Electrical
Infrared thermography inspection field guide for electrical equipment
Read the heat before the connection fails: load the gear, compare the phases, judge delta-T against NETA, and record the finding with the required repair priority.
Direct answer
Infrared thermography finds abnormal surface heating on energized electrical equipment under load. NETA Table 100.18, as published by Fluke from ANSI/NETA MTS-2007, calls for immediate repair above 15°C over a similar component under similar loading, or above 40°C over ambient air. NFPA 70B (2023), Section 7.4, specifies normal circuit loading and permits at least 40 percent of nominal circuit loading when normal loading is not feasible; record the reference and current with every finding.
On this page
Infrared thermography, and what it catches before the failureHow does heat reveal a bad connection?Emissivity and the reflected-temperature trapHow much load do you need for an IR scan?What delta-T means repair?Phase-to-phase comparison: what makes a valid reference?Worked example: a hot B-phase lug on a 400 A feederSeverity, priority, and what gets fixed whenWhat to scan on an electrical surveyBusway hot joints: which evidence separates the causes?What proves a busway hot-joint repair is ready for service?IR windows and arc-flash safetyThe camera and the qualified thermographerSurvey conditions and steady-state loadWhat goes in the reportBeyond electrical: mechanical, envelope, and roofsHow often should you run an IR survey?After the find: repair and re-scanWhat to documentCommon mistakesField checklistStandards and referencesUnits, terms, and conversionsReview and update recordOpen the related tool for the calculation, checklist, or packet.
FieldOS by AnvilfieldOffline-first FieldOS for job photos, proof packets, property memory, calculations, teams, billing, and owner-ready reports.Key takeaways
- NFPA 70B (2023) Section 7.4 specifies normal circuit loading and permits at least 40% of nominal circuit loading when normal loading is not feasible.
- NETA Table 100.18, as published by Fluke from MTS-2007, calls for repair as time permits at 4 to 15°C above a similar component under similar loading or 11 to 20°C above ambient.
- NETA Table 100.18, as published by Fluke from MTS-2007, calls for immediate repair above 15°C over a similar component under similar loading or above 40°C over ambient.
- EPRI's 2018 thermography guide requires a verified target on the actual component, with emissivity and reflected-temperature compensation accounted for in the measurement.
- Clamp the current before calling a hot phase a bad connection, because an unbalanced load makes the heavier phase run hot honestly.
Infrared thermography, and what it catches before the failure
Infrared thermography is the inspection of electrical equipment with a thermal imaging camera that reads the heat coming off a surface and turns it into a picture you can measure. A loose or corroded connection develops resistance heating under current; an overload increases heating even at a sound connection. The camera sees that heat. You find the bad connection while the gear is still working, not after it has burned itself open and dropped the load.
That is the whole value of the method. It is non-contact and it is done with the equipment energized and loaded, so you catch the defect at the stage where an isolated repair or replacement is still possible, instead of the stage where it is a failed bus and an unplanned outage. EPRI's guide identifies resistance heating as an early warning when load, access, and measurement conditions reveal the defect. Heat is the early warning, and infrared is how you read it.
Resistance faults need current to produce a detectable thermal pattern. EPRI's Infrared Thermography Guide (2018), Section 4.2.7, explains that low load suppresses these patterns, although leakage-current defects can generate heat on energized equipment without a normal operating load. Record an unloaded or lightly loaded resistance-fault survey as incomplete coverage and schedule a loaded return scan.
How does heat reveal a bad connection?
A bad connection makes heat through resistance heating, the I squared R loss. Power dissipated at the joint is the current squared times the resistance of that joint, so current and joint resistance determine the electrical heat generated. EPRI's Infrared Thermography Guide (2018) also identifies conduction, convection, and radiation as the paths that control heat removal and surface temperature. The current-squared term is why heat climbs so fast as load comes up, and why a marginal connection that looks fine at light load lights up under a heavy one.
The catch is that the camera does not measure temperature directly. It measures radiated infrared energy and converts it to a temperature using the surface's emissivity, the fraction of energy a surface radiates compared to a perfect emitter. Paint, insulation, and some oxidized surfaces emit more strongly than polished metal; quantitative readings still need the correct surface settings and a resolved target. Bare, shiny metal has low emissivity, radiates little, and instead reflects the temperature of whatever is around it, including the heater across the room and the thermographer.
Read the same surface at corresponding locations on comparable components. A shiny bus can read cool when it is actually hot, or read hot when it is only mirroring a heat source nearby. NETAWORLD Journal's 2023 thermography explanation identifies reflected energy as a major contributor on polished conductors; a lug is not automatically a suitable target merely because it is a connection.
Emissivity and the reflected-temperature trap
FLIR's guidance on increasing target emissivity gives about 0.95 for most high-quality electrical tape. Use the target material's verified value rather than assigning every painted, oxidized, or insulated surface the same setting. Emissivity describes radiation relative to a blackbody at the same temperature; it does not describe how much heat a surface holds.
EPRI's Infrared Thermography Guide (2018), Section 3.3, treats emissivity and reflected-temperature compensation as measurement inputs. A high-emissivity target must be on the component being measured and in thermal equilibrium with it. Insulation farther down a cable has its own temperature and cannot establish the hidden lug temperature. Install compatible tape, paint, or targets during an electrically safe outage, following equipment instructions.
Reflected apparent temperature is the partner setting. It describes the background radiation reflected into the camera, not simply the air temperature. Compare matched finishes and viewing angles; change the viewing angle to test a suspected reflection. A pattern that moves with the viewing position points to reflected heat. Low emissivity amplifies errors in both the emissivity and reflected-temperature settings.
How much load do you need for an IR scan?
NFPA 70B (2023), Sections 7.4.4 through 7.4.6, requires inspection at normal circuit loading, permits at least 40 percent of nominal circuit loading when normal loading is not feasible, and requires retained loading records. The denominator is nominal circuit loading, not automatically the breaker frame or busway nameplate rating. Record amperes and identify the rating or operating-load basis used for any percentage.
EPRI's Infrared Thermography Guide (2018), Section 5.2.1, explains that resistance heating follows current squared times resistance. At unchanged resistance, doubling the current produces four times the electrical loss at the joint. Surface temperature also depends on cooling, conduction, enclosure construction, and time under load, so do not multiply a measured delta-T by a current-squared ratio and report the result as a verified full-load temperature.
Schedule the survey at representative operating load and allow temperatures to stabilize. Use repeated readings to confirm that the target and reference have settled at the recorded load. EPRI distinguishes steady-state from transient inspections; a recently switched load and a mature thermal pattern are different inspection conditions. A low-load hot spot still warrants action, while a low-load clean image calls for a return scan.
What delta-T means repair?
Delta-T is target temperature minus reference temperature. NETA Table 100.18, published in Fluke's Electrical inspections using thermal imaging application note from ANSI/NETA MTS-2007, provides separate component-reference and ambient-reference action bands. These are suggested maintenance actions, not absolute equipment temperature ratings.
For similar components under similar loading, NETA's published bands are 1 to 3°C for investigation, 4 to 15°C for repair as time permits, and above 15°C for immediate repair. Against ambient air, the corresponding bands are 1 to 10°C, 11 to 20°C, and above 40°C; the additional 21 to 40°C ambient band calls for monitoring until corrective measures are accomplished. Keep the exact reference beside the severity.
A valid component comparison needs matching construction, surface finish, loading, and cooling. Ambient comparison remains useful even when a twin exists, but the two results need not have the same action band. Report both and act on the more urgent valid finding. Also check the equipment's manufacturer temperature limits; a differential table cannot authorize operation above them.
| Delta-T over similar component | Delta-T over ambient air | Suggested action |
|---|---|---|
| 1 to 3°C | 1 to 10°C | Investigate the cause of the temperature difference |
| 4 to 15°C | 11 to 20°C | Plan repair as time allows |
| No separate component-reference band | 21 to 40°C | Continue monitoring until correction is complete |
| Over 15°C | Over 40°C | Repair immediately |
Phase-to-phase comparison: what makes a valid reference?
The odd phase out is a useful starting point for electrical thermography. Corresponding lugs or breaker poles are valid references when construction, measured current, target surface, and cooling conditions match. A hotter phase identifies a thermal difference to diagnose; it does not establish a bad connection by itself.
Comparable phases share an enclosure and operating environment, making them useful references when measured currents and cooling are similar. A 15°C component-to-component rise is still in NETA's 4 to 15°C band; immediate repair begins above 15°C in the published table. Match emissivity and resolve the same target area before assigning a temperature difference.
Measure the current on every phase, using installed metering or qualified electrical measurements under the safety program. The [electrical troubleshooting and multimeter testing guide](/field-guides/electrical/electrical-troubleshooting-multimeter-testing/) covers instrument selection and measurement controls.
EPRI's electrical applications chapter distinguishes high-resistance connections from load-related heating. A localized peak at a joint supports a resistance fault; broad heating along the heavily loaded conductor supports a load issue. Balanced current strengthens the joint diagnosis, but device heat, unequal cooling, and reflections still need to be separated.
Worked example: a hot B-phase lug on a 400 A feeder
Use a 480 V three-phase feeder carrying 280 A per phase on a 400 A rating, or 70 percent of rating. Through an installed IR window with transmission compensation, the example temperatures are A phase at 41°C, C phase at 43°C, B phase at 68°C, and ambient air at 30°C. The lugs have matching target surfaces and steady loading.
Anvilfield calculates a component-reference delta-T of 27°C by subtracting the A-phase temperature from the B-phase temperature. Subtracting ambient instead gives 38°C. NETA's published criteria put 27°C over a comparable component in the immediate-repair band and 38°C over ambient in the monitor-until-corrected band. The references produce different classifications because they answer different comparisons.
The action is immediate repair based on the valid component comparison, with prompt operator notification and an electrically safe isolation arranged under the site procedure. Do not downgrade the finding to the next available outage because the ambient comparison is less severe. Inspect the lug and device for damage, repair or replace as required, and repeat the loaded scan before closing the thermal finding.
| Reading | Value |
|---|---|
| System and load | 480 V three-phase; 280 A per phase; 70 percent of 400 A rating |
| A phase lug | 41°C |
| B phase lug | 68°C |
| C phase lug | 43°C |
| Ambient air | 30°C |
| Delta-T over coolest phase | 27°C (immediate repair band) |
| Delta-T over ambient | 38°C (ambient monitoring band; component comparison controls action) |
Severity, priority, and what gets fixed when
The delta-T sorts a valid finding into a suggested action, and the action is what an owner plans around. Investigation means establishing the cause and follow-up, not silently waiting for the next annual survey. NETA's probable-deficiency band permits repair as time allows; its immediate-repair band requires prompt escalation and safe corrective action.
Two things bend the priority off the raw number. Criticality is the first: the same delta-T on a feeder to a chiller in July or a connection feeding a process that cannot stop justifies acting faster than it would on a spare circuit. The load at the time of the scan is the second: a significant rise at light load deserves prompt attention because increased current raises resistance heating, and a borderline rise found at light load deserves a re-scan at higher load before it is dismissed.
Write the priority as an action and a timeframe, not just a color. Repair immediately, plan a repair as time permits, or monitor until corrective measures are accomplished tells the planner what to do. A find tagged red with no recommended action and no load behind it is a number that gets argued about instead of fixed.
What to scan on an electrical survey
You scan the places where current changes hands, because that is where resistance and heat collect. Bolted lug terminations, crimp and split-bolt splices, breaker line and load connections, fuse clips and fuse bodies, disconnect blades, motor terminal boxes, contactor and starter terminals, transformer connections and bushings, and the joints in busway, especially the bolted joints and the plug-in stab connections where a busway plug clips onto the run.
The body of a conductor rarely fails. The connection is where it happens, so that is where you spend the time. On busway, the joints and the plug-in points are the suspects, and a hot busway joint under load is the same I squared R story as a hot lug, just carrying a lot more current and a lot more consequence when it lets go. Service managers expanding an electrical survey route can use PorchRocket's Ground Control to list commercial buildings by business type and size, then confirm the gear inventory with the operator before pricing.
An installed IR window provides a line of sight without removing the enclosure cover. Opaque metal covers show their own surface temperature, not the internal connection temperature. EPRI's guide distinguishes this indirect heating from direct target measurement. Cover removal and subsequent scanning follow the electrical safety program, with qualified personnel, established boundaries, and task-specific PPE.
Busway hot joints: which evidence separates the causes?
Locate the exact joint pack, phase, plug-in connection, and busway run before assigning a cause. EPRI's electrical applications chapter distinguishes localized connection heating from load-related heating and from heat conducted to an exterior enclosure. On enclosed busway, a hot housing locates an investigation area; it is not a direct measurement of an inaccessible joint.
EPRI's Section 5.2.1.2 calls for investigating or monitoring even a small abnormal exterior pattern because the internal connection can be much hotter. Do not use a low housing delta-T to clear the hidden joint against the direct-component severity bands.
Record simultaneous phase currents, upstream and downstream loading, adjacent joint temperatures, room air temperature, fan or cooling status, and any recent load transfer. Compare equal joint types with matching finishes and viewing geometry. On a data center route, a redundant-path transfer changes the load basis, so the before and after temperatures must carry the path state as well as amperes.
For load-normalized trends, group scans by comparable current and cooling conditions and plot each joint's rise against its recorded current. Keep the original readings with any calculated index. EPRI's current-squared loss relationship explains why load matters; it does not supply a universal temperature correction or contact-resistance value from a thermogram. Use the [busway installation guide](/field-guides/electrical/busway-busduct-installation/) to reconcile joint identity, orientation, supports, and the installed product.
| Possible cause | Evidence to collect | Repair decision |
|---|---|---|
| High-resistance joint | Localized joint peak; comparable current; elevated isolated joint resistance; damaged or contaminated contacts | Inspect isolated joint; repair or replace under its manufacturer procedure |
| Unequal phase or parallel-path loading | Measured current imbalance and heating extending along conductors | Resolve load or current-sharing cause; inspect any localized joint anomaly separately |
| Cooling or enclosure effect | Nearby equipment also warmer; changed airflow, ambient, obstruction, or enclosure condition | Restore specified cooling and repeat the comparison at matched load |
| Reflection or measurement error | Apparent hot spot shifts with angle; unmatched finish; wrong window compensation | Correct measurement conditions and reacquire the target |
| Heat-damaged insulation or joint pack | Discoloration, pitting, corrosion, cracked insulation, or altered clamping parts after isolation | Apply manufacturer replacement criteria; do not close the job by retorquing alone |
What proves a busway hot-joint repair is ready for service?
Build the repair evidence in two stages: isolated acceptance and loaded thermal verification. Schneider's I-Line II Rev. 02 maintenance instructions call for comparing insulation resistance with earlier records before re-energizing, and recommend an infrared check after the repaired busway reaches stable operating temperature. [Insulation resistance](/field-guides/glossary/insulation-resistance-ir/) checks insulation condition; it does not establish low resistance across a current-carrying joint.
Vertiv's busway maintenance scope lists ductor testing across joints separately from insulation-resistance testing. Measure contact resistance across the isolated repaired joint using the manufacturer or project test procedure and comparable joints as references. Record instrument, test current, lead positions, measured resistance, component temperature, and the exact test span.
Megger's A Guide to Low Resistance Testing, DLRO_AG_en_V04 (2018), shows how parallel current paths change the measured resistance. Keep parallel current paths out of a joint measurement before accepting the result as that joint's contact resistance. If a parallel path remains, identify the measurement as a combined-path result and use an approved method that isolates the joint's contribution. Apply the product's acceptance criteria rather than inventing one micro-ohm limit for every busway family.
The closure packet includes as-found photographs, damage and contamination findings, replaced part identities, assembly and torque records, accepted electrical test results, and paired before and after thermograms with load and cooling conditions. Schedule the loaded verification before closing the thermal work order. The [busway receiving and megger QA guide](/field-guides/datacenter/busway-receiving-megger-qa/) covers the insulation-test record that accompanies this service-stage repair.
| Evidence gate | Acceptable record | Who uses it |
|---|---|---|
| Isolated mechanical repair | Damage disposition, approved replacement parts, correct assembly and recorded manufacturer torque | Repair supervisor |
| Isolated electrical checks | Insulation resistance and joint contact resistance accepted against their separate criteria | Testing lead and commissioning authority |
| Re-energized thermal check | Stable representative load; matched references and camera settings; abnormal pattern resolved | Thermographer and operator |
| Return to routine monitoring | Closed cause, accepted tests, updated baseline and next survey date | Maintenance planner |
IR windows and arc-flash safety
An infrared window is a permanently installed port, made of an IR-transparent crystal or polymer, that lets you scan visible internal connections without opening the enclosure. Fluke identifies avoided cover removal as a way to reduce inspection risk. The window does not set the arc-flash boundary or guarantee that the operator stands outside it.
NFPA 70E (2024), Section 130.2(C), permits thermography without an energized electrical work permit when the restricted approach boundary is not crossed and a qualified person uses the required safe work practices and PPE. That exemption does not authorize cover removal or other tasks automatically. Assess the complete task, equipment condition, shock exposure, and arc-flash exposure before work.
EPRI's guide, Section 3.3.5.2, requires compensation for an external IR window's attenuation and re-emission. Record the window identity, transmission setting, window temperature, camera and lens, viewing angle, and target coverage. A dirty window, blocked line of sight, or unresolved target leaves an inspection gap. The [grounding electrode system and bonding guide](/field-guides/electrical/grounding-electrode-system-bonding/) covers the enclosure bonding that supports the equipment safety program.
The camera and the qualified thermographer
ASNT's explanation of SNT-TC-1A makes certification the employer's responsibility under an approved written practice. The practice defines the training, experience, examinations, and assigned duties for each level. A course attendance certificate alone is not employer certification. Record the thermographer's authorization for the equipment, procedure, and analysis being performed.
EPRI's guide separates detector resolution, spatial resolution, measurement spot size, thermal sensitivity, and focus. Choose the lens and working distance so the small lug or joint fills the manufacturer's required measurement area; detector pixel count alone is not a universal camera minimum. An out-of-focus image mixes a small hot target with cooler surroundings and understates its peak temperature.
Before the first image, the thermographer sets emissivity and reflected apparent temperature for the surfaces being read, and confirms the camera's temperature range covers what is expected. Those settings are the difference between a number you can put in a report and a number that is off by tens of degrees.
Survey conditions and steady-state load
A delta-T is only as good as the conditions it was taken in, so the survey records the conditions, not just the temperatures. The equipment should be at a steady-state load, meaning it has carried its load long enough to reach a stable temperature, not just switched on. A connection caught mid-warmup reads lower than its real steady value.
Ambient temperature gets recorded because the over-ambient criteria depend on it directly. Outdoors, wind is the quiet enemy: even a light breeze convects heat off a hot connection and pulls the apparent temperature down, so a real defect can read as a minor one or vanish. Note the wind, and treat outdoor over-ambient numbers on a windy day as understated. Sun load does the opposite, heating surfaces that carry no fault at all, so account for solar gain on outdoor and rooftop gear.
Record current per phase and the operating-load basis alongside every temperature comparison. NFPA 70B (2023), Section 7.4.6, requires loading characteristics to be retained for future reference. Compare repeat surveys at matched load, steady state, ventilation, target surface, and camera geometry; a cooler image at a reduced load does not prove that the repair succeeded.
What goes in the report
A thermographic report that an owner can act on pairs a thermal image with a normal visible-light photo of the same component, so the repair crew knows exactly which lug to open. Each find carries the location, the equipment and component identified, the load at the time of the scan, the measured temperatures and the delta-T, the reference used (similar component or ambient), the severity, and the recommended action with a priority.
The visible photo is not a formality. A thermogram alone shows a hot blob with no context, and the crew sent to fix it cannot tell phase A from phase C, or one identical breaker from the next in the row. The paired visible image, with the hot spot marked, is what makes the find repairable by someone who was not standing there when it was shot.
The other half of a good report is the baseline. The first survey of a piece of gear becomes the reference the next one is compared against, so the same component scanned the same way a year later shows whether it is stable, improving after a repair, or trending hot. Without a repeatable baseline, every survey starts from zero and the trend, which is often the real signal, is lost.
Beyond electrical: mechanical, envelope, and roofs
The same camera and the same physics find heat anywhere a problem makes it, so a thermographer rarely scans only electrical gear. On the mechanical side, a failing bearing runs hot, a misaligned coupling or an overloaded motor shows up as heat, and so do a slipping belt, a blocked cooling passage, or an overheated gearbox. The method is the same: find the component running hotter than its healthy twin or its own history.
On the building side, infrared reads missing or wet insulation, air leakage, and moisture, because wet and dry materials hold and release heat differently. A roof moisture survey uses exactly this: trapped water under the membrane stores the day's heat and releases it slowly after sunset, so a scan in the right evening window shows the wet areas glowing against the dry roof. That is its own discipline, with its own timing and confirmation by core sample or capacitance meter, and it overlaps with electronic leak detection on low-slope roofs.
The point for an electrical tech is that the instrument is multi-use, and the discipline of load, emissivity, reflected temperature, and a measured reference carries across every one of those applications. The targets change. The method does not.
How often should you run an IR survey?
NFPA 70B (2023), Table 9.2.2, sets maximum infrared thermography intervals of 12 months for equipment Conditions 1 and 2 and 6 months for Condition 3 where manufacturer recommendations are unavailable and equipment failure presents unacceptable personnel or environmental risk, subject to the interval adjustments in that edition's Chapter 9. The 2023 publication is the Standard for Electrical Equipment Maintenance, replacing the earlier recommended-practice status. Identify the edition used by the facility and document the condition assessment, manufacturer instructions, and interval decision in the maintenance program.
Keep insurer loss-prevention recommendations and contract survey obligations with the maintenance schedule. They establish the facility's additional scope and reporting obligations. Record inaccessible targets and low-load exclusions so the owner can arrange the missing coverage rather than treating a route completion date as proof that every connection was inspected.
There is also the acceptance scan. New gear gets an infrared survey once it is energized and under load during commissioning, which catches the connections that were never torqued right before the building is occupied. That belongs in the commissioning sequence, and on a data center or mission-critical job it is part of the power QA covered in the [data center electrical commissioning guide](/field-guides/datacenter/datacenter-electrical-commissioning-power-qa/), where the plant is proven under load before the critical load arrives.
After the find: repair and re-scan
Finding the hot connection is half the job. Establish an electrically safe work condition, isolate all supplies and backfeeds, lock out, and verify absence of voltage before disturbing the connection. Follow the equipment's maintenance procedure and record the as-found damage before cleaning or disassembly. The [electrical lockout and tagout guide](/field-guides/electrical/lockout-tagout-electrical-safety/) and [termination torque QA guide](/field-guides/electrical/termination-torque-qa/) cover isolation and controlled joint assembly.
Schneider Electric's I-Line II Indoor Busway bulletin 45123-961-01, Rev. 02 (April 2020), requires factory-built replacement devices for badly discolored, corroded, pitted, or heat-damaged joints and terminations. It warns that overheating and retorquing can damage insulators. Follow the model-specific cleaning, replacement, hardware, and torque instructions; polishing plated contacts or adding antioxidant is not a universal repair.
Re-energize only after the required inspections and electrical tests are accepted, then return to representative load and stable temperature. Compare the same target and reference under matched conditions and check manufacturer temperature limits. A healthy component can remain warmer than ambient or a neighbor; closure means the abnormal pattern and cause have been resolved, not that every delta-T is zero.
What to document
Every find becomes a record, and the record is what survives the technician leaving and the next survey happening. Capture enough that someone a year out can locate the component, understand the severity, reproduce the comparison, and confirm whether it was fixed.
| Field to record | Why it matters |
|---|---|
| Equipment and component | Locates the exact lug or device for the repair crew |
| Load percent and current per phase | Establishes loading and the basis for repeat comparisons |
| Reference temperature and type | Similar component or ambient, the basis for the delta-T |
| Delta-T | The measured rise that drives the severity |
| Severity and priority | States investigation, planned repair, monitored correction, or immediate repair, with a deadline |
| Recommended action | Tells the crew what to do, not just what is wrong |
| Thermal plus visible image | Makes the find repairable by someone who was not there |
| Measurement setup and conditions | Records target finish, emissivity, reflected apparent temperature, window compensation, viewing position, cooling, and load stability |
| Repair and closure evidence | Links isolated inspection, part replacement, accepted electrical tests, and the loaded verification scan to the original finding |
Common mistakes
- Treating a low-load clean scan as proof that resistance faults are absent.
- Ignoring emissivity and reflected temperature, then reporting a shiny bus that is reflecting, not hot.
- Comparing dissimilar components instead of phase-to-phase or to a true twin.
- Not recording the load, which leaves the delta-T impossible to judge or compare later.
- Calling a hot phase a bad connection without clamping the current to rule out an unbalanced load.
- Opening an energized panel without the arc-flash PPE and the qualified-person controls.
- Shooting out of focus, which reads the hot spot low and hides a real defect.
- Skipping the re-scan after repair, so nobody knows whether the fix actually took.
Field checklist
Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.
Standards and references
NETA's thermographic criteria distinguish similar-component rise from ambient-air rise. This guide identifies the public Table 100.18 source as ANSI/NETA MTS-2007, reproduced by Fluke in its 2010 application note. Use the facility's specified testing edition in the report; retain the reference basis and the actual action criteria with the findings.
NFPA 70B (2023) is a maintenance standard, and its Section 7.4 and Table 9.2.2 provide the load-record and interval requirements described here for that edition. NFPA 70E (2024) addresses electrical work practices, risk assessment, boundaries, and PPE. The [arc-flash study and labels guide](/field-guides/electrical/arc-flash-study-labels/) explains the equipment information used to plan the scan.
ASNT's SNT-TC-1A framework is employer-based qualification and certification under a written practice. EPRI's Infrared Thermography Guide (2018) supplies the measurement physics, indirect-heating distinctions, and window-compensation methods used here. Manufacturer maintenance instructions control the actual joint repair and return-to-service tests.
Units, terms, and conversions
Infrared thermography goes by a few names and the readings come with their own vocabulary, so the same idea reads differently across a camera menu, a report, and a standard.
It is called IR thermography, thermal imaging, or an infrared survey. Temperatures are in degrees C or degrees F, the rise is the delta-T, and the camera's sensitivity is its NETD. The two settings that make a reading honest are emissivity and reflected apparent temperature, and an IR window provides a view through a closed enclosure.
- Delta-T
- The temperature rise of a hot component over a reference, either a similar component under similar load or the ambient air
- Emissivity
- Radiation emitted by a surface relative to a blackbody at the same temperature, from 0 to 1; finish, wavelength, and viewing angle determine the appropriate value
- Reflected apparent temperature
- The temperature of the surroundings that reflects off the target and into the camera, which corrupts the reading on low-emissivity metal
- IR window
- A permanently installed infrared-transparent port that lets you scan an energized enclosure without opening it
- NETD
- Noise-equivalent temperature difference, a measure of camera thermal sensitivity; it does not establish absolute temperature accuracy
- Thermographer level
- Employer-assigned thermography qualification and duties under the approved SNT-TC-1A written practice
Review and update record
Reviewed by Anvilfield on 2026-11-06. Corrected reference-specific severity, the worked feeder action, nominal-load wording, emissivity targets, IR-window safety, maintenance-standard status, and repair closure. Added busway diagnosis and return-to-service evidence. Final review corrected monitoring duration, phase diagnosis, heat-transfer and sensitivity definitions, and parallel-path test interpretation; expanded exterior-busway and closure records.
How to cite this page: Anvilfield, Infrared thermography inspection field guide for electrical equipment, 2026, https://anvilfield.com/field-guides/electrical/infrared-thermography-inspection/.
FAQ
What does an infrared inspection find?
An infrared inspection finds abnormal surface heating from high-resistance connections, failing breaker poles, overloaded conductors, and bad busway joints. EPRI's Infrared Thermography Guide (2018) separates connection resistance from load imbalance, leakage current, and device heating. On mechanical equipment, thermal patterns also identify hot bearings and motors.
How much load do you need for an IR scan?
NFPA 70B (2023), Section 7.4, specifies normal circuit loading and permits at least 40 percent of nominal circuit loading when normal loading is not feasible. Record actual current and the nominal-load basis. Low-load hot spots remain findings; a clean low-load scan needs a loaded follow-up.
What delta-T means repair?
NETA Table 100.18 as published by Fluke from MTS-2007 calls for immediate repair above 15°C over a similar component under similar loading, or above 40°C over ambient. The 4 to 15°C component and 11 to 20°C ambient bands call for repair as time permits. The 21 to 40°C ambient band calls for monitoring until correction.
What is an IR window?
An IR window is an infrared-transparent port that gives a view of internal components without removing the enclosure cover. Use camera-specific transmission compensation. The window reduces the need to expose energized parts; the electrical risk assessment establishes boundaries and PPE.
Why does a shiny bus bar read the wrong temperature?
Bare, shiny metal has low emissivity, so reflected radiation strongly affects the reading. A shiny bus can read cool when it is hot, or hot when it reflects a nearby heat source. Measure a verified target on the actual component and match surface finish, settings, and viewing angle for comparisons; a nearby painted cable is not the lug temperature.
How often should electrical equipment be scanned with infrared?
NFPA 70B (2023), Table 9.2.2, gives maximum 12-month infrared intervals for Conditions 1 and 2 and 6-month intervals for Condition 3. Chapter 9 also provides interval adjustments. Its interval provision applies where manufacturer recommendations are unavailable and failure presents unacceptable personnel or environmental risk. Record the facility's edition, condition assessment, manufacturer instructions, and interval decision.
What do I do after infrared finds a hot connection?
Assign the action from the valid reference comparison, notify the operator, and establish an electrically safe work condition before repair. Inspect damage, follow manufacturer cleaning or replacement instructions, and document assembly and electrical test results. Re-scan at comparable stable load to verify that the abnormal pattern is resolved.
Is phase-to-phase comparison better than comparing to ambient?
A phase comparison is useful when construction, current, surface finish, cooling, and measurement geometry match. Measure current before diagnosing the hotter phase. Record ambient rise separately; a valid component comparison can demand immediate repair even when the ambient rise is in a lower action band.
Can I do an infrared survey without opening the panel?
Yes, where installed IR windows provide a clear view of the required targets. Compensate for window transmission and document blocked or unresolved connections. A closed cover does not establish the operator's distance from an arc-flash boundary; use the electrical safety program to set task controls.
Does an insulation resistance test prove a busway hot joint is repaired?
No. Insulation resistance checks insulation between conductors and ground; a joint contact-resistance test checks the current-carrying connection. Close the repair with manufacturer acceptance of the isolated work and electrical tests, followed by a loaded thermal comparison at stable temperature.
People also ask
Codes cited in this guide
This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.
Sources checked
- Fluke, Electrical inspections using thermal imaging, application note 3358415B (2010) Page 3 publishes NETA MTS-2007 Table 100.18; pages 1 and 2 describe contact damage and retightening limitations. Opened with curl 2026-11-06. Reopened with curl for final review on 2026-11-06.
- EPRI, Infrared Thermography Guide, report 3002012582 (November 2018) Sections 3.3, 4.2.7, 4.3.8, and 5.2 verify compensation, load, steady state, indirect heating, and fault mechanisms; Sections 1.5.5 and 3.3.6 distinguish thermal sensitivity and measurement capability. Opened and reopened with curl 2026-11-06.
- Schneider Electric, I-Line II Indoor Busway, 45123-961-01 Rev. 02 (April 2020) Maintenance section: heat-damage replacement, torque precautions, insulation-resistance comparison, and stable-temperature infrared verification. Opened with curl 2026-11-06. Reopened with curl for final review on 2026-11-06.
- FLIR, Use Low-Cost Materials to Increase Target Emissivity Electrical-tape emissivity and the importance of an opaque, appropriate target. Opened with curl 2026-11-06. Reopened with curl for final review on 2026-11-06.
- NETAWORLD Journal, Using Thermographic Surveys to Monitor Condition (2023) Publisher explanation of emitted and reflected radiation and low-emissivity conductors. Opened with curl 2026-11-06. Reopened with curl for final review on 2026-11-06.
- ASNT, Explaining Employer-Based Certification Programs (2020) Employer certification, written practice, training certificates, and assigned responsibilities. Opened with curl 2026-11-06. Reopened with curl for final review on 2026-11-06.
- ASNT, 10 Key SHALLS of SNT-TC-1A (2023) Employer written-practice establishment and Level III approval. Opened with curl 2026-11-06. Reopened with curl for final review on 2026-11-06.
- NFPA, NFPA 70B first-draft meeting agenda, March 2024 PDF page 130 (Public Input 92) reproduces 2023 Sections 7.4.4 through 7.4.6; PDF page 142 reproduces the interval provision and 12/12/6-month thermography row. Revision markings checked visually; proposed revisions are not treated as adopted requirements. Opened and reopened with curl 2026-11-06.
- NFPA, NFPA 70E first-draft public-input responses, A2026 cycle Public Input 2 reproduces the existing thermography permit exemption in 130.2(C). Proposed renumbering is not treated as adopted text. Opened with curl 2026-11-06. Reopened with curl for final review on 2026-11-06.
- Vertiv, Busway Maintenance and Thermography Manufacturer service scope distinguishes ductor tests across joints from phase-to-phase and phase-to-ground insulation-resistance tests. Opened with curl 2026-11-06. Reopened with curl for final review on 2026-11-06.
- Megger, A Guide to Low Resistance Testing, DLRO_AG_en_V04 (2018), manufacturer guide hosted by TRS-RenTelco Pages 12 and 13 cover joint tests and separate current/potential leads; pages 26 through 32 cover temperature, test conditions, and parallel-path effects on resistance readings. Opened with curl 2026-11-06.