Field glossary · component
Busway
Busway distributes electrical power through factory-assembled conductors inside a protective enclosure, with joints and fittings completing the route. Its voltage drop depends on where loads tap the run, not just the nameplate amperage. A row with evenly spaced loads loses less voltage than the same total load concentrated at its far end. Use the electrical data for the actual busway family, bar material, frequency and loading pattern.
Prefabricated busbar run, the common alternative to many parallel sets on high-amp feeders
Calculate busway drop from the load locations
Schneider Electric's I-Line electrical data scales its tabulated busway voltage drop by actual current divided by rated current and actual length divided by 100 ft. Select the table column for the load power factor first. The table describes a concentrated load at the end of a run, so every section carries the full current.
Schneider Electric's busway voltage-drop guidance divides the concentrated-load value by two for distributed plug-in loading. That shortcut suits loads spread along the run; a cluster of taps near the far end needs a segment calculation. Starting at the source, assign each segment the sum of its downstream loads, calculate its drop and add the drops to the tap being checked.
For an actual ReliaGear selection, ABB lists 1.85 V per 100 ft for 400 A copper busway at rated load, 60 Hz, 25°C ambient and 0.80 power factor. At 300 A over 150 ft, the concentrated-load result is 1.85 x 300/400 x 150/100 = 2.08 V. The distributed-load approximation gives about 1.04 V; calculate separate segments when only a few taps carry most of the load. Both cases carry 300 A at the feed; the tap arrangement changes the voltage at the end.
How 50 Hz and 400 Hz affect busway ratings
ABB specifies multiplying ReliaGear's 60 Hz reactance by 0.83 for a 50 Hz voltage-drop calculation while leaving its resistance unchanged. A frequency change therefore affects the reactive part of the calculation rather than simply multiplying the final voltage-drop number.
For 400 Hz operation, ABB limits ReliaGear busway to 85 percent of its continuous current rating. This product-specific rule matters in aircraft and other frequency-conversion applications. It does not authorize applying the same multiplier to a different busway system.
Match joint maintenance to the busway family
ABB identifies a 50 ft-lb joint connection for the ReliaGear construction in its technical guide and describes Belleville-washer joints that do not require routine retorquing. That is a product instruction, not a generic busway torque or a reason to retighten every joint during a service visit. Identify the installed joint design and maintenance instructions before specifying the work.
The estimating distinction is between a feeder run that carries power to its end and plug-in sections that provide branch takeoff positions. Count the tap units, joint packs and changes of direction separately from straight footage. A current rating and total run length alone leave those installation quantities undefined.
Specify the assembly that the calculation describes
A busway submittal needs the exact series, conductor material, neutral and ground arrangement, mounting orientation, operating frequency and tap schedule. Include the segment lengths used in the voltage-drop calculation. Moving most taps to the last third of a row changes the calculation even when the total connected amperage stays unchanged.
UL 857, 14th edition dated September 10, 2025, is the current busway product standard. Its scope covers service-entrance, feeder and branch-circuit busways and associated fittings. The installed assembly still carries its own marked ratings; the standard's scope does not upgrade an older product.
The busway installation guide covers supports, joints and commissioning. Use the receiving and insulation-test guide for the acceptance record that travels with the installed run.
Distinctions
- Busbar
- A busbar is a conductor within an assembly. Busway is the complete distribution system, including its enclosure, insulation, joints and fittings.
- Cable tray
- Cable tray supports separately selected cables. A busway product supplies the conductors and enclosure as a rated assembly, so tray fill arithmetic does not determine busway capacity.
Frequently asked questions
Can I use one voltage-drop value for every busway of the same ampere rating?
Use the selected manufacturer's electrical data. Conductor material, bar spacing and construction change resistance and reactance, and the power factor and tap locations change the resulting drop.
Sources checked
Also defined as
- Datacenter: An overhead bus run with plug-in tap-off boxes that feeds rack power without new conduit