Field glossary · component
Disconnecting means
A disconnecting means is the device or coordinated set of devices that opens a specified electrical supply path, such as a conveyor's incoming feeder. Its boundary matters: opening the conveyor disconnect can leave a separately supplied service light energized. Select the device by its listing and circuit position, then identify every supply it actually interrupts. An ampere rating alone cannot establish that application.
The NEC term for the device that disconnects a circuit from its supply; a switch, breaker, or in some cases a plug
Read the listing before choosing a motor isolator
Leviton's motor-control guidance identifies UL 60947-4-1 manual motor controllers with the marking Suitable as Motor Disconnect. UL Solutions explains why that marking matters: the controller belongs on the load side of branch-circuit protection, not in the feeder position ahead of it.
For a nonfused horsepower-rated machine incoming switch, UL's NFPA 79 guidance calls for a UL 98 device rather than a UL 508 manual motor controller. Its explanation rests on the different electrical spacing evaluations for feeder and branch-circuit use.
Sketch the final branch protective device beside the proposed switch before approving a substitution. The disconnect-switch guide covers placement and ratings; this sketch establishes the product's circuit position. UL's machine examples interpret NFPA 79-2021. NFPA now publishes NFPA 79-2024 and NEC 2026, so identify the project's governing editions separately from the age of the application note.
Trace the disconnect through a two-motor machine
Under the NFPA 79-2021 application discussed by UL Solutions, a listed self-protected combination starter qualifies as the machine supply disconnect only for a machine consisting of one motor circuit. The exception does not extend to a conveyor with several motors and auxiliary loads.
Consider a conveyor with a 10 hp belt motor, a 3 hp feeder motor, and a 120 V control-power supply. A marked motor controller beside the belt motor identifies an isolation point for that branch. It does not, by that marking alone, establish an incoming disconnect for the feeder motor and control supply as well.
The proposed replacement schedule should distinguish the incoming switch from the belt-motor controller and feeder-motor controller. Put the listing and motor rating beside each device. A larger enclosure or a higher ampere rating cannot turn the belt-motor controller into the machine's incoming isolator.
Which circuits stay live with the main switch off?
UL Solutions' NFPA 79-2021 explanation requires a separate disconnect for an excepted circuit that stays supplied when the machine incoming disconnect opens. A separately supplied maintenance light is a reason to trace the auxiliary feed, not evidence that the main handle disconnects it.
Identify the upstream source and disconnect for each such circuit on the conveyor wiring record. Include the incoming switch's line-side conductors in the energized-boundary review: opening its contacts does not disconnect the supply feeding those terminals.
Do not classify every retained control voltage as an excepted external supply. UL's FAQ separately addresses a machine's internal transformer and 24 VDC supply with UPS backup and says that arrangement does not itself require an additional machine supply disconnect. Trace where the power originates before selecting the rule.
The wiring diagram identifies the supply paths; an open-handle photograph identifies position. Neither is a voltage test. Follow the lockout and isolation reference when establishing the condition needed for work.
Distinctions
- Branch protection
- UL's machine-supply FAQ permits branch-rated fuses after a suitable nonfused incoming switch. In that arrangement, the switch opens the circuit and the downstream fuses provide the required overcurrent protection.
Frequently asked questions
Does a motor-disconnect marking permit use ahead of branch protection?
UL Solutions says a manual motor controller with that marking remains a branch-circuit device. Moving it ahead of the final branch protective device changes the application to a feeder position that the marking does not authorize.
What should a replacement disconnect submittal identify?
Identify the replaced circuit position, device listing, voltage and motor ratings, application markings, protective-device arrangement, and the circuits the replacement will disconnect.
Sources checked
- UL Solutions: NFPA 79-2021 machine supply FAQ, feeder versus branch use, single-motor limitation, excepted circuits, and internal UPS example
- Leviton: UL 60947-4-1 manual motor controllers and motor-disconnect marking
- NFPA: NFPA 79 publisher record, current 2024 edition
- NFPA: NFPA 70 publisher record, current 2026 edition
Also defined as
- Datacenter: The device that opens the circuit; the EPO is the room's emergency disconnecting means for IT power and HVAC