ANVILFIELD Try FieldOS

Field calculator

Three-phase power calculator (kW, kVA, amps)

Three-phase power ties together voltage, current, and power factor, and the field needs to move between them constantly to size a service, check a load, or read a nameplate. Apparent power in kVA equals the square root of three times the line-to-line voltage times the line current, divided by 1000, and real power in kW equals that kVA times the power factor. Enter the line-to-line voltage (208, 240, 480, or 600 are common), the line current in amps, and the power factor, which is 1.0 for a resistive load and lower for motors and other inductive loads. To go the other way and solve current from a known kW load, amps equals kW times 1000 divided by the square root of three, the voltage, and the power factor. These are the core relationships; use the equipment nameplate and the real power factor, and apply NEC conductor sizing, continuous-load, and derating rules to the actual installation.

Worked example

A 480 V three-phase feeder carries 100 A at 0.9 power factor. What is the real power?

  • Voltage (line-line)480 V
  • Current100 A
  • Power factor0.9
  1. Apparent power = √3 × V × I = 1.732 × 480 × 100 = 83.1 kVA.
  2. Real power = kVA × PF = 83.1 × 0.9 = 74.8 kW.

83.1 kVA and 74.8 kW. The √3 factor is what separates three-phase from single-phase power math.

Change the numbers in the calculator above to run your own.

More Electrical calculators

When public facilities plan added motor capacity, PorchRocket's Bid Control surfaces early electrical project signals in board meetings, budgets and capital plans for contractors preparing service upgrade estimates.

Next step: Find manufacturing service accounts

Three-phase power FAQ

How does the three-phase power calculation work?

Three-phase power ties together voltage, current, and power factor, and the field needs to move between them constantly to size a service, check a load, or read a nameplate. Apparent power in kVA equals the square root of three times the line-to-line voltage times the line current, divided by 1000, and real power in kW equals that kVA times the power factor. Enter the line-to-line voltage (208, 240, 480, or 600 are common), the line current in amps, and the power factor, which is 1.0 for a resistive load and lower for motors and other inductive loads. To go the other way and solve current from a known kW load, amps equals kW times 1000 divided by the square root of three, the voltage, and the power factor. These are the core relationships; use the equipment nameplate and the real power factor, and apply NEC conductor sizing, continuous-load, and derating rules to the actual installation.

What does the three-phase power result mean?

Three-phase power: apparent power kVA = sqrt(3) × line-to-line volts × line amps / 1000, and real power kW = kVA × power factor. Enter the line-to-line voltage (such as 208, 240, 480, or 600), the line current in amps, and the power factor (1.0 for resistive, lower for motors). To find amps from a known kW load instead, amps = kW × 1000 / (sqrt(3) × volts × PF). These are the basic relationships; use the equipment nameplate and actual power factor, and apply NEC conductor sizing, continuous-load, and derating rules for the real install.

More in the Load calculation, NEC 220 field guide.