Field glossary · safety
Safe working load (SWL)
Safe working load is a component's permitted service force for its specified installation. Dayton Superior rates the A55 form tie at 2,250 lb with an approximately 2:1 safety factor. That rating is compared with the tie's force demand, calculated from concrete pressure and tributary area, not directly with a pressure in psf. The application factor, connecting hardware and loading direction must match the basis used to assign the rating.
The rated load for a tie or shore, the breaking strength reduced by a built-in safety factor
The application determines the required safety factor
Dayton Superior's September 2024 Condensed Accessory Handbook recommends a minimum safety factor of 2.0 for form ties. For form anchors, it distinguishes 2.0 for form weight and concrete pressure from 3.0 where the anchor supports forms, concrete, live load and impact. The accessory category and what it supports determine which recommendation applies.
Dayton Superior's A55 Sure-Lock Tie data sheet assigns 2,250 lb SWL with an approximately 2:1 safety factor to that particular tie. It identifies the A56 bracket and A57 strongback bracket as its companion hardware. Substituting another connection leaves the published system configuration even when the tie itself is unchanged.
Convert form pressure into tie force
For a tie assigned 2 ft2 of tributary area under a design pressure of 900 psf, the force is 900 x 2 = 1,800 lb. That is 80% of the A55's published 2,250 lb rating. Increasing the assigned area to 3 ft2 raises the force to 2,700 lb, or 120% of the rating. The latter layout fails the tie-force check even though the concrete pressure is unchanged.
Use the design pressure at that location and the actual assigned tributary area. This checks the tie only; the brackets, walers, sheathing, anchors and overall stability still need the formwork system's design checks.
Recalculate a rating when the required factor increases
Dayton Superior's handbook recalculates SWL as original SWL multiplied by original safety factor, divided by the newly required factor. A component rated 2,250 lb at a factor of 2.0 would be limited to 1,500 lb when a factor of 3.0 is required: 2,250 x 2 / 3. Increasing the factor reduces the permitted service load.
That adjustment addresses the factor used in the rating; it does not quantify lost capacity from bent steel, damaged threads or an unsupported connection. Keep the rating basis separate from the condition finding. Changing a spreadsheet factor cannot restore a damaged component or establish the capacity of hardware assembled outside its specified configuration.
A shore rating does not authorize an eccentric head load
OSHA 29 CFR 1926.703(b)(7) prohibits eccentric loads on shore heads unless the members are designed for them. A force smaller than the published axial SWL can still fall outside the designed loading arrangement when it acts off center. Locate the load relative to the head and bearing, not just relative to a catalog number.
Under OSHA 29 CFR 1926.703(b)(3), a log containing only a pre-pour shoring inspection leaves the during-placement and immediately-after-placement inspections undocumented. Record the first check immediately before placement, then give the later checks their own times in the shoring record. Record changes in head contact, base bearing and alignment as they occur.
Distinctions
- Ultimate load
- This is the failure-capacity basis used with the specified factor. It is not the service load allowed on the component.
- Form pressure
- Pressure multiplied by the component's assigned tributary area produces a force. Comparing a psf pressure directly with an SWL in pounds skips that area.
Frequently asked questions
Can a safety factor be treated as spare capacity for a faster pour?
The permitted load is the SWL under the specified conditions. The margin between that rating and ultimate capacity is already assigned to the safety factor; it is not an additional service-load allowance.