ventilation calculation separately. Use the actual DCV sensor and failure-response requirements from that edition, rather than copying an older sensor rule of thumb.
Use NEC 2026 where adopted; otherwise use the edition effective for the permit, with local amendments. Minnesota shows why the date matters: its permits filed on or after August 17, 2026 use NEC 2026, while earlier filings use NEC 2023. Confirm the applicable edition with the authority having jurisdiction before estimating electrical changes.
Record nameplate voltage, phase, minimum circuit ampacity (MCA) and maximum overcurrent protection (MOCP), plus any separate heater feed. Have the electrical design reconcile those values, conductor corrections, disconnects and equipment instructions. Cooling tons do not size the branch circuit. Greenheck's IVE/IV manual provides an indoor DOAS example of nameplate-based power sizing; use the manual for the actual unit installed.
DOE's DX-DOAS definition references a 55°F dewpoint capability at AHRI 920-2020 rating conditions. That product classification does not establish the project's supply-dewpoint target or prove room latent capacity. AHRI 1060-2023 addresses air-to-air recovery exchanger ratings, a different boundary from the complete DOAS refrigeration system.
DOAS in high-density and high-load buildings
The buildings driving the most DOAS work right now are the high-density and high-internal-load ones, and the comfort spaces attached to data centers and AI compute facilities are a clear case. The white-space servers reject huge sensible heat that is handled by close-coupled cooling, not comfort air, but the people spaces around them, the offices, network operations rooms, and support areas, still need ventilation and humidity control. A DOAS gives those spaces dry, conditioned fresh air without dragging the whole comfort system into the sensible fight the IT load is already winning.
The general pattern holds anywhere the sensible load is large and concentrated while the ventilation is comparatively small: separate the two so each system is built for its real job. A high-density office or a lab with heavy equipment gets a tight, dry ventilation supply from the DOAS and a sensible system sized for the equipment heat, instead of one oversized unit lurching between extremes.
One caution for these spaces. CO2-based demand-control ventilation uses occupant CO2 as the occupancy signal, and rooms with combustion, gas suppression, or other non-occupant CO2 sources change that relationship, which is exactly why 62.1 restricts DCV there. On a technical space, verify the ventilation control logic against what is actually in the room before trusting a CO2 reading to set the airflow.
Commissioning a DOAS
Commissioning a DOAS is proving the unit delivers the design outdoor air, dry enough, with the recovery working, the reheat behaving, and the parallel system balanced against it. The most common failure is not broken hardware. It is a unit that was installed, started, and never measured, so nobody knows whether it holds the dewpoint on a mild wet day, which is the exact day it matters.
Start with the outdoor airflow, measured at the unit against the design rate per space. Then verify the supply dewpoint under load, not just the supply temperature, because temperature alone tells you nothing about whether the air is dry. Confirm the energy recovery is performing by reading temperatures and, where you can, humidity across the wheel or core and comparing the effectiveness to the rating, the same way the ERV commissioning guide lays out. Drive the reheat and check it is recovering heat, not buying it, and that it does not run when there is no call for it.
Then balance the parallel sensible system against the DOAS contribution, because the two interact. If the DOAS is on a cold-supply strategy donating sensible cooling, a parallel system balanced as if the DOAS were neutral will overcool. Test the building across conditions if you can, including a part-load case, because the part-load humidity is the whole reason the DOAS exists and the only time you will catch it slipping.
Maintaining it once it is in service
A DOAS hands the owner a short list of maintenance items that, skipped, quietly erase its performance. The energy wheel is first. A wheel that is dirty, slipping its belt, or stuck slows the recovery and the unit's coil suddenly has to do far more work, which shows up as higher energy and, in winter, a wheel that frosts and a supply that drifts. The wheel seals wear and let exhaust leak into the supply, so they get inspected, against their required condition.
Filters are next, on both the outdoor air and the exhaust. The DOAS pulls 100 percent outdoor air, so it loads filters with everything outside, and a loaded filter cuts the airflow below the ventilation rate the building is required to deliver. The owner who lets filters go is starving the building of fresh air without knowing it.
The condensate drain is the one that bites. A DOAS condenses a lot of water, because removing the latent load is its job, with condensate volume determined by its airflow and entering and leaving conditions. A plugged drain backs water into the unit, onto the floor, or into the ductwork, and a P-trap that dries out or was never primed lets the unit pull air through the drain. Check the drain, the trap, and the pan as routine, not after the ceiling stains.
What belongs in a commercial DOAS service contract?
Build the scope around unit tags and rooms served. Include filter sizes and access, recovery-device cleaning, drain inspection, humidity-sensor comparison, airflow verification and a seasonal trend review. Price lift access, controls access and an occupied-hours visit explicitly. Greenheck's manual shows why filter access and frost-control options belong in the equipment survey. Set visit intervals from the unit manual, loading and operating history.
Service managers planning a commercial DOAS maintenance territory use PorchRocket's Ground Control to find buildings by rooftop HVAC, roof age and size, with lists delivered within 48 hours after payment. Confirm equipment type onsite: rooftop equipment does not establish that a building has a DOAS, and a prospect list does not establish an owner's buying intent.
Deliver a trend showing outdoor conditions, unit airflow, leaving dewpoint, discharge temperature and representative room humidity. Show which readings passed the approved sequence, which remained untested and who owns each correction. That gives the owner a service scope they can compare at renewal.
What to document
A DOAS that nobody documented is a system the next technician has to reverse-engineer at the worst possible time, on a humidity complaint in August. The record is what proves the unit was set to the design and lets the next person tell a drifting setpoint from a real fault.
Capture it per unit. Record the design and measured outdoor airflow, the supply dewpoint setpoint and the measured value under load, the energy recovery type and its measured effectiveness against the rating, the supply strategy and whether reheat is recovered or new heat, and what the parallel sensible system is and how it was balanced against the DOAS. Note the ventilation standard and edition the design was based on, and who verified each number.
| Field to record | Why it matters |
|---|---|
| Unit tag and area served | Ties the data to the right equipment and spaces |
| Design and measured OA cfm | Proves the ventilation rate is actually delivered |
| Supply dewpoint, setpoint and measured | Dewpoint, not temperature, proves the latent capacity |
| Energy recovery type and effectiveness | Confirms recovery against the rating, not modeled |
| Supply strategy (neutral or cold), reheat source | Drives the parallel balance and the energy story |
| Parallel sensible system and balance | The two systems interact and must match |
Common mistakes
- Setting the DOAS on supply temperature instead of dewpoint, so the air is the right temperature but not dry enough and the space stays humid.
- Mismatching the parallel sensible system to the DOAS contribution, so a cold-supply unit overcools or a neutral design leaves the room warm.
- Skipping energy recovery on 100 percent outdoor air, which drives the conditioning energy up and can miss the ASHRAE 90.1 requirement.
- Never verifying the outdoor air rate, so the building is over or under ventilated and the ventilation requirement fails quietly.
- Buying new gas or electric heat for reheat when recovered heat was available, wasting energy and tripping the reheat limits.
- Ignoring the condensate drain and trap on a unit that produces more water than a mixed-air system, so it backs up and floods.
- Running chilled beams or radiant while letting the DOAS dewpoint slip, so the cold surfaces sweat and stain the ceiling.
Field checklist
Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.
Standards and references
The ventilation rate a DOAS delivers comes from ASHRAE Standard 62.1 in most commercial and institutional work, through its ventilation-rate procedure of a per-person plus per-area calculation, or from the adopted mechanical code where that governs. The demand-control ventilation sensor accuracy and placement rules also live in 62.1, along with the restriction against CO2-based DCV where there are CO2 sources other than people.
Apply the adopted energy code's recovery and reheat provisions to the selected system. Record the edition, applicable tables, metrics and exceptions with the design. A previous edition's threshold or section number is not a substitute for that review.
Thermal comfort targets, the temperature and humidity the design holds, trace to ASHRAE Standard 55. Energy recovery devices are rated and certified under AHRI Standard 1060, which is what you check measured effectiveness against. Above all of these, the equipment manufacturer's data and the project's design engineer and specifications control the actual setpoints and capacities. Cite the standard that governs the point, and resolve the code, listing and project requirements together.
Units, terms, and conversions
DOAS work crosses a few unit systems, because the same air state shows up on a psychrometric chart, a controls graphic, and a manufacturer's selection differently.
Airflow is in cubic feet per minute (cfm) on most drawings, or liters per second or cubic meters per hour in metric sources. Dewpoint and dry-bulb temperature are in degrees Fahrenheit here, degrees Celsius elsewhere. Humidity shows up as relative humidity in percent, as dewpoint, or as a moisture content in grains of water per pound of dry air, which is the unit latent capacity is often figured in. Energy recovery is given as effectiveness, a percentage of the available enthalpy difference recovered, and the latent load itself is energy, in Btu per hour or kilowatts.
- Dewpoint
- The temperature at which air becomes saturated and water condenses, the true measure of how dry the air is
- Enthalpy recovery effectiveness
- The share of the total energy difference between exhaust and outdoor air that the recovery device transfers
- Total energy wheel
- A rotating enthalpy wheel that transfers both heat and moisture between the exhaust and the entering outdoor air
- Reheat
- Adding heat to dehumidified air to raise its supply temperature, ideally from recovered heat rather than new energy
- Sensible heat ratio
- The fraction of a cooling load that is temperature versus moisture, which sets how the DOAS and parallel system split the work
- Grains per pound
- Moisture content of air by weight, used to size the latent load the DOAS has to remove
Methodology
Anvilfield research uses 2,000 cfm, 0.075 lb of dry air per cubic foot, room humidity ratio 0.0092 and supply humidity ratio 0.0076 lb/lb. The rounded room and supply conditions are 75°F at 50% RH and a 50°F supply dewpoint, with 53°F cold supply. Dry-air mass flow is cfm times 60 times density. Room moisture pickup multiplies mass flow by the room-to-supply humidity-ratio difference. Outdoor coil condensate uses entering humidity ratio 0.0150 without upstream recovery, with 8.34 lb/gal for the water conversion.
Sensible calculations use a 1.08 standard-air coefficient times cfm times temperature difference. Reheat raises supply from 53°F to 73°F; refrigeration tons divide Btu/h by 12,000. The office case uses 10,000 ft², 100 occupants, 5 cfm/person and 0.06 cfm/ft², with zone effectiveness cases of 1.0 and 0.8. These are scheduled analysis inputs; the adopted standard establishes project rates. Trane supplies the moisture-balance and reheat framework, with Greenheck, AHRI, DOE and the listed code sources providing equipment and rating context. The saved calculation script reproduces each result.
FAQ
What is a DOAS?
A DOAS treats ventilation outdoor air separately from recirculating space conditioning. It conditions that air to the required supply state while parallel equipment handles the remaining room load. Airflow and supply humidity ratio determine the assigned moisture capacity.
How is a DOAS different from a regular HVAC system?
A DOAS gives ventilation air a separate conditioning path; a mixed-air system treats outdoor and recirculated air together. Either arrangement requires appropriate selection and humidity controls. A DOAS does not automatically remove every room latent load.
What is a parallel sensible system?
A parallel sensible system handles the room temperature load remaining after the DOAS contribution. Fan coils, VRF, chilled beams and radiant systems are options. Sensible-only operation requires verified moisture control and surface temperatures above the room dewpoint.
Does a DOAS need energy recovery?
Check the adopted energy code and system selection. Recovery requirements depend on the edition, climate, airflow, operating hours, outdoor-air fraction and exceptions. Select and commission the appropriate recovery equipment rather than applying a universal trigger.
Should DOAS supply air be neutral or cold?
Choose the supply strategy from zone loads, distribution and the approved energy sequence. Cold supply contributes useful room cooling; neutral supply adds reheat to control delivered temperature. Compare the complete operating case.
What dewpoint should a DOAS supply?
Select supply dewpoint from the airflow, target room moisture condition and assigned latent load. The air must be dry enough to carry the required room moisture, not merely arrive at the room target dewpoint.
Why is my building humid even though the DOAS is running?
Check the moisture balance and actual supply dewpoint and airflow first. Then inspect recovery, controls, infiltration, drains and the parallel-system sequence. A running fan or acceptable supply temperature does not establish latent capacity.
How much outdoor air should a DOAS deliver?
It delivers the ventilation rate from ASHRAE 62.1 or the adopted code, summed from a per-person and a per-area component across the spaces served, so a classroom carries far more than a warehouse. Measure the outdoor airflow at the unit and compare it to the design rate per space rather than trusting the schedule.
Does a DOAS replace the cooling system?
No. A DOAS handles the ventilation air and the latent load, but the room sensible load still needs a parallel system such as fan coils, VRF, chilled beams, or radiant. On a cold-supply design the DOAS donates some sensible cooling, but it is not sized to carry the full room temperature load on its own.
Can a DOAS use CO2 demand-control ventilation?
Use CO2 demand control where the adopted standard and approved room application permit it. Verify sensor requirements, non-occupant sources, minimum outdoor airflow and the response to sensor failure.
People also ask
Codes cited in this guide
This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.
Sources checked
- ASHRAE: 2025-2026 publication list Publisher lists Standard 62.1-2025 and Standard 90.1-2025. The adopted code and referenced edition establish the project requirements.
- NFPA: NFPA 70, National Electrical Code 2026 edition and code-development information.
- Minnesota DLI: Electrical codes and standards Permit-date example for NEC 2026 versus NEC 2023.
- Trane: Impact of DOAS Supply-Air Dew Point Temperature on Space Humidity Room moisture balance, supply dewpoint and sensible contribution.
- Trane: Using Hot Gas Reheat for Humidity Control Humidity controls, mixed-air applications and reheat exceptions.
- Greenheck: IVE/IV Modular Dedicated Outdoor Air Unit IOM, document 487167 Indoor installation, electrical sizing, service access and frost control; model-specific guidance.
- AHRI: Standards 1060 and 1061 2023 air-to-air recovery exchanger rating scope.
- U.S. DOE: Direct Expansion-Dedicated Outdoor Air Systems DX-DOAS classification, AHRI 920-2020 reference and federal test procedure.