TEV vs ultrasound for switchgear partial-discharge surveys

Pair TEV and ultrasound, separate noise from discharge, and turn repeatable condition evidence into a dated diagnostic action.

Partial dischargeSwitchgearTEVUltrasoundCondition monitoring

Direct answer

Use TEV and ultrasound together where their signal paths permit. Interpret magnitude, pulse rate and pattern with background and operating conditions; a single dB reading does not establish switchgear condition.

On this pageWhat does a switchgear partial-discharge survey tell you?Where do TEV and ultrasound work best?What are the TEV partial-discharge limits?How do you distinguish PD from electrical and acoustic noise?How do you make PD measurements repeatable?Can you survey energized switchgear with the doors closed?Which PD findings need action, and what makes a trend credible?Worked example: low TEV with positive ultrasound evidenceHow often should a PD survey be repeated?Which follow-up tests confirm a suspected source?How much does a switchgear PD survey cost, and how long does it take?How do you scope a repeatable switchgear survey program?Field checklist: from first reading to closed findingSources and how to cite this page
Need to run this in the field?

Open the related tool for the calculation, checklist, or packet.

What does a switchgear partial-discharge survey tell you?

Use transient earth voltage (TEV) and ultrasound together for switchgear partial-discharge surveys: TEV detects fast electrical pulses on grounded metal enclosures, while ultrasound detects discharge sound through an available air path or a suitable contact sensor. EA Technology's UltraTEV Plus² manual V13.05.00 uses pulse magnitude, repetition rate and pattern evidence to interpret activity; a single dB reading does not establish switchgear condition. Record background noise, sensor position, phase reference, operating state, temperature and humidity so each finding can be repeated and assigned a follow-up action. [S1]

Partial discharge is localized electrical discharge that does not completely bridge the insulation between electrodes. Detection establishes signal evidence; localization identifies its origin; diagnosis identifies the defect; the operating decision assigns the response. Keep those four conclusions separate in the report. [S1]

A satisfactory infrared inspection does not clear an insulation-discharge finding: resistive heating and PD are different condition evidence. Place the survey within the medium-voltage switchgear maintenance program, with a defined route from finding to diagnostic work.

Define the asset and operating state before choosing the sensor

Mark bus, breaker, cable and instrument-transformer compartments on photographs and the electrical one-line. Record manufacturer, model, insulation medium, nominal and available measured operating voltage, breaker position, accessible surfaces and ownership boundary. Define the surveyed substation by asset IDs, including inaccessible compartments; an open breaker alone does not establish isolation throughout the lineup. [S4, S14]

Where do TEV and ultrasound work best?

Select the sensor from the path between the suspected source and the accessible measurement point. Internal electromagnetic emissions can escape enclosure discontinuities and couple onto exterior metal; airborne ultrasound needs an air passage, while a contact probe needs effective structural coupling. This table is Anvilfield’s method synthesis. [S1, S8]

Method applicability
Method and reported quantityBest survey applicationRequired signal pathMain blind spot or interferenceNext evidenceBasis
TEV, dBmV and pulses per cycleElectromagnetic PD screening of metal-enclosed switchgearSensor square to accessible grounded enclosure; internal emissions escape at a joint, gasket or other discontinuity before coupling onto the outer surfaceExternal RF on metalwork; shielding and geometry; low pulse counts below instrument floorBackground-metal comparison, waveform, phase plot and localizationS1 §§3.6 to 3.10, 4.1
Airborne ultrasound, UTP2 dBµVSurface discharge with an existing air passage from the compartmentAcoustic path through existing opening or approved acoustic provision; microphone stays clear of plantSealed compartment; leakage noise; changed microphone angle or distanceAudio plus phase pattern and repeat scan at the same pointS1 §§3.10.2, 4.3
Contact ultrasound, UTP2 dBµVEnclosures without an effective air passage, where structure transmits the soundRepeatable contact with the relevant tank or panelExtra enclosure layer between probe and source tank; poor coupling; movement; rain; vibrationCoupling check, alternative point and cross-method evidenceS1 pp. 62 to 64
Acoustic imaging, FLIR Si2 PD-capable modelLocating a sound source with an available acoustic viewAcoustic path, documented distance and orientationReflections, masking and incorrect voltage/component/distance inputsStored image, PRPD, parameter record, second viewS9
UHF, instrument-specific levelGIS or other equipment with a suitable window, antenna or installed sensorVerified electromagnetic coupling through an appropriate provisionMetal shielding; unsuitable port; external transmittersSensitivity check and specialist localizationS1 §4.4; S8
HFCT, calibrated system-specific outputCable or termination discharge investigationSuitable accessible earth conductor and approved sensor arrangementInstallation geometry and cable-path attenuation; inaccessible earthCable-specific analysis and localizationS1 §4.2; S8
Charge-based PD, apparent charge in pCControlled apparatus test under a specified test planCalibrated electrical measuring circuitExternal interference; test arrangement differs from operating surveyApparatus-specific acceptance and recorded voltage sequenceS7, IEC 60270:2025 ed. 4

Why the two methods can disagree

A low TEV result can coexist with surface-discharge sound, while loud acoustic activity can come from vibration or leakage. EA’s UTP2 manual V13.05.00, §4.3.5, excludes contact-probe use where another layer separates the probe from the tank containing the suspected source. Mark that compartment unassessed by contact ultrasound; an outer cabinet reading cannot clear the inner tank. [S1, S4]

Identify the insulation around the component separately from the breaker interruption medium. A vacuum breaker can occupy an air-insulated lineup; its nameplate does not establish external acoustic access to the sealed interrupter. High-frequency current transformer (HFCT) and ultra-high-frequency (UHF) follow-up likewise require suitable earth-conductor or sensor arrangements, not simply an available instrument. [S1, S8]

What are the TEV partial-discharge limits?

Use the instrument's magnitude, pulse rate and pattern interpretation together with equipment condition and failure consequence. EA Technology's UltraTEV Plus² manual V13.05.00 specifies a 10 dBmV minimum pulse-count level, so a zero counter below that level does not establish the absence of partial discharge. The numerical boundaries below describe instruments and measurement frameworks, not universal switchgear acceptance bands. [S1]

Numerical settings and limits
Authority and editionQuantityVerified value or ruleInterpretation
EA UTP2 manual V13.05.00, June 17, 2025, p. 84TEV measurement range0 to 60 dBmVInstrument range, not acceptable asset range
SameTEV pass band3 to 80 MHzSensor/system frequency response; different tools can capture different interference
SameTEV resolution / stated accuracy1 dB / ±1 dBSmall changes require repeatability evidence; this is not total field uncertainty
SameMinimum pulse-count level10 dBmVCounter behavior below this level cannot clear an asset
Same, p. 85Airborne ultrasound range-7 to +71 dBµVUTP2 signal level, not airborne sound-pressure dB
SameAirborne center frequency40 kHzA sensor characteristic, not a universal optimum for every acoustic survey
Same, §3.12.2, pp. 19 to 20Alarm settingsTEV red/amber and ultrasonic red levels are user-adjustableSave actual settings; a color is not a universal equipment limit
Same, §7, p. 83Calibration interval12 monthsInstrument calibration, distinct from asset survey interval; function check is not calibration
EA phase-reference application note v1, September 17, 2021Recorded survey data window described by that note10 secondsLock to actual system frequency before recording; identify acquisition settings for later firmware
IEC 60270:2025, ed. 4Charge-based measurement scopeAC up to 500 Hz or DCDefines measurement framework, not a handheld TEV alarm limit
IEC TS 62478:2016, ed. 1Electromagnetic and acoustic measurement scopeHF/VHF/UHF and acoustic methods; sensitivity/calibration and location includedUse this framework for nonconventional methods, not as a dB conversion table
FLIR Si2a, T810671-AA-en-US web manualNorm / High / Ultr filter bands10 to 65 / 20 to 65 / 30 to 130 kHzModel/mode-specific choices; Norm unavailable in Leak detection mode; record selected filter
FLIR Si2 T810637-AG web manualDisplayed normalized SPL bandwidth20 kHzManufacturer processing convention; retain original settings

Keep dBmV, dBµV, dB SPL and pC separate

TEV dBmV references 1 mV; UTP2 ultrasonic dBµV describes its transducer chain; acoustic SPL uses a sound-pressure reference. Apparent charge in pC belongs to a calibrated electrical measuring arrangement. Do not subtract ultrasound from TEV or convert an enclosure TEV reading directly into apparent charge. [S1, S7, S9]

Where manufacturers and standards differ

EA's narrowband airborne sensor and FLIR's selectable acoustic filters describe different systems; preserve each configuration on repeat visits. FLIR's acoustic severity assessment uses distance, voltage and component type, whereas UTP2 interpretation combines TEV magnitude and repetition rate. Neither manufacturer's severity label transfers directly to the other. [S1, S9, S10]

The UTP2 manual defines its short-term TEV Severity index as magnitude in millivolts multiplied by pulses per cycle, not displayed dBmV multiplied by pulse count. Retain both inputs separately. Its adjustable alarm thresholds also mean that a green display records a configured response, not apparatus acceptance. [S1, §§3.9 and 3.12.2]

How do you distinguish PD from electrical and acoustic noise?

Use phase-resolved partial-discharge (PRPD) plots with localization and noise checks: interference synchronized to the supply can also appear phase-related. EA’s UTP2 manual V13.05.00, §4.3.1, describes discharge audio as crackling; compare that sound with the stored phase plot, background and source location. The instrument shifts ultrasound into the audible range for headphones; retain the original audio files for review. EA identifies radio transmissions, overhead insulators and transformer bushings as external electromagnetic sources; safely accessible, unrelated metalwork provides a useful background comparison. The matrix below is Anvilfield’s diagnostic synthesis. [S1, S2]

Noise-source matrix
Suspected sourceAffected channelClueDiscriminating checkDispositionSource
External radio transmissionTEV/UHFSimilar activity on unrelated metal; narrowband RF where spectrum is availableRecord background-metal result; use supported UHF tuning or TEV localizationLabel external interference when supported; preserve recordingsS1, S2
Variable-speed drive or UPS interferenceElectromagnetic channelsActivity changes with plant operating state or appears across multiple panelsCorrelate timestamped operating log with longer monitoring; do not switch equipment merely to improve a readingSeparate operating-state groups in analysisS6
Remote corona on bushing or overhead insulatorTEV/UHF and sometimes acousticSignal appears at several nearby surfacesLocate spatial source and compare background referencesRecord external source separately from internal switchgear suspicionS1 §4.1.1
Air or gas leakageAirborne acousticBroadband hiss or source near pneumatic equipmentLocalize acoustic source; compare phase pattern and signal at the switchgear pointClassify the acoustic source before assigning electrical severityS1 acoustic method; S10 leak/PD modes; Anvilfield synthesis
Rain or transformer vibrationContact ultrasoundPanel vibration can imitate discharge soundRecord weather and vibration; repeat with stable probe and an alternative supported methodMark contaminated reading; do not call it PD from sound aloneS1 p. 64
Probe motion or poor couplingContact ultrasoundSignal changes as probe moves or is pressedSecure probe; document surface/coupling; repeat same positionReject unstable acquisition and reacquireS1 pp. 62 to 64
Phase-reference driftTEV/acoustic phase plotsPattern smears across phase during captureRe-establish system-frequency lock and record againReplace invalid pattern classification with locked captureS3
Localized discharge candidateOne or more methodsRepeatable location with mechanism-consistent phase/audio/waveform evidenceRepeat at same point, compare neighboring/background points, localizeOpen condition finding with supporting files and follow-up testS1, S4

What distinguishes surface, internal and floating-metal discharge?

Name the suspected mechanism separately from confidence and action priority. FLIR groups surface/internal discharge in one PRPD class, so its camera label alone cannot identify the defective component. NETA World’s Fall 2020 account explains that poor-contact and floating-metal patterns can resemble each other, move in phase and mask weaker sources. [S9, S13]

Mechanism and confirmation
Suspected mechanismPhysical distinctionEvidence that advances the findingFollow-up that resolves the uncertaintyBasis
Surface dischargeActivity along an insulation surfaceLocalized acoustic evidence with a usable path; humidity-labeled recordsIsolated inspection for contamination, tracking or damaged insulation; verify after approved correctionS1; S4; S5
Internal dischargeActivity within insulation rather than an exposed surfaceLocalized TEV and mechanism-consistent phase/waveform evidenceApparatus-specific controlled PD test and component investigationS1; S3; S7
Poor contact or floating metalPoor HV connection versus an electrically floating conductive part in an electric fieldSimilar PRPD patterns can arise from either mechanism; flat broad event bands and phase movement support further localizationLocate and inspect the component; verify intended contact/bonding and resurvey after repairS13; S12

Verify the phase reference before naming the defect

EA’s 2021 phase-reference note shows two captures at the same 11 kV cable box: an unlocked capture resembles noise, while a locked capture reveals an internal-void-type pattern. Save reference source, frequency, lock state and capture duration; restore lock before repeating a smeared pattern. The UTP2 manual states that ultrasonic classification is unavailable without phase lock, so a missing classifier is not a negative PD result. [S3; S1, §3.10.3]

How do you make PD measurements repeatable?

EA Technology's UltraTEV Plus² manual V13.05.00 requires ultrasonic comparisons at the same position with the same sensor type. Anvilfield adds three captures per point and route-end function checks in the protocol below. [S1, p. 62]

Repeatability protocol
StepRecord or actionProtocol requirementComparison ruleBasis
IdentifyAsset, compartment, point photoAsset ID / front breaker / rear cable / marked sensor footprintSame point ID for later comparisonS1; Anvilfield protocol
InstrumentModel, serial, firmware, accessory, calibration, filter/gain and actual alarm settingsUTP2; V13.05.00 manual basis; 12-month calibration intervalNew sensor or processing configuration starts a labeled seriesS1
Function checkBefore/after route check resultRecord pass/fail and timestamp at both ends of routeFailed check requires review of affected acquisitionsS1 function check; before/after cadence is Anvilfield protocol
BackgroundMetal and air references, photo and timeCapture before route and after material interference changesRecord background alongside signal; do not algebraically remove unrelated pulse maximaS1; Anvilfield interpretation
PositionContact face or microphone positionSame marked footprint; same acoustic distance, angle and pathAirborne/contact series remain separateS1 p. 62; S9
ReferenceFrequency/reference source and lock50 or 60 Hz as applicable; locked state savedReacquire smeared or unlocked phase plotS3
ReplicateCapture count and durationThree captures per method per marked point; 10 seconds each for the acquisition in EA’s 2021 noteRetain all amplitudes, counts, patterns and timestamps; report their range, identify clipping and examine spreadCount is Anvilfield protocol; duration basis S3
ConditionsVoltage, current if available, switch state, ambient temperature, RHRecord actual kV, A, °C and %RH with timestamps and live/historical sensor state; mark unavailable values explicitlyNo invented zeroes or guessed matching conditionsS4, S6, S9
InterpretationSignal class, confidence and coverageCandidate PD / noise / unresolved / no PD detected at covered pointSeparate evidence quality from asset action priorityS1; Anvilfield synthesis
ArchiveRaw signal, audio, image and reviewer actionAsset-linked files plus due date and work orderPreserve as-found evidence after repairS4, S5

Voltage supplies electrical stress; current records operating state and influences temperature. Keep both where available, without importing a thermography minimum-load percentage into PD screening. Label comparisons matched conditions, changed conditions or unassessed. A humid-condition increase still needs action, while its cause requires comparison within the recorded environmental conditions. [S4, S6]

The UTP2 manual V13.05.00 retains bracketed historical temperature/RH readings after sensor removal. Let live readings settle and record their timestamp and live/historical status; a value carried from the previous panel is not a fresh environmental measurement. [S1, §3.6]

Distinguish repeatability from accuracy

Instrument accuracy excludes changes in geometry, background and coupling. Compare replicate spread before interpreting a small rise, and check range-end readings for clipping before calling a flat maximum stable. New localization or pattern evidence can justify action even when amplitude barely changes. [S1, S3; Anvilfield interpretation]

Can you survey energized switchgear with the doors closed?

Yes, where approved external measurements and installed signal paths support the method. EA’s UTP2 manual V13.05.00 permits ground-potential use only, requires earthed metalwork and gives the instrument, leads and accessories no inherent shock protection. It prohibits altering earth connections or disturbing plant mechanically, electrically or by applying heat during measurement. [S1, p. ii]

Keep doors, barriers, interlocks and bonds intact during external screening. Follow the site task assessment and arc-flash information; PD amplitude determines neither PPE nor approach distance. Refer bond defects to the grounding test scope without changing the bond for a reading.

Keep diagnostic access separate from routine screening

For utilization installations covered by OSHA Subpart S, 29 CFR 1910.333(a)(1) requires deenergizing exposed live parts before work on or near them unless the employer demonstrates increased hazards or infeasibility from design or operating limitations. Plan intrusive inspection under the electrical isolation procedure, with source isolation, stored-energy control, lockout/tagout and qualified-person voltage verification, including backfeed and induced voltage. OSHA 1910.333(b)(2)(iv)(B) requires checking the voltage tester immediately before and after verification on circuits over 600 V nominal; a TEV detector is not that voltage tester. OSHA 1910.331 defines the scope and exclusions for generation, transmission and distribution work. [S14]

CRYSOUND’s open-panel localization applied an external HV source after supply isolation: the diagnostic circuit was energized during testing. Treat it as a separate controlled HV test. EA’s manual prohibits measurements during nearby electrical storms or immediately after circuit energization; it gives no fixed waiting time. Its preferred clearance of more than 30 cm from perpendicular metalwork concerns sensor geometry, not personnel safety clearance. [S12, S1]

Which PD findings need action, and what makes a trend credible?

A positive result needs evidence review and an assigned action, even without a long trend. Anvilfield’s register below separates diagnostic confidence, suspected mechanism and consequence; the authorized owner/operator controls switching. Prioritize a localized finding by the insulation involved, defect evidence, available redundancy, fault exposure and outage consequence. A quiet trend on a critical bus still needs an assigned diagnostic response.

A PD amplitude trend is comparable only when sensor, position, acquisition settings, operating state and environmental conditions are recorded together; changed conditions require a separate interpretation. This Anvilfield rule follows the acquisition and monitoring evidence in S1, S3, S4 and S6.

Condition-labeled severity evidence
Condition labelEvidence neededTrend interpretationAction and timing basisSource
Covered point, no PD detectedValid check, usable signal path, controlled background, no supporting PD signatureSnapshot baseline for this method and pointRetain coverage record and scheduled program due dateS1, S6
Noise-dominated or unresolvedBackground/source/coupling explains signal, or discrimination incompleteDo not plot as confirmed asset deteriorationRepeat controlled acquisition during the visit where feasible; unresolved case enters follow-up registerS1, S2; Anvilfield workflow
Repeatable localized candidateRepeatable spatial source plus mechanism-consistent phase/audio/waveform supportDiagnostic confidence rises even without amplitude growthReviewer assigns localization or inspection task and a due date before report closureS1, S4; Anvilfield workflow
Environment-sensitive surface-discharge evidenceSurface-type signal plus RH/temperature seriesCompare similar conditions; retain humid-condition peaksAssign monitoring or targeted inspection using the condition-specific intervalsS4, S6
Deterioration under matched conditionsRepeated, comparable evidence of increased activity or changed patternEscalating condition evidence, not a failure-date calculationNotify authorized operator promptly; set investigation and operating response from consequence and evidenceS1; Anvilfield workflow
Verified repair responseDefect found/corrected and comparable post-work surveyNew as-left baseline linked to as-found recordClose only with documented scope and repeat-test resultS5, S12

Published repair evidence versus a continuing deterioration trend

CRYSOUND reports 30 dB TEV and 26 dBµV ultrasound before localization of a loose field deflector associated with an undersized O-ring, followed by 5 dB TEV and noise-level ultrasound after correction. Anvilfield calculates a 25 dB TEV difference from those readings. Retain those values as a repair comparison, with environmental matching recorded as unknown. [S12]

NETA World’s Fall 2020 discussion explains that PD amplitude can rise or fall with operating conditions and defect development; amplitude is not a remaining-life clock. EA’s Trinity Mirror case provides physical closure evidence instead: contact ultrasound localized activity, inspection found CT surface treeing, and replacement followed by retesting eliminated the source. [S13, S5]

Worked example: low TEV with positive ultrasound evidence

EA Technology’s May 15, 2018 survey used an UltraTEV Plus² and airborne ultrasound at indoor Substation 1, with 31 °C and 27% RH recorded. F1A was open while F1B carried the load. The table retains the source’s amplitude bins and ultrasonic “dB” notation. [S4]

Observed inputs and interpreted result
Input or locationTEV observationUltrasound observationResult or retained condition
F1A front breaker compartment0 to 10 dBmV bin; <1 pulse/cycle; negative phase indication0 to 10 dB reported bin; positive phase/audio; PD classificationAcoustic evidence supports suspected surface PD
F1A rear cable compartment0 to 10 dBmV bin; <1 pulse/cycle; negative phase indication0 to 10 dB reported bin; positive phase/audio; PD classificationAcoustic evidence supports suspected surface PD
F1B front breaker compartment0 to 10 dBmV bin; <1 pulse/cycle; negative phase indicationSame reported amplitude bin; negative phase/audio; noise classificationNo PD detected in recorded checks
F1B rear cable compartment0 to 10 dBmV bin; <1 pulse/cycle; negative phase indicationSame reported amplitude bin; negative phase/audio; noise classificationNo PD detected in recorded checks
Reported follow-upRepeat Substation 1 survey every 3 to 6 monthsInspect and/or perform offline testing during an outageReport also calls for attention to greater humidity on retest

Turn the observed result into a checkable work order

Anvilfield groups the two positive point records into one F1A feeder finding, preserving front-breaker and rear-cable evidence separately. Assign the maintenance lead a repeat-survey task and planned isolated inspection or offline testing, with the original environmental record attached. Localize before assigning two separate defects: the front and rear points can receive emissions from one source.

Anvilfield estimates an August 15 to November 15, 2018 retest window by adding the report’s three to six calendar months to May 15. Use that window on the F1A work order, with earlier review if the evidence worsens. [S4]

How often should a PD survey be repeated?

IEEE DEIS’s July 2023 webinar abstract describes routine survey programs operating every few months or annually; EA’s surface-discharge case specifies three to six months, and its service page describes one to two weeks of temporary monitoring. Use these published practices to select a condition-specific task, with an accountable reviewer and due date. [S11, S4, S6]

Survey and monitoring intervals
Use casePublished interval or durationAuthority/dateHow to apply
Established routine substation survey programsEvery few months or annuallyIEEE DEIS webinar abstract, July 2023Practice description; select asset task interval in owner's program
Substation 1 surface PD in worked exampleEvery 3 to 6 monthsEA report, June 8, 2018Source-specific retest and monitoring recommendation, with outage investigation
Separate no-PD substation in same report2 yearsEA report, June 8, 2018Retain as contrasting case evidence, not default for every quiet asset
Intermittent PD, interference or critical asset investigationTypically 1 to 2 weeksEA Americas service page, undated/retrievedTemporary recording of TEV, ultrasound, temperature and RH
Persistent high-consequence monitoring needContinuous monitoring with defined alarm responseIEEE DEIS 2023; EA service pageAssign review and escalation ownership

Specify who reviews monitored records, who receives alarms and who authorizes the operating response. Installing sensors does not resolve an open finding; the monitoring task must answer whether activity follows plant operation, environment or a persistent localized source. [S6; Anvilfield workflow]

Which follow-up tests confirm a suspected source?

Choose follow-up by the unresolved question: source direction, acoustic location, cable path, controlled electrical response or visible insulation damage. Anvilfield’s register assigns test objectives and closure evidence.

Follow-up test register
TriggerFollow-up and objectiveOperating/access conditionEvidence to retainAccountable role and closureBasis
Broad TEV signal or uncertain external sourceTEV time-of-flight/location and background comparisonApproved external grounded surfacesPoint map, timing comparison, reference readings and raw capturesPD reviewer resolves source or marks unresolvedS1, S2
Repeatable acoustic candidateAcoustic localization with second view or suitable contact probeExisting approved path; otherwise separately planned accessAudio, PRPD, point/distance image and settingsDiagnostic lead assigns compartment/source confidenceS1, S9
Suspected cable termination sourceHFCT survey and cable-specific localizationApproved access to suitable earth conductor; no altered bondsSensor arrangement, cable ID, waveforms and calibration basisCable diagnostic specialist issues location/test conclusionS1, S8
Internal insulation question needing controlled testCharge-based PD test to apparatus-specific procedureIsolated asset under a controlled test arrangement and applied test voltageCalibration, applied voltage/time sequence and frequency, inception/extinction where measured, apparent charge, noise record and acceptance basisTest engineer evaluates against specified apparatus criteriaS7; S13
Surface PD with contamination/moisture suspicionIsolated visual inspection and OEM-approved correctionApproved isolation and work procedureAs-found photographs, contamination/damage, component IDs, correctionMaintenance lead completes work; reviewer verifies repeat surveyS4, S5
Intermittent activity or condition-sensitive peaksTemporary TEV/acoustic monitoringSuitable sensor installation and retrieval planTimestamped activity, temperature and RH throughout the selected monitoring periodAsset engineer reviews condition groups and assigns actionS6
Repair completedRepeat same-point survey and applicable electrical checksRestored approved test/operating conditionsAs-found/as-left files, settings and operating/environment recordAuthorized owner closes finding against stated scopeS5, S12

Controlled offline PD tests can measure inception and extinction voltages under the applied voltage sequence. Retain voltage, waveform, frequency, calibration and background, and keep these results separate from the operating survey series. NETA World’s Fall 2020 article explains this online/offline distinction; IEC 60270:2025 supplies the charge-based measurement framework. [S13, S7]

Insulation-resistance testing answers a different insulation question, while thermography documents surface-temperature evidence. Neither alone clears a localized PD finding. Combine their results by asset and defect, without substituting one method’s severity scale for another.

What the closeout record must retain

Keep the original raw traces, audio, point photographs, instrument settings, checks, background, operating conditions and coverage exclusions. Add the actual defect, corrected component, test basis and repeat result. “Source eliminated at repeat test” is a useful closure statement tied to evidence and scope. [S1, S4, S5]

How much does a switchgear PD survey cost, and how long does it take?

Anvilfield estimates $2,000 in direct cost for a 12-panel survey allowing two technicians four field hours, four total reporting person-hours, $300 in instrument allocation and $200 in travel. Increasing field time to six elapsed hours raises that estimate to $2,500. The selected planning inputs are shown below.

Anvilfield survey cost estimate
Cost inputQuantity and selected rateBase costSix-field-hour case
Field crew2 technicians × 4 hours × $125/person-hour$1,0002 × 6 × $125 = $1,500
Review/reporting4 person-hours × $125/person-hour$500$500
InstrumentsSelected daily allocation$300$300
TravelSelected allowance$200$200
Total direct costSum of four lines$2,000$2,500
Cost divided over 12 panelsTotal / 12; rounded$167/panel$208/panel

Build the time allowance from measurement points

Count marked points, methods and repeat captures before assigning crew time. For 12 panels with three points each, two methods and three captures per method, the plan contains 216 records. At the ten-second acquisition described by EA’s phase-reference note, raw recording totals 2,160 seconds, or 36 minutes. [S3; Anvilfield estimate]

Method note: Anvilfield’s November 5, 2026 estimate multiplies field and reporting person-hours by a selected $125 hourly rate, then adds instrument and travel allowances. Four field hours cover preparation, access, background checks, movement, placement and flagged-point repeats; four reporting hours cover evidence review and the action register. The rate is an estimate input, not a measured market average.

Price controlled HV testing, switching services, repairs, outage losses and overnight travel separately. Overhead, profit and taxes also sit outside this direct-cost model. Accessible points and diagnostic follow-up drive the scope more accurately than panel count alone.

How do you scope a repeatable switchgear survey program?

Specify a complete point map, complementary method coverage, background checks, raw evidence, condition labels and a dated findings register before counting panels. Obtain equipment records, maintenance history and operating restrictions from the owner. State which compartments each method covers and which remain unassessed.

Use the predictive-maintenance program to connect baselines, criticality and work orders, while retaining PD-specific comparability. The preventive-maintenance program guide supplies cross-trade route and closure practices. Keep thermal, PD and outage-test findings together by asset without averaging their incompatible severity scores.

Scope by site, then verify the indoor equipment inventory

Group sites geographically to plan travel between facilities. Contractors building a regional survey route use PorchRocket's Asset Search to locate visible substations and power sites with the owner of record attached to each find.

Facility records establish the indoor switchgear inventory; field testing establishes its measured condition. Confirm the utility/customer operating boundary against the one-line, since property ownership alone does not define permission to survey every asset.

Field checklist: from first reading to closed finding

Use this Anvilfield checklist to complete the survey record. Every positive or unresolved finding needs a responsible role, a due date and closure evidence; inaccessible scope receives “not assessed,” never an invented zero.

0 of 15 complete

Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.

Sources and how to cite this page

Anvilfield. Editorial review date: November 5, 2026. Sources checked: November 6, 2026. The IEC references below are public publisher scopes; the summaries do not reproduce paywalled clauses.

  1. S1. EA Technology, UltraTEV Plus² Operating Manual, model UTP2, 2388-MANUL-V13.05.00, June 17, 2025.
  2. S2. EA Technology Australia, PD FAQ: Background Noise, February 9, 2023.
  3. S3. EA Technology, Importance of accurate phase reference lock when using the UltraTEV Plus2, v1, September 17, 2021.
  4. S4. EA Technology, Partial Discharge Survey Examples of MV & HV Assets, report June 8, 2018, survey May 15, 2018.
  5. S5. EA Technology, UltraTEV Plus2 confirms and classifies Partial Discharge on Trinity Mirror HV Network, undated case study; initial survey February 2016.
  6. S6. EA Technology Americas, Partial Discharge Surveys, undated live service page.
  7. S7. IEC 60270:2025, edition 4.0, published June 5, 2025, public publisher scope.
  8. S8. IEC TS 62478:2016, edition 1.0, published August 29, 2016, public publisher scope.
  9. S9. FLIR Si2 series, Partial discharge detection, T810637-AG-en-US, live manual.
  10. S10. FLIR Si2a, Locating sound sources, T810671-AA-en-US live manual.
  11. S11. IEEE Dielectrics and Electrical Insulation Society, Improving Network Reliability with Partial Discharge Monitoring, July 2023 webinar announcement/abstract for August 8, 2023.
  12. S12. CRYSOUND, Floating Partial Discharge in MV Switchgear: Detection and Repair Case Study, undated page.
  13. S13. NETA World, Partial Discharge Secrets, Tips, and Tricks, Fall 2020, EA Technology-hosted publisher reprint.
  14. S14. OSHA, 29 CFR 1910.331, Scope, and 1910.333, Selection and use of work practices, public regulatory text checked November 6, 2026.

Update log: November 5, 2026, final article review added layered-enclosure exclusions, clarified energized diagnostic access and OSHA isolation requirements, preserved suspected-source confidence, and removed repeated explanations.

How to cite this page: Anvilfield, TEV vs ultrasound for switchgear partial-discharge surveys, 2026, https://anvilfield.com/field-guides/electrical/switchgear-partial-discharge-survey-interpretation/

Related tools

Next step: Find power sites

FAQ

Is TEV or ultrasound better for switchgear PD surveys?

Use both where signal paths permit: TEV screens electromagnetic pulses and ultrasound adds acoustic evidence, especially for surface activity.

What TEV level is acceptable?

Use the specific instrument's magnitude, pulse-rate and pattern interpretation with asset evidence; no single TEV dB number clears all switchgear.

Does zero TEV pulse count mean no partial discharge?

No; the UTP2 manual V13.05.00 specifies a 10 dBmV minimum pulse-count level.

Can ultrasound detect PD through a closed panel?

Airborne ultrasound needs an air path. Contact ultrasound needs suitable coupling to the source tank; EA excludes its UCP1 probe where another enclosure layer separates that tank from the probe.

Can ultrasonic dB be compared with TEV dBmV?

No; they are different measurement channels and reference quantities.

How do I distinguish PD from noise?

Combine safe background comparisons, localization, stable acquisition and phase/audio/waveform evidence.

Does humidity change partial-discharge readings?

Surface activity can vary with humidity, so preserve RH and temperature with every comparable measurement.

How often should switchgear PD testing be done?

Published programs range from every few months to annually; assign the actual interval from asset condition and the maintenance program.

Does PD testing replace infrared thermography?

No; discharge evidence and surface-temperature evidence address different aspects of equipment condition.

Does a higher PD reading predict a failure date?

No. Compare sensor, position, settings, operating state and environment before assigning deterioration; defect type and failure consequence govern the response.

Does a phase-related PRPD pattern prove partial discharge?

No. Supply-synchronized interference can also form a phase-related pattern. Combine PRPD with localization and noise checks; floating-metal and contact discharge can move in phase.

Does a positive PD result mean switchgear must shut down?

Assign an action from the mechanism, confidence, observed change and failure consequence; the owner's authorized operator controls switching.

People also ask

Codes cited in this guide

This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.