Equivalent length
An equivalent length belongs to a fitting, a flow condition and a reference straight-duct friction rate. A fitting losing 0.12 in. w.g. represents 150 ft when that reference loses 0.08 in. w.g. per 100 ft. It represents 100 ft against a 0.12-per-100-ft reference. The fitting has not changed; the comparison basis has. Preserve that basis when replacing a worksheet allowance with measured or manufacturer loss data.
The feet of straight duct that would cost the same static pressure as a given fitting, read from the Manual D tables
Identify the reference behind the fitting value
ACCA identifies Section N4 of ANSI/ACCA 1 Manual D-2016 as the source of default fitting equivalent lengths used on its Effective Length Worksheet. Select the fitting that matches the actual takeoff, elbow or transition. Its shape and flow path matter; a plan symbol showing a bend does not identify the construction represented by a table entry.
Southwark Metal's equivalent-length guidance describes fitting values as assigned by type, style and configuration. Record that identity with the design. Changing a takeoff to fit a joist bay changes the installed fitting, so preserve its revised geometry rather than retaining a lower-loss value selected for a fitting that is no longer there.
Use pressure loss when the supplier gives a curve
ASHRAE defines a fitting's loss coefficient in Chapter 21 of its 2025 Fundamentals handbook as total pressure loss divided by velocity pressure at the designated reference section. ASHRAE specifies actual section velocity for the fitting calculation, rather than the velocity in a circular equivalent. A curve or coefficient therefore needs its reference area and airflow.
Where the fitting loss and straight-duct friction rate use the same flow basis, equivalent feet = fitting pressure loss / straight-duct pressure loss per foot. Keep total-pressure fitting data and the associated duct-loss method consistent. This calculation makes a supplier's tested fitting comparable with a route-length worksheet without pretending its pressure loss is extra physical duct.
Avoid charging the same component twice
A coil or filter entered as a separate pressure deduction should not also enter the route as equivalent feet representing that same loss. Assign every loss in the Manual D pressure budget a component or fitting identifier and one calculation location. When a manufacturer curve replaces a worksheet allowance, remove the old allowance from that same identifier.
Distinctions
- Developed length
- Material takeoff uses the physical routed length. A fitting allowance expressed as 150 equivalent feet contributes resistance to the design calculation but does not add 150 feet of purchased duct or internal refrigerant volume.
Field example
At the selected airflow, a fitting loses 0.12 in. w.g. and the reference straight duct loses 0.08 in. w.g. per 100 ft. The fitting represents 0.12 / 0.08 x 100 = 150 equivalent feet. A replacement losing 0.04 in. w.g. represents 50 ft on the same basis, saving 100 equivalent feet and 0.08 in. w.g.
Frequently asked questions
Does a longer equivalent length add refrigerant charge?
A fitting assigned 150 equivalent feet still contains only its actual physical volume. Use actual line sizes and lengths for the manufacturer's charge adjustment; the equivalent-feet entry changes the resistance calculation, not the amount of tubing filled.
Sources checked
Also defined as
- Straight pipe length plus the added pressure-drop length of every elbow, valve, and accessory
- Straight lineset length plus the added loss of every elbow and bend