ANVILFIELD Try FieldOS

Plumbing

Air admittance valves and island vents field guide for plumbers

What an AAV does, how it differs from a real vent, where the code lets you use one, how to mount it, and why the system still needs a vent to the roof.

Air Admittance ValveAAVIsland VentVentingPlumbing

Direct answer

An air admittance valve (AAV) is a one-way valve that opens under the negative pressure of a draining fixture to let air into the drain, protecting the trap seal from siphoning, then closes to keep sewer gas out. It vents a fixture without a pipe to the roof, but acceptance varies by code, so the adopted code and AHJ control.

On this pageWhat an air admittance valve isWhy does a draining fixture need a vent?How does an air admittance valve work?AAV versus a conventional ventWhat can an air admittance valve not do?Where AAVs get usedHow do you vent an island sink?The island fixture (loop) ventAre air admittance valves allowed by code?IPC versus UPC on AAVsASSE 1051 and 1050, the listingHow high does an air admittance valve have to be?Accessible, ventilated, and uprightSizing the AAVDo air admittance valves go bad?Why does an air admittance valve smell of sewer gas?Positive pressure and the stackWhen not to use an AAVWhat the inspector checksWhat to documentCommon mistakesField checklistStandards and referencesUnits and terms

Key takeaways

  • An air admittance valve (AAV) is a one-way valve that opens under draining suction to admit air and protect the trap seal, then closes against sewer gas.
  • An AAV admits air only and cannot relieve positive pressure, so the system still needs atmospheric venting (normally the stack through the roof).
  • AAV acceptance varies by jurisdiction: the IPC permits them under conditions while the UPC has historically restricted or prohibited them; confirm the adopted code and AHJ.
  • ASSE 1051 covers individual and branch-type AAVs; ASSE 1050 covers stack-type AAVs, and the two are not interchangeable.
  • Mount AAVs upright, accessible, and ventilated: branch AAVs commonly at least 4 in above the branch, stack AAVs around 6 in above the highest fixture's flood level rim.

What an air admittance valve is

An air admittance valve, the AAV, is a one-way valve that admits air into the drainage system when a fixture drains and seals against sewer gas the rest of the time. Plumbers also call it a Studor vent, the way a brand name becomes the generic. It does one job: break the vacuum a draining fixture creates so that vacuum cannot pull the water out of the trap.

The valve sits at the top of a short vent stub off the fixture drain, usually under the sink or in the wall cavity behind it. Inside is a light diaphragm that lifts on suction and drops shut under its own weight when the suction stops. No power, no spring, no connection to anything. Air goes in. Gas does not come out.

Where it earns its place is the fixture you cannot easily run a vent pipe from to open air. The kitchen island with no wall behind it. The remodel where the old vent is gone and the roof is finished. The basement bath added long after the stack was set. The companion DWV venting guide covers conventional vents and how the trap seal works; this one is about venting that fixture when the pipe to the roof is the hard part.

Why does a draining fixture need a vent?

A draining fixture needs a vent because moving water drags air with it, and if no vent feeds that air in, the drain pulls it through the only other opening, the fixture trap. The falling slug of water leaves a vacuum behind it. That vacuum reaches back up the trap arm and siphons the trap dry.

Lose the trap seal and you have an open pipe to the sewer sitting under the fixture. Hydrogen sulfide and methane come up into the room, and nobody smells the problem until the gas is already there. The seal is the only barrier, and it is roughly 2 in of water held in a U of pipe. It does not take much suction to empty it.

A vent breaks the vacuum by giving the moving water somewhere to pull air from. A conventional vent does that with a pipe open to atmosphere at the roof. An AAV does the same thing locally. It opens and feeds air into the drain right at the fixture instead of running a pipe up through the building. Same physics, different source of air.

How does an air admittance valve work?

An AAV works on pressure difference and gravity, with no moving part beyond a light sealing diaphragm. At rest, the diaphragm sits closed on its seat under its own weight and any positive pressure in the line, so sewer gas stays in the pipe. There is no spring forcing it open or shut.

When the fixture drains, the falling water pulls a slight negative pressure in the line. That suction is enough to lift the diaphragm off its seat. Room air flows in through the valve intake, feeds the drain, and breaks the vacuum that would otherwise siphon the trap. The moment the water stops and the pressure equalizes, the diaphragm drops shut again.

The direction is one-way by design, and that is the whole idea. Negative pressure opens it to let air in. Static or positive pressure holds it shut to keep gas in. That asymmetry is also the limit. The valve only ever admits air. It cannot relieve pressure pushing the other way, and a lot of bad installs come from forgetting that.

AAV versus a conventional vent

A conventional vent is an open pipe to atmosphere with no moving parts. It admits air when the drain pulls a vacuum and it relieves pressure when the stack surges, because air moves both directions through an open pipe. It never wears out and it handles both failure directions. The cost is the pipe: you have to get it up through the structure and out the roof, with the slope, the supports, and the roof penetration that come with it.

An AAV trades that pipe for a valve at the fixture. No roof penetration, no chasing a vent through finished framing, far less labor on a retrofit. The cost is a moving part that admits air one direction only and wears out over time. It breaks siphonage. It does nothing for positive pressure.

The honest read is that an AAV solves the hard half of venting cheaply and leaves the other half on the table. Use it where running a real vent is the genuine problem, not as the default because it is faster than doing the venting right.

AspectConventional ventAir admittance valve
Admits air (breaks siphonage)Yes, open pipeYes, opens on negative pressure
Relieves positive pressureYesNo, seals against it
Moving parts / wearNoneDiaphragm, wears out
Roof penetrationRequiredNone
Best caseNew work, accessible routingIsland, remodel, hard-to-vent fixture

What can an air admittance valve not do?

An AAV admits air. That is all it does. It does not relieve positive pressure, it does not vent the building, and it is not a replacement for the system's connection to atmosphere. The one-way limit is right there on every spec sheet, but it gets forgotten the moment a vent is inconvenient.

Positive pressure is the gap. When a slug of water falls down a stack, it compresses the air below it and pushes back up the branches. A conventional vent lets that pressure escape to the roof. An AAV seals against it, because positive pressure is exactly what holds the diaphragm shut. So the transient has nowhere to go but back through a trap seal somewhere in the system, and it can blow that seal out into a room.

The building still needs atmospheric venting. The main stack still has to be open to the air, usually through the roof, so the system can both pull air in and push it out. AAVs handle the local fixtures that are hard to vent. They do not replace the vent that keeps the whole system balanced. Stress that on any job that starts leaning on them too hard.

Where AAVs get used

AAVs earn their keep wherever running a conventional vent is the expensive part of the job. The classic case is the kitchen island sink, with no wall behind it to chase a vent up. Right behind it is the remodel: a fixture moved or added where the existing vent is gone and opening the roof and walls to run a new one would blow the budget.

Additions and finished basements are the same story. A basement bath added years after the stack was set often sits far from any existing vent, and an AAV vents it without tearing into the floor above. Wet bars, island prep sinks, and a lavatory stranded in the middle of a remodel all fall in the same bucket.

On larger and commercial work AAVs show up too, including data centers and tenant fit-outs where fixtures land far from the core plumbing and a roof run is impractical. The principle does not change with the building size. The AAV vents the local fixture; the system still needs its connection to atmosphere, and on a big building that means the stack venting must already be there and adequate before anyone leans on AAVs for the strays.

How do you vent an island sink?

You vent an island sink one of two ways, because the thing that makes it hard is the same in both. There is no wall behind the fixture to run a vent up. A conventional vent has to rise above the fixture flood level before it can turn horizontal, and an island has no wall to hide that rise.

The two answers are an AAV under the island, or an island fixture vent, the loop vent, run under the counter and tied back to a vented line. The AAV is faster and needs no roof tie. The loop vent is all hard pipe with no moving parts, which some inspectors and some codes prefer or require.

Which one you use comes down to the adopted code and the AHJ more than preference. Some jurisdictions take the AAV without question. Some prohibit it and the loop vent is your only legal path. Find that out before you rough in the island, not after, because the two roughs are different and you cannot easily convert one to the other once the slab is poured.

The island fixture (loop) vent

The island fixture vent, the loop vent, vents an island sink with hard pipe instead of a valve. The vent leaves the fixture drain, rises as high as it can under the countertop, loops back down below the floor, then runs horizontally and ties into a vent connected to the system. From the side the assembly looks like a P lying on its back: the sink connects at the top, the long lower leg is the vent.

It works because the pipe is sized so the horizontal run never fills with water. The drain and vent run in 2 in pipe even though the sink alone would take 1-1/2 in, so a half inch of air space always rides on top of the flowing water and feeds air back around the loop. Undersize it and the loop floods and stops venting.

The catch is the low point under the floor. The loop dips below the drain, so it collects debris, which is why the assembly needs a cleanout to rod it out. It is more pipe and more careful layout than an AAV. The payoff is no moving part to fail and acceptance in jurisdictions that will not take an AAV. The exact rules live in the adopted code, so size and configure the loop to it.

Are air admittance valves allowed by code?

Sometimes. AAV acceptance varies by jurisdiction more than almost anything else in venting, and that is the single fact to get straight before you design around one. The International Plumbing Code recognizes AAVs and permits them under stated conditions. Other jurisdictions restrict or prohibit them, and historically the Uniform Plumbing Code has been the restrictive side of that line.

This is not a small detail you sort out at inspection. A layout built around an AAV in a jurisdiction that prohibits them gets red-tagged, and the fix is real pipe, real rough-in, real rework. The valve being listed and sitting on the shelf at the supply house does not mean the code where you are working accepts it.

Check the adopted code edition and any local amendments, and when there is any doubt, ask the AHJ before you rough in. Where AAVs are allowed, acceptance comes with conditions on listing, location, access, and what the valve may serve. Hedge every AAV decision to the code that governs the job, because the answer genuinely changes from one jurisdiction to the next.

IPC versus UPC on AAVs

The two model codes split on AAVs, and which one your jurisdiction adopted decides the question. The IPC permits AAVs, referencing the ASSE product standards, with conditions on where and how they are installed and what they vent. Jurisdictions on the IPC, which covers much of the country, generally allow them.

The UPC has historically been far more restrictive. Jurisdictions on it, or on state codes derived from it, have often had no allowance for AAVs at all, or only narrow ones. That is why the same island sink gets an AAV in one state and a loop vent across the line. Neither plumber is wrong. They are working different codes.

Do not assume from the model code alone. States and cities amend the codes they adopt, and some allow or prohibit AAVs by local amendment regardless of the base code. The only reliable answer is the adopted edition plus local amendments plus the AHJ. Confirm all three before you commit a layout to an AAV.

ASSE 1051 and 1050, the listing

AAVs are made to ASSE product standards, and a code that accepts AAVs will require the listed, labeled valve. There are two standards for two jobs. ASSE 1051 covers individual and branch type AAVs, the ones that vent a single fixture or a horizontal branch serving several fixtures. ASSE 1050 covers stack type AAVs, the larger valves made to vent a stack where branches connect on multiple floors.

The distinction matters when you select and size. A branch AAV under a sink is a 1051 device. A valve sitting on top of a stack to vent the whole stack is a 1050 device, and the two are not interchangeable. Put a small branch AAV where a stack AAV belongs and the stack runs under-vented.

Use a valve listed to the right standard for the application, installed within its listing. The listing carries the manufacturer's conditions on height, orientation, and capacity, and those conditions are part of what the code is accepting. Confirm the standard and the listing against the adopted code, because an unlisted valve is not an approved valve no matter how well it performs on the bench.

How high does an air admittance valve have to be?

Height is where AAV installs go wrong, and the rule has two parts. An individual or branch AAV mounts above the trap weir of the fixture it serves, and a common code figure is at least 4 in above the horizontal branch or fixture drain being vented. A stack type AAV mounts higher, with figures commonly around 6 in above the flood level rim of the highest fixture it serves. Treat these as the common code numbers and confirm them against the adopted code and the manufacturer's instructions.

The reason for the height is to keep the valve above the water. Mount it below the trap weir or down in the branch and drainage can reach the diaphragm, foul it, or hold it open. Then it leaks gas or stops sealing. The 4 in is the margin that keeps water off the working part.

There is also a clearance above insulation, commonly cited around 6 in, so blown insulation or batt cannot smother the air intake. The valve has to breathe. Bury the intake and it cannot admit air no matter how high it sits. The exact dimensions vary by code and by valve, so confirm them against the adopted code and the listing rather than carrying one number everywhere.

Accessible, ventilated, and upright

An AAV has to be accessible, because it is a wearing part that will need replacement, and it has to sit in a ventilated space, because it needs room air to admit. Both rules get broken the same way. Somebody seals the valve inside a finished wall with no access panel. Now it cannot breathe and nobody can reach it when it fails.

Accessible means a permanent way to get to it: under the sink in the cabinet, or behind an access panel in the wall. Not glued up inside the framing behind finished drywall. When the diaphragm hardens in fifteen or twenty years, the next plumber has to swap it without a demolition.

Ventilated means the valve draws from open room air, not a sealed cavity and not a space packed with insulation against the intake. And it mounts upright. The diaphragm seals by gravity dropping it shut, so the valve goes vertical, plumb within the tolerance in the instructions, commonly a few degrees off plumb at most. Lay it on its side and the seal does not seat. Accessible, breathing, and plumb. Miss any one and the valve fails early or cannot be serviced when it does.

Sizing the AAV

An AAV is rated for a venting capacity, and you size it to the load it vents the same way you size a vent, by the fixtures or the drainage fixture units on the line. A branch AAV is rated for an individual fixture or a branch up to a stated capacity. A stack AAV is rated higher because it vents a stack. Match the rated capacity to the fixtures served and stay inside the listing.

Undersizing is the quiet failure. Put a small branch valve on a load it cannot admit enough air for, and the trap seals still get pulled, because the valve cannot flow the air the drain demands fast enough. It looks installed and it is still under-venting.

The fixture-unit values and the per-size capacities come from the adopted code and the manufacturer's data, and the two model codes do not assign identical numbers. Pull the capacity from the listing for the valve you are installing and check it against the code that governs the job. The companion DWV venting guide covers drainage fixture units in depth; size the AAV to the same load the line carries.

Do air admittance valves go bad?

Yes. An AAV is a mechanical valve with a sealing diaphragm that cycles open and shut thousands of times, and it wears out. The rubber or elastomer seal hardens and loses its spring over the years, and once it cannot seat cleanly it either leaks sewer gas or sticks. Service life is often quoted around 20 to 30 years, but a kitchen valve living in grease and soap film can foul much sooner.

Two failure modes. Stuck shut and it stops admitting air, so the fixture it vents siphons its trap and starts draining slow or gurgling. Stuck or leaking open and it stops sealing, so sewer gas comes through into the room. Contamination from the drain, grease, soap, debris, even glue or primer that ran down into the valve during install, all speed it up.

This is the whole reason for the access rule. The valve is a part you replace, not a fitting you set once and forget. Plan for the swap when you mount it. A valve you cannot reach is a valve that fails into a wall, and then the smell or the slow drain becomes a demolition job instead of a five-minute change.

Why does an air admittance valve smell of sewer gas?

An AAV smells of sewer gas when the seal is not closing, or when an AAV is doing a job that needed a real vent. Sulfur or rotten-egg odor near the fixture is the classic tell, and it usually means the diaphragm has hardened, fouled, or stuck and is no longer sealing the drain when the fixture sits at rest.

Check the simple things first. Confirm the valve is the source by listening and smelling at it while the fixture is idle. Look for contamination on the seat, grease and soap in a kitchen, or glue and primer that ran in during a sloppy install. If the seal is shot, the fix is a new valve, not a repair, which is why it had to be accessible in the first place.

The other cause is misuse. If the AAV is venting a fixture or a stack the system could not balance, and there is no adequate atmospheric vent, a positive pressure transient pushes gas past the seal or out of a trap, and the smell comes and goes with use elsewhere in the building. That one is not a valve you replace. That is venting that needed a pipe to the roof and got a one-way valve instead.

Positive pressure and the stack

The AAV's blind spot is positive pressure, and on a tall stack that blind spot becomes a design problem, not a nuisance. When a large volume of water falls down a stack it compresses the air ahead of it and drives a positive pressure transient out along the branches below. A conventional vent and the open stack relieve that pressure to atmosphere. An AAV cannot, because positive pressure is what holds it shut.

So a system cannot run on AAVs alone. The stack needs a path to atmosphere to relieve the pressure, normally the stack vent through the roof. On large or tall buildings where positive transients are a known issue, engineered relief is sometimes added, including positive air pressure attenuators (PAPA devices) made to absorb the surge. Those are an engineered solution to the pressure side, not something an ordinary branch AAV does.

The field takeaway is the same every time. AAVs vent the negative side locally. Something else has to handle the positive side and keep the system tied to atmosphere. Where the design leans on AAVs for hard-to-vent fixtures, confirm the stack venting and any relief are adequate for the building before you trust it.

When not to use an AAV

Some places an AAV does not belong, code aside. Not as the building's only venting; the system needs its connection to atmosphere for positive pressure and balance, and AAVs do not provide it. Not in an inaccessible spot, sealed in a wall with no panel, because you have buried a part that has to be replaced. Not in an unventilated or insulation-packed cavity, because the valve cannot draw the air it admits.

Not where the code prohibits it. That one is absolute regardless of how well it would work, and it is the most common reason an AAV install fails. Not undersized for the load, and not the wrong type, a branch valve where a stack valve belongs.

And not as a cover for bad layout. An AAV is the right answer when running a vent is the genuine problem, the island, the stranded remodel fixture. It is the wrong answer when it is just faster than doing the venting right on a job where the real vent was available. Reach for it for the hard case, not the lazy one.

What the inspector checks

On an AAV the inspector starts with whether it is allowed at all under the adopted code, because in some jurisdictions that answer ends the conversation. Where AAVs are accepted, the checklist is short and specific, and it is the same list of things that make the valve actually work.

The inspector looks for a valve listed to the right ASSE standard for the application, 1051 for a branch, 1050 for a stack. They check the height above the branch or the flood level rim, the upright orientation, and whether the location is accessible and ventilated rather than sealed in a wall. They confirm the valve is sized for what it vents and that the system still has adequate atmospheric venting somewhere, because an AAV does not replace the stack vent.

Get those right and the AAV passes. The two that fail most are access, a valve glued into a closed wall, and acceptance, an AAV used where the local code does not allow one. Both are avoidable by checking the code and planning the access before the wall closes.

What to document

An AAV is a part that will be replaced years from now by someone who is not you, so the record matters more than for a fitting that lasts the life of the building. Write down what was installed and why it was the legal choice, so the next plumber and the next inspector are not guessing.

Capture the valve make and model, the ASSE listing it meets, the fixtures or DFU it serves and its rated capacity, the mounting height above the branch or flood level rim, where the access is, and the code basis that made the AAV acceptable on this job. If you used a loop vent instead, record that and why. The access location especially, because a valve nobody can find is a valve nobody can service.

ItemRequirementNote
Valve type and listingASSE 1051 branch or 1050 stackMatch to the application
Acceptance basisAllowed by adopted code and AHJThe first thing that can fail
Mounting heightAbove trap weir and branch, per codeCommonly 4 in for a branch, more for a stack
OrientationUpright, within listed toleranceGravity seats the diaphragm
AccessAccessible cabinet or panelIt is a replaceable part
VentilationOpen room air, clear of insulationValve must breathe to admit air
Capacity and sizingRated for fixtures or DFU servedUndersized still siphons traps
Atmospheric vent presentStack still vented to atmosphereAAV does not replace it

Common mistakes

  • Using an AAV where the adopted code or the AHJ prohibits it.
  • Sealing the valve in an inaccessible or unventilated wall with no panel.
  • Mounting it too low, below the trap weir or the required height above the branch.
  • Relying on AAVs for the whole system with no adequate atmospheric vent for positive pressure.
  • Installing the wrong size or type, a branch AAV where a stack AAV is needed, or a valve undersized for the load.
  • Mounting it on its side or out of plumb so the diaphragm cannot seat.
  • Letting glue or primer run into the valve during install, fouling the seal from day one.
  • Leaving a failed or stuck valve in service instead of replacing it.

Field checklist

0 of 8 complete

Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.

Standards and references

The plumbing code is the first reference and the one that decides whether an AAV is even on the table. The IPC recognizes AAVs and permits them under stated conditions. The UPC and codes derived from it have historically restricted or prohibited them. Which one governs, plus any local amendments, is the controlling question, so confirm the adopted edition and the AHJ before you design around a valve.

The product standards are ASSE 1051 for individual and branch type AAVs and ASSE 1050 for stack type AAVs. A code that accepts AAVs accepts listed, labeled valves made to these standards and installed within the listing. The manufacturer's instructions carry the specific height, orientation, and capacity conditions, and those are part of what the code is accepting.

The numbers in this guide, the 4 in above the branch, the roughly 6 in for a stack or above insulation, the 20 to 30 year service life, are common figures, not universal mandates. Heights, sizing, and acceptance all vary with the adopted code and the listed valve. Hedge every one to the code that governs the job and the manufacturer's data. The rule that does not vary: an AAV vents a local fixture, the system still needs its vent to atmosphere, and the valve has to stay accessible for the day it wears out.

Units and terms

AAVs and island venting carry a handful of terms that show up across code books, spec sheets, and supply catalogs under more than one name, so the same idea reads differently from one document to the next.

AAV
Air admittance valve, a one-way valve that admits air on negative pressure and seals against sewer gas; often called a Studor vent after the original brand
Trap seal
The plug of water held in a fixture trap, commonly about 2 in deep, that blocks sewer gas from the room
Trap weir
The top of the trap outlet, the level water rises to before it spills toward the drain; the AAV mounts above it
Island fixture vent
The loop vent, a hard-piped vent that rises under the counter and loops back below the floor to vent an island sink without an AAV
ASSE 1051 / 1050
Product standards for individual and branch type AAVs (1051) and for stack type AAVs (1050)
Flood level rim
The top edge of a fixture where it would overflow; stack AAV height is referenced to the highest fixture's rim
PAPA
Positive air pressure attenuator, an engineered device that absorbs positive pressure transients an AAV cannot relieve
AHJ
Authority having jurisdiction, the official whose adopted code and rulings control whether an AAV is allowed

Related tools

Tenant fit-outs put sinks far from the core plumbing, making local venting part of the remodel offer; PorchRocket's Ground Control lists office properties with decision-maker contacts available as an add-on.

Next step: Find sink relocation bids

FAQ

What is an air admittance valve?

An air admittance valve, often called a Studor vent, is a one-way diaphragm valve mounted at a fixture drain. Suction from draining water lifts the diaphragm to admit air; the rest of the time it drops shut and seals sewer gas in the line. It vents fixtures where a roof vent is hard to run.

Are air admittance valves allowed by code?

Sometimes, and it varies by jurisdiction. The IPC permits AAVs under stated conditions, while the UPC and codes derived from it have historically restricted or prohibited them. The valve being sold locally does not mean it is approved. Confirm the adopted code edition, local amendments, and the AHJ before you design around one.

How do you vent an island sink?

Two ways, because there is no wall behind the fixture to run a vent up. You use an AAV under the island, or an island fixture vent, the loop vent, run high under the counter and tied back to a vented line. The choice depends on what the adopted code and the AHJ allow.

Do air admittance valves go bad?

Yes. An AAV is a mechanical valve with a sealing diaphragm that wears out, often quoted at 20 to 30 years but sooner in grease and soap. Stuck shut, it stops venting and the trap siphons. Stuck open, it leaks sewer gas. That is why code requires it to stay accessible for replacement.

What is the difference between an AAV and a regular vent?

A conventional vent is an open pipe to the roof with no moving parts that handles both siphonage and positive pressure. An AAV is a one-way valve at the fixture that admits air only and wears out. The AAV saves the roof run, but it does not relieve positive pressure, so the system still needs a vent to atmosphere.

Why does my air admittance valve smell of sewer gas?

A sewer-gas or rotten-egg smell near the fixture usually means the diaphragm has hardened, fouled, or stuck and is no longer sealing at rest. The fix is a new valve, not a repair. If the smell tracks with use elsewhere, the AAV may be covering for missing atmospheric venting on the stack.

How high does an air admittance valve need to be mounted?

Above the trap weir of the fixture, and a common code figure is at least 4 in above the horizontal branch it vents. Stack-type valves mount higher, often around 6 in above the highest fixture's flood level rim. Keep it clear of insulation too. Confirm the exact heights against the adopted code and the manufacturer.

Can a whole house be vented with AAVs?

No. AAVs admit air but cannot relieve positive pressure, so a system on AAVs alone has nowhere to send the surge from a falling stack. The building still needs atmospheric venting, normally the stack through the roof. AAVs handle individual hard-to-vent fixtures, not the system's connection to outside air.

What size air admittance valve do I need?

Size it to the load it vents, by fixtures or drainage fixture units, and stay within the valve's rated capacity. A branch AAV serves a fixture or a small branch; a stack AAV serves a stack. An undersized valve looks installed but still lets traps siphon. Pull capacity from the listing and the adopted code.

People also ask

Codes cited in this guide

This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.