ANVILFIELD Try FieldOS

Field calculator

Mixed air temperature calculator (MAT)

When an air handler blends outdoor air with return air, the result is the mixed air temperature, the air that hits the heating or cooling coil. It is a weighted average: MAT equals the outdoor-air percentage times the outdoor temperature plus the return-air percentage times the return temperature, where the return fraction is 100 minus the outdoor fraction. Enter the outdoor temperature, the return temperature, and the outdoor-air percentage. This is a core check for testing and balancing and for economizer commissioning, because the measured mixed air should match what the damper position implies. Two cautions matter in the field. In cold weather a high outdoor-air fraction can pull the mixed air below freezing, tripping the freeze-stat or bursting a coil, so the low-limit control and the minimum outdoor-air setting matter. And real mixing boxes stratify, with cold and warm layers that do not fully blend, so a single sensor can read wrong; traverse across the duct. Confirm the design outdoor-air fraction and the readings against the balancing report and the engineer.

More HVAC calculators

Commissioning an air handler brings mixed air temperature into the acceptance readings, and PorchRocket's Bid Control lists public HVAC bids for crews selling that testing and balancing work.

Next step: Find rooftop service stops

Mixed air temp FAQ

How does the mixed air temp calculation work?

When an air handler blends outdoor air with return air, the result is the mixed air temperature, the air that hits the heating or cooling coil. It is a weighted average: MAT equals the outdoor-air percentage times the outdoor temperature plus the return-air percentage times the return temperature, where the return fraction is 100 minus the outdoor fraction. Enter the outdoor temperature, the return temperature, and the outdoor-air percentage. This is a core check for testing and balancing and for economizer commissioning, because the measured mixed air should match what the damper position implies. Two cautions matter in the field. In cold weather a high outdoor-air fraction can pull the mixed air below freezing, tripping the freeze-stat or bursting a coil, so the low-limit control and the minimum outdoor-air setting matter. And real mixing boxes stratify, with cold and warm layers that do not fully blend, so a single sensor can read wrong; traverse across the duct. Confirm the design outdoor-air fraction and the readings against the balancing report and the engineer.

What does the mixed air temp result mean?

Mixed air temperature: MAT = (percent outdoor air × outdoor temp) + (percent return air × return temp), where the return fraction is 100 minus the outdoor fraction. Enter the outdoor air temperature, the return air temperature, and the outdoor-air percentage, and the tool blends them. This is the temperature of the air leaving the mixing box ahead of the heating or cooling coil, and it is a core check for testing, balancing, and economizer commissioning. Two cautions: in cold weather a high outdoor-air fraction can pull the mixed air below freezing and trip the freeze-stat or burst a coil, so watch the low limit; and real mixing boxes stratify, so measure across the duct rather than at one point. Confirm the design outdoor-air fraction and the readings against the balancing report and the engineer.

More in the Manual J load calculation field guide.