Field glossary · measurement
U-factor
U-factor expresses the rate of heat transfer through a stated building component per unit area and temperature difference. In U.S. practice its units are Btu/(h·ft²·°F), and lower values indicate less heat flow under the same conditions. Identify whether the value describes glazing, a complete window, or an opaque assembly. Taking the reciprocal gives the resistance of that same evaluated construction, with the same boundaries.
The inverse of total R at the assembly level, the form the energy code may check
Read the units before comparing two U-values
DOE's fenestration purchasing guidance gives a typical window U-factor range of 0.2 to 1.2 Btu/(h·ft²·°F). Those figures describe a rate per area and temperature difference. U-factor has units, unlike the dimensionless solar heat gain coefficient shown beside it on a window label.
NIST's SI conversion tables give 1 Btu/(h·ft²·°F) = 5.678263 W/(m²·K), using the international-table Btu. Multiply a U.S. U-factor by 5.678 to compare it with a metric schedule: U = 0.30 becomes approximately 1.70 W/(m²·K). Divide by the same factor for the reverse conversion; comparing the two bare decimals would make identical products look very different.
The roof insulation guide introduces the assembly's resistance basis. Reading U = 0.05 in U.S. units gives R = 20 for the same evaluated assembly. It does not assign R-20 to each individual layer.
Combine heat-flow paths by conductance
EPA's October 2020 multifamily simulation guidelines calculate overall wall U-factor by area-weighting regions with different thermal properties. Heat follows parallel paths through insulation, framing, and other parts of an assembly. Calculate each path's conductance and area share before combining them. Averaging path resistances gives a different result because the low-resistance path carries disproportionate heat flow.
For a wall with 80 percent of its area at complete-path R-30 and 20 percent at complete-path R-5, the area-weighted U-factor is 0.80/30 + 0.20/5 = 0.0667 Btu/(h·ft²·°F). Its effective resistance is approximately R-15. The arithmetic average of those path resistances would be R-25, overstating the assembly's resistance.
The R-30 and R-5 inputs above are complete-path resistances, including the layers and boundaries in each path, rather than insulation labels. EPA's area-weighting method likewise starts with evaluated assembly regions. The window-film guide and curtain-wall guide help identify the actual glass and frame construction represented by a proposed replacement.
Translate a U-factor change into a heat-flow change
Using DOE's U.S. U-factor units, 600 square feet of glazing at U = 0.30 and a 40°F temperature difference transfers 7,200 Btu/h by the U × area × temperature-difference calculation. Reducing U to 0.20 under the same conditions gives 4,800 Btu/h, a reduction of 2,400 Btu/h in that heat-transfer component.
Keep solar gain and air leakage as separate calculation inputs. NFRC presents air leakage and solar heat gain as separate label categories, each describing a different performance characteristic. Adding them to a U-factor comparison requires their own measured or rated quantities.
NFRC states that commercial Label Certificates are project-specific and include the project address, contact information, and certified ratings. Retain that certificate with the approved glazing schedule so a replacement order can be traced to the rated construction and project.
Distinctions
- Center-of-glass U-factor
- A center-of-glass value describes the glazing region it evaluates. The complete product result also accounts for the frame and edge construction, which must remain identified when comparing a glass replacement with a window replacement.
Frequently asked questions
Does cutting U-factor in half cut the energy bill in half?
It halves the calculated U × area × temperature-difference heat flow for the same area and conditions. Annual building energy also includes solar gains, infiltration, ventilation, equipment, and operating schedules.
Sources checked
- U.S. Department of Energy FEMP: fenestration U-factor units, typical range and heat-transfer basis
- National Fenestration Rating Council: label categories and commercial Label Certificates
- U.S. EPA ENERGY STAR: Multifamily New Construction Simulation Guidelines, version 1 revision 02, October 2020, wall U-factor averaging on page 12
- NIST SP 811 Appendix B.9: heat-transfer-coefficient unit conversion
Also defined as
- Concrete: The rate of conductive heat transfer through the glazing; film affects it less than it affects SHGC