ANVILFIELD Try FieldOS

HVAC

Kitchen hood fire suppression semi-annual service guide

Inspect the wet-chemical system, replace the links, prove the nozzles still aim at the appliances, test actuation and the gas trip, and tag what you found.

Hood SuppressionWet ChemicalUL 300NFPA 96NFPA 17A

Direct answer

A commercial kitchen hood suppression system is a wet-chemical fire system that protects the cooking appliances, hood, plenum, and exhaust duct from a grease fire. NFPA 96 requires a trained technician to inspect and service it every 6 months, replacing fusible links, confirming each nozzle still aims at its hazard, and testing actuation. The AHJ and manufacturer govern.

On this pageWhat the system protects and why 6 monthsThe wet-chemical system, part by partWhat is UL 300 and why does it matter?NFPA 96, NFPA 17A, and the semi-annual intervalWhy does moving an appliance break the system?Fusible links and the grease that defeats themWhat happens in the actuation test?The agent tank, the cartridge, and the hydro clockThe K-class extinguisher as the backupGrease loading and the cleaning relationshipThe fuel and power shutoff interlockThe inspection tag, the report, and the AHJWhat fails a hood suppression inspection?How the wet chemical actually puts the fire outThe owner's monthly check vs the technician's semi-annualWhat to documentCommon mistakesField checklistStandards and referencesUnits and terms

Key takeaways

  • NFPA 96 and NFPA 17A require a trained technician to inspect and service a wet-chemical hood suppression system every 6 months.
  • Lost nozzle coverage after an appliance is moved or swapped is the number one finding; confirm every cooking surface falls under a nozzle rated for that hazard, size, and height.
  • Replace metal-alloy fusible links at every semi-annual; baked-on grease insulates them and raises their effective trip temperature.
  • Fire the system without discharging agent: pull the cartridge, trip the detection line, and confirm the gas valve physically closes and the alarm and fan respond.
  • Wet-chemical agent cylinders carry a 12-year hydrostatic test interval; read and track the date stamp each service and flag it before it expires.

What the system protects and why 6 months

A commercial kitchen hood suppression system is a pre-engineered wet-chemical fire system that protects the cooking line. It covers the appliances themselves, the hood that captures the smoke and grease, the plenum behind the filters, and the exhaust duct that carries it all to the roof. Those four zones are where a grease fire starts and where it travels, and the system is aimed at each of them on purpose.

It is a one-shot system. The agent sits in a tank under no pressure until a fire melts a fusible link or someone pulls the manual station, and then a gas cartridge drives the agent out through the nozzles. That is the whole point of the service. The system spends years doing nothing, so the only way to know it will fire when it has to is to inspect and test it on a schedule.

The schedule is every 6 months. NFPA 96 sets the semi-annual interval for inspection and service by a trained, qualified person, and NFPA 17A backs it for the wet-chemical extinguishing system specifically. The owner still has a monthly walk-around to do, but the real service, the links and the actuation test and the nozzle check, belongs to a technician twice a year. Confirm the adopted edition and any local amendments, because the AHJ controls what gets enforced.

The wet-chemical system, part by part

Walk a system the same way every time and you stop missing parts. Start at the tank and follow the agent to where it comes out, then follow the detection back to what trips it.

The agent tank holds the wet chemical, a potassium-based liquid that sits at no pressure until discharge. The release assembly, usually a regulated release with a gas cartridge of nitrogen or CO2, is what punctures and drives the agent out. Distribution piping runs from the tank to the nozzles, and every nozzle is a specific flow number aimed at a specific hazard: one type over a fryer, another over a range, another into the plenum, another up the duct. Each nozzle wears a blow-off cap, metal or silicone rubber, to keep grease out of the orifice until the day it fires.

On the detection side, fusible links hang in the duct and over the cookline on a cable run held under tension. Heat melts a link, the cable goes slack, and the release fires. The manual pull station gives a person the same trip by hand, and it has to sit in the path of egress, not behind the line. Tying it together is the interlock that shuts off gas or power to the appliances and the alarm contacts. That is the system. Tank, release and cartridge, piping and nozzles, links and cable, pull station, gas valve, alarm.

What is UL 300 and why does it matter?

UL 300 is the listing standard a kitchen suppression system has to meet to protect modern cooking equipment, and it is the line between a system that works on today's fryers and one that does not. A system that is not UL 300 listed is obsolete, and most jurisdictions require those older systems to be replaced, not just serviced.

The history explains the rule. Kitchens used to fry in animal fat, and dry chemical put those fires out fine. Restaurants moved to vegetable oils, which auto-ignite hotter, commonly cited around 360 degrees C against roughly 290 to 315 degrees C for lard. Dry chemical would knock the flame down, but if the oil was still above its auto-ignition point the fire flashed right back as soon as the powder settled. Insurers were eating the losses and fire departments kept watching the reflash.

UL 300, introduced in 1994, moved the trade to wet chemical for cooking hazards. Wet chemical does two jobs at once. It saponifies, reacting with the hot grease to lay a soapy foam blanket that cuts off oxygen, and it cools the oil below its auto-ignition temperature so it cannot reflash. That cooling is the part dry chemical never did, and it is exactly what high-efficiency, heat-retaining appliances demand, because they are insulated and slow to give up their heat. If a system on the wall is pre-UL-300, the conversation is replacement, and that is a call for the AHJ and the owner, not something a service tag papers over.

NFPA 96, NFPA 17A, and the semi-annual interval

Three documents and one authority govern this work. NFPA 96 is the standard for commercial cooking ventilation and fire protection: the hood, the grease duct, the exhaust, and the fire protection over the cooking operation. NFPA 17A is the standard for wet-chemical extinguishing systems, which is the system itself. UL 300 is the listing the equipment has to carry. Above all of them sits the AHJ, the authority having jurisdiction, who adopts an edition, amends it, and enforces it.

The interval that drives this guide comes from both NFPA 96 and NFPA 17A: a trained, qualified person inspects and services the system every 6 months. That semi-annual service is the technician's job and it carries the tag. Separate from it, NFPA 17A also calls for a monthly inspection the owner or a trained employee can perform, a quick check that the tank gauge is in range, the nozzle caps are on, the manual station is clear, and the tag is current.

Two services get confused with this one and should not be. The kitchen exhaust cleaning, the grease removal from hood, duct, and fan, is its own service on its own schedule under NFPA 96, driven by how hard the kitchen cooks. The portable extinguisher service falls under NFPA 10. They are related, they show up in the same kitchen, but the suppression semi-annual is its own scope. Name the right standard for the part you are touching and confirm the section against the adopted edition, because the numbering shifts between cycles.

Why does moving an appliance break the system?

Because the nozzles are aimed at where the appliances were, not where they are now. This is the number one finding on a semi-annual, and it is the one that actually gets people hurt. The kitchen swaps a 3-foot fryer for a 4-foot one, slides a range over to fit a new griddle, or adds a wok station, and nobody calls the suppression company. The nozzles still point at empty stainless. The new fryer has no coverage at all.

Pre-engineered systems are designed to a specific layout. Each nozzle has a listed coverage: a maximum appliance size, a height range from the nozzle tip to the cooking surface, and an aim point. A fryer nozzle is not a range nozzle. A nozzle rated for a 21-inch fryer does not protect a 24-inch one. Move the appliance out from under the nozzle, change its height, or grow it past the listed dimension, and the protection is gone even though the hardware looks untouched.

So the semi-annual is not just checking that nozzles are clean and capped. It is standing on the line and confirming, appliance by appliance, that every cooking surface still falls under a nozzle rated for that hazard at that size and that distance. When it does not, you re-aim, add coverage, or re-engineer the system to the new layout, and you write the appliance change on the report. A system that protected the kitchen a year ago protects a different kitchen today, and the only way to catch the drift is to measure it against the appliances that are there now.

Fusible links and the grease that defeats them

Fusible links are the system's thermostat. A link is two pieces of metal joined by a solder alloy with a known melting point, hung in the heat stream over the cookline and in the duct, holding a cable under tension. When the air around a link reaches its rating, commonly in the range of about 165 to 360 degrees F depending on where it sits and the manufacturer's temperature selection, the solder lets go, the cable releases, and the system fires. The link rating is matched to the location, so the duct link and the cookline link are often different temperatures.

Grease is what kills them. A link coated in baked-on grease responds slower or not at all, because the grease insulates the metal from the heat it is supposed to sense and effectively raises its trip temperature. That is why links get replaced on a schedule rather than reused. The common cadence: metal-alloy fusible links are replaced at the semi-annual service, and other detector types are examined and cleaned or replaced at least annually. Confirm the cadence and the link temperatures against the manufacturer's manual and the adopted code.

Replace them, do not just look at them. New links go in matched to the rating stamped on the old one, the cable gets re-tensioned, and you confirm the detection line is taut with no kinks at the corner pulleys. A link that looks fine and a link that will trip at its rating are two different things, and you cannot tell which you have by eye once grease is on it.

What happens in the actuation test?

You fire the system mechanically and electrically without discharging agent, and you watch everything downstream respond. This is the heart of the semi-annual. A clean tank and aimed nozzles mean nothing if the release does not trip and the gas does not shut off.

Pull the cartridge first so no agent can discharge, or follow the manufacturer's procedure for a no-discharge functional test. Then trip the system the way a fire would: release the detection line and confirm the regulated release actuates, the mechanism strikes where the cartridge would be punctured. With that proven, work the chain it is supposed to drive. The gas valve has to trip closed, and you confirm it physically, the appliances lose fuel. The exhaust fan and the alarm have to do what the design calls for. The manual pull station gets its own pull, because it is a separate path to the same actuation and it has to work on its own.

Test the gas trip every time and put a hand on it. A mechanical gas valve that has sat latched for years can stick, and a valve that does not close leaves burners feeding a fire the agent is trying to put out. Electric appliances get a shunt-trip or contactor that drops power on actuation, and that gets verified too. After the test, reset the release, reinstall a fresh cartridge per the manufacturer, re-arm the gas valve, and confirm the system is back in the set, ready position before you leave. A system left tripped or a gas valve left latched open is worse than the deficiency you came to fix.

The agent tank, the cartridge, and the hydro clock

The agent tank and its expellant cartridge are checked every semi-annual and replaced or tested on their own clocks. The tank holds the wet chemical at no internal pressure, so you are confirming the agent is present, the fill is right for the system, and the tank shows no corrosion or damage. The agent has a service life and the manufacturer dates it, so check the agent against its replacement interval, not just its presence.

The expellant cartridge is the energy. It is a sealed steel cylinder of nitrogen or CO2 that gets punctured on actuation to push the agent out. Cartridges are weighed against their stamped charged weight, because a slow leak shows up as lost weight long before anything else flags it. A cartridge light by more than the manufacturer's allowance gets replaced. On a discharge or a test that punctures it, it gets replaced, full stop.

The tank itself carries a hydrostatic test interval. For wet-chemical agent cylinders the common interval is 12 years, after which the cylinder is hydrostatically tested or condemned. Read the date stamp on the cylinder every service and track it, because a tank that is one service away from an overdue hydro is something you flag now, not the day it expires. Confirm the interval against NFPA 17A and the cylinder marking, since the test cycle is set by the standard and the manufacturer.

The K-class extinguisher as the backup

Every commercial kitchen with cooking grease hazards needs a portable Class K extinguisher, and it is part of what you confirm on the visit even though it services on its own NFPA 10 cycle. The K-class is the manual backup for the small fire the fixed system should not have to fire on, and the cool-down tool after the system has discharged.

It is wet chemical for the same reason the hood system is: a potassium-based agent, often potassium acetate, that discharges as a fine mist and saponifies the grease rather than splashing burning oil out of the vessel. A water or ABC extinguisher on a grease fire makes things worse, water flashes to steam and throws flaming oil, and dry chemical can let it reflash. The K-class is the one rated for the hazard.

Two field points. NFPA 10 places the Class K within a maximum travel distance of the cooking hazard, commonly cited at 30 ft, so confirm it is mounted in reach of the line and not buried in a back room. And there is a placard requirement: a sign at the extinguisher telling the user to actuate the fixed system first, then use the portable. People reach for the red bottle on reflex. The placard is there to stop them from skipping the system that protects the whole line.

Grease loading and the cleaning relationship

Grease is the fuel the whole system exists to fight, and grease loading is also what quietly defeats it. The hood, the plenum, the duct, and the fan accumulate grease every service hour, and that buildup does two bad things at once. It is more fuel for a fire to spread through, and it coats the very parts that are supposed to detect and suppress that fire.

Loaded fusible links trip slow or not at all. Capped nozzles plug with grease if the caps are missing or the buildup is heavy. A grease-laden duct is a chimney waiting for a flame front. The suppression system and the exhaust cleaning are two services, but they fail together, and a tech who only services the suppression hardware while the duct runs black is treating half the problem.

The exhaust cleaning is its own NFPA 96 service on its own frequency, set by how hard and how greasy the kitchen cooks. A high-volume wok or charbroil operation may need it monthly. A low-volume kitchen runs longer. The two services should talk to each other, because the cleaning frequency tells you how fast grease is loading the links and nozzles you just replaced. Note the duct condition on the suppression report even when cleaning is somebody else's contract. It is the context for everything you checked.

The fuel and power shutoff interlock

The interlock is what makes the agent's job winnable. When the system fires, it has to cut the energy feeding the fire at the same instant it lays down the agent, and that is the interlock: the gas valve or the electrical shutoff slaved to the actuation.

On a gas line it is a mechanical or electric gas valve in the supply to the appliances under the hood, held open and tripped closed on discharge. Cut the gas and the burners die, so the agent is fighting a fire with no fuel behind it. Leave the gas on and the system is dumping agent onto burners still throwing flame, and it can reflash the moment the agent is spent. On electric appliances the equivalent is a shunt-trip breaker or contactor that drops power to the cooking equipment on actuation. Every appliance under the hood has to be on the interlocked supply, gas or electric, or it keeps cooking through the discharge.

There is a ventilation side too. On discharge the exhaust fan behavior follows the design and the listing, and makeup air handling is part of it, because you do not want a running fan pulling agent off the cooking surface before it can do its work, nor a dead exhaust letting smoke fill the space. The design sets which fans run and which stop on actuation. Test the interlock as part of actuation, confirm the gas physically closes, and verify the fan and alarm do what the design specifies, not what you assume.

The inspection tag, the report, and the AHJ

The tag is the public face of the service, and the report is the record behind it. After a semi-annual, the system carries a tag showing the date, the company and technician, and the result. A current tag tells the fire marshal, the insurer, and the next owner that a qualified person serviced the system on schedule.

The AHJ is who that tag answers to. The authority having jurisdiction, usually the fire marshal, adopts the code edition, sets the local rules, and inspects the kitchen against them. When a system passes, it gets the current tag. When it has a deficiency the technician cannot correct on the spot, the system gets flagged, the deficiency goes on the report with what it will take to fix, and in many jurisdictions a system with a real impairment gets red-tagged, marked out of service, with the AHJ and the owner notified.

Do not soften a deficiency to keep a customer happy. An overdue hydro, a fryer with no nozzle coverage, a gas valve that will not trip, those are the findings that matter, and a tag that says pass over a system that will not fire is the kind of paper that ends careers when the kitchen burns. Write what you found, tag it honestly, and let the report carry the detail the tag cannot. The report is what the AHJ reads and what backs the tag if anyone ever asks.

What fails a hood suppression inspection?

A system fails when any part of the detect, actuate, suppress, and shut-off chain will not perform, and the failures rank by how often they show up and how badly they bite. Work them in that order and you find the dangerous ones first.

Nozzle coverage gone after an appliance change is the headline failure, because the system looks fine and protects nothing over the new equipment. Then the gas valve that will not trip closed on test, which leaves fuel on a fire. Then fusible links overdue or grease-loaded so they will not melt at their rating. Then an expellant cartridge light on weight or an agent tank past its hydro date. Then nozzles missing caps and plugged with grease, or piping that has been bumped out of aim. Then a manual pull station blocked, buried behind the line, or seized. Then a missing or expired tag, a missing K-class placard, or a Class K extinguisher out of reach or out of date.

Most of these are not subtle once you test instead of look. The actuation test catches the dead gas valve and the seized release that an eyeball walk-by misses entirely. That is the whole argument for functional testing over visual inspection: a system can look pristine and still fail to fire, and the only way to know is to make it try.

How the wet chemical actually puts the fire out

Two mechanisms, and both have to happen or the fire comes back. The agent does not just smother the flame the way a powder does.

First, saponification. The potassium-based agent reacts chemically with the hot fats and oils and turns the surface into a soap-like foam. That foam blanket seals the grease off from oxygen, which knocks the flame down. Second, cooling. The agent is water-based and it pulls heat out of the oil, dropping it below its auto-ignition temperature. The blanket holds the seal while the oil cools under it, and a cooled oil cannot reflash even after the agent layer breaks.

This is the exact reason UL 300 exists and the reason a high-efficiency fryer is so dangerous. Those appliances hold heat. A dry agent could blanket the surface, but the deep, insulated oil stayed above auto-ignition and flashed back the instant the powder cleared. Wet chemical keeps the seal long enough for the cooling to win. When you confirm the nozzles are aimed at the cooking surface and the agent and cartridge are right, you are protecting both halves of that mechanism: the blanket and the cool-down.

The owner's monthly check vs the technician's semi-annual

Two different jobs get called inspection and they are not the same scope. Keeping them straight is part of explaining the service to an operator who thinks one covers the other.

The monthly is a quick visual the owner or a trained employee performs and logs. Tank gauge in the green where the system has one, nozzle caps in place, manual pull station unobstructed, no obvious damage, and the semi-annual tag current and not expired. It takes minutes and it needs no tools. Its whole purpose is to catch the gross problem, a missing cap, a blocked pull station, a tank someone bumped, between the real services.

The semi-annual is the technician's service: links replaced, nozzles confirmed aimed at the current appliances, the actuation and gas trip tested, the cartridge weighed, the tank and hydro date checked, the interlock proven, and the tag and report issued. One is a glance to catch the obvious. The other is a functional test of the whole chain. An operator who logs the monthlies and skips the semi-annual has a system nobody has actually fired in years, which is a system nobody can vouch for.

What to document

When the fire marshal pulls the file, or a grease fire finally puts the system to the test, the tag on the cabinet is worth nothing without the report behind it. The report is what proves the system was right on the day you left, and it is the baseline the next tech reads against.

Capture the system type and manufacturer, whether it is UL 300 listed, the agent type and the tank weight or fill with its date, the cartridge weight against its charged weight, the fusible link temperatures and the date they were replaced, a confirmation that every nozzle is aimed at its current appliance with any appliance changes noted, the actuation and gas-trip test result, the interlock and alarm result, the cylinder hydro date, the K-class and placard status, the deficiencies found, and the tag result. If you re-aimed nozzles or flagged an appliance change, write what drove it, because the next person needs to see the kitchen changed and the system was brought back to it.

Field to recordWhy it matters
System type, manufacturer, UL 300 listedPre-UL-300 systems need replacement, not just service
Agent type, tank weight or fill, dateConfirms the agent is present and within its service life
Cartridge weight vs charged weightA light cartridge means a slow leak before anything else flags
Fusible link temperatures and replacement dateProves links were replaced, not just looked at
Nozzles aimed at current appliances, changes notedThe number one failure: coverage lost to an appliance change
Actuation and gas-trip test resultA system can look fine and still fail to fire
Interlock and alarm resultConfirms fuel and power cut on discharge
Cylinder hydrostatic test date12-year clock; flag it before it expires
K-class extinguisher and placard statusThe portable backup under NFPA 10
Deficiencies and tag resultBacks the tag and tells the AHJ what was found

Common mistakes

  • Tagging a system as passed without confirming the nozzles still aim at the current appliances after a layout change.
  • Looking at fusible links instead of replacing the metal-alloy links on the semi-annual.
  • Skipping the actuation test and calling a visual walk-by an inspection.
  • Not testing the gas valve, or leaving it latched open after the test instead of re-arming it.
  • Missing an overdue cylinder hydrostatic test because the date stamp was never read.
  • Ignoring grease loading on links and nozzles because the duct cleaning is somebody else's contract.
  • Leaving a nozzle without its blow-off cap so grease plugs the orifice before the next fire.
  • Softening a real deficiency to keep the customer happy instead of red-tagging an impaired system.

Field checklist

0 of 12 complete

Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.

Standards and references

The framework lives in a handful of documents, each owning a piece. NFPA 96 is the standard for ventilation control and fire protection of commercial cooking operations: the hood, the grease duct, the exhaust, the cleaning, and the requirement for an automatic fire-extinguishing system over the cooking equipment, inspected on a semi-annual basis by a qualified person. NFPA 17A is the standard for wet-chemical extinguishing systems, covering the system itself, the semi-annual service and the monthly owner inspection, and the cylinder hydrostatic test cycle.

UL 300 is the listing standard the system has to meet to protect modern cooking equipment, and it is why pre-1994-era dry-chemical systems are obsolete and slated for replacement rather than service. NFPA 10 governs the portable Class K extinguisher, its travel distance to the hazard, and its service. The exact section numbers shift between editions, so confirm them against the edition the jurisdiction has actually adopted and any local amendments before citing them on a report.

Above all of these is the AHJ, the authority having jurisdiction, who adopts the code, amends it, and enforces it, and the manufacturer, whose listed manual governs the specific nozzle coverage, link temperatures, agent and cartridge data, and the no-discharge test procedure for that system. When the manual and a rule of thumb disagree, the manual and the listing win. Cite the standard that controls the point and let the manufacturer's data and the AHJ govern the call.

Units and terms

The trade has its own vocabulary on a kitchen suppression job, and the same part shows up under different names across a manufacturer manual, a code, and a service ticket.

Wet chemical is the potassium-based liquid agent and the system type UL 300 requires for cooking hazards. A fusible link is the solder-jointed heat detector that releases the system at its rated temperature. Saponification is the reaction that turns burning grease into a smothering soap foam. The expellant cartridge is the gas cylinder that drives the agent out. K-class, or Class K, is the fire class and extinguisher type for cooking oils and fats. Semi-annual means the every-6-months technician service, distinct from the monthly owner inspection and the separate exhaust cleaning.

Wet chemical
The potassium-based liquid agent that saponifies and cools a grease fire; the system type UL 300 requires for cooking hazards
UL 300
The listing standard a kitchen suppression system must meet for modern cooking equipment; pre-UL-300 systems are obsolete
Fusible link
A solder-jointed heat detector holding the detection cable; melts at its rated temperature to actuate the system
Saponification
The reaction between the wet-chemical agent and hot grease that forms an oxygen-sealing soap foam
Expellant cartridge
The sealed nitrogen or CO2 cylinder punctured on actuation to push the agent out of the tank
K-class
The fire class and portable extinguisher type for cooking oils and fats, governed by NFPA 10
Semi-annual
The every-6-months service by a trained technician, distinct from the monthly owner inspection

Related tools

Calculators and readiness checks for this work

Next step: List restaurant service accounts

FAQ

How often is a kitchen hood suppression system inspected?

A trained technician inspects and services a commercial kitchen wet-chemical hood system every 6 months under NFPA 96 and NFPA 17A. The owner also performs a monthly visual check of the gauge, nozzle caps, pull station, and tag. The AHJ and adopted code edition control the enforced interval.

What is UL 300?

UL 300 is the listing standard a kitchen suppression system must meet to protect modern cooking equipment. Introduced in 1994, it moved the trade from dry chemical to wet chemical, which both smothers and cools grease so it cannot reflash. Pre-UL-300 systems are obsolete and typically must be replaced.

Do fusible links need replacing on a hood system?

Yes. Metal-alloy fusible links are commonly replaced at every semi-annual service because baked-on grease insulates them and raises their effective trip temperature. Other detector types are examined and cleaned or replaced at least annually. Match the replacement link to the rating stamped on the original and confirm the cadence against the manufacturer's manual.

What fails a hood suppression inspection?

The most common failure is lost nozzle coverage after an appliance was moved or swapped. Others: a gas valve that will not trip, grease-loaded or overdue fusible links, a light expellant cartridge, an overdue cylinder hydro, missing nozzle caps, a blocked manual pull station, or an expired tag. Functional testing catches what a visual walk-by misses.

How does the actuation test work without discharging agent?

The technician pulls the cartridge first so no agent can release, then trips the detection line to confirm the regulated release actuates. From there they verify the gas valve closes by hand, the electric shutoff drops, and the exhaust fan and alarm respond. The manual pull station is tested as a separate actuation path.

How often is the agent tank hydrostatically tested?

Wet-chemical agent cylinders are commonly hydrostatically tested every 12 years, after which the cylinder is tested or condemned. The technician reads the date stamp each semi-annual and tracks it so an overdue hydro is flagged before it expires. Confirm the interval against NFPA 17A and the cylinder marking.

Why does moving a fryer break the suppression system?

Pre-engineered systems aim each nozzle at a specific appliance at a listed size and height. Move a fryer out from under its nozzle, raise it, or grow it past the rated dimension, and the protection is gone even though the hardware looks untouched. The semi-annual exists to catch that drift and re-aim or re-engineer coverage.

Is a Class K extinguisher required in a commercial kitchen?

Yes. NFPA 10 requires a portable Class K wet-chemical extinguisher for cooking grease hazards, commonly within 30 ft of the cooking line, plus a placard telling users to actuate the fixed system first. It is the manual backup and the cool-down tool after the hood system discharges, on its own service cycle.

What is the difference between the monthly and semi-annual hood inspection?

The monthly is a quick visual the owner or a trained employee logs: gauge, nozzle caps, pull station, and tag. The semi-annual is the technician's functional service: replacing links, confirming nozzle aim, testing actuation and the gas trip, weighing the cartridge, checking the hydro date, and issuing the tag and report.

People also ask

Codes cited in this guide

This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.

NFPA 10NFPA 17ANFPA 96UL 300