ASTM D698-12(2021) establishes a soil's moisture-density relationship at standard compactive effort: 12,400 ft-lbf/ft3, or 600 kN-m/m3. The material specification selects Method A, B or C; gradation guides the choice when no method is specified. The report must identify the tested fraction and any oversize correction before its maximum dry density becomes a field reference. Otherwise, the numerator and denominator of a compaction percentage can describe different soil fractions.
Applies to
Geotechnical laboratories produce the reference curve, earthwork inspectors match field tests to the sampled material, and designers set the acceptance percentage and moisture band. Use the base and subgrade guide for placement and field acceptance. D698 does not assign a universal density target or test frequency. When grading work changes borrow sources, verify that the laboratory method and screened fraction still represent the delivered fill.
Key topics
Which Proctor method does the specification require?
ASTM D698-12(2021) gives the specified method priority; use gradation to choose among eligible methods when the material specification is silent. Method A permits at most 25 percent retained on No. 4, and Method B at most 25 percent retained on 3/8 inch. Both use a 4-inch mold and three layers of 25 blows. Method C uses the fraction passing 3/4 inch, a 6-inch mold and three layers of 56 blows. The larger mold is prohibited for A and B.
When more than 5 percent oversize changes the comparison
ASTM D698-12(2021) requires D4718/D4718M correction when excluded oversize exceeds 5 percent by mass. Correct both the unit-weight and water-content basis, either for the laboratory specimen or the appropriate field specimen. ASTM D4718/D4718M-15(2023) permits bringing the laboratory and field results onto either a total-material or finer-fraction basis. Identify the selected basis beside the reported density; changing only one side of the comparison defeats the correction.
Why crushing in the mold can create an unreachable target
D698 identifies particle degradation as a source of unrepresentative laboratory maxima: when laboratory compaction breaks down more aggregate than field compaction, the denser laboratory grading can produce a maximum the field cannot achieve. It also prohibits reusing soil already compacted in the laboratory. Investigate changing gradation and specimen preparation when repeated field results remain low despite suitable moisture and the specified rolling effort.
Recognize soils outside a straightforward Proctor comparison
ASTM D698 limits its methods to material with no more than 30 percent retained on the 3/4-inch sieve. Its public guidance describes test fills and method specifications for problematic coarse soils, including equipment, lift thickness, moisture range and passes. Free-draining and gap-graded materials also need attention because a sharp, representative moisture-density maximum can be difficult to obtain. Resolve that control basis before calling repeated low percentages a roller failure.
How it is used in the field
A sample has 32 percent retained on No. 4, 18 percent on 3/8 inch and 8 percent on 3/4 inch. Method A is outside its gradation limit; Method B is eligible, as is Method C. If the contract specifies B, its excluded 18 percent exceeds the 5 percent correction threshold. Under C, the excluded 8 percent also needs correction. Report the specified method and actual excluded fraction with the curve so either result can be compared with field material on the same basis.
For an accepted, corrected laboratory maximum of 125 lb/ft3 and a field dry density of 120 lb/ft3 on the same basis, relative compaction is 96 percent. Compare that result with the project's stated target and moisture band. Keep the corrected and original figures so the reviewer can reproduce the comparison. A percentage without its material basis conceals the adjustment that made the numbers comparable.
When a borrow source changes, identify the new sample and material description before assigning another field result to the existing curve. A different aggregate fraction or particle durability changes the laboratory question, even if both deliveries have the same commercial description. The grading guide covers field placement; the laboratory record establishes the reference used to accept it.
For a coarse fill outside the 30 percent limit, document the specified alternative control plan and test-fill results rather than reporting a D698 percentage from an unrepresentative screened sample. Preserve the agreed equipment, lift, moisture and pass requirements with each accepted area. D698's discussion of problem soils explains why the control method has to change with the material.
Edition history
ASTM lists D698-12(2021) as active. The 2012 designation identifies the revision and 2021 its reapproval. The related correction practice is D4718/D4718M-15(2023); neither the year nor method letter should disappear when the laboratory transfers results into a contractor's worksheet.
Earthwork estimators following municipal paving schedules use PorchRocket's Bid Control to find public paving bids and early agency capital-plan signals.
Frequently asked questions
Can the soil from one Proctor point be compacted again for the next point?
D698 excludes material previously compacted in the laboratory. Reuse can change particle structure or grading and is outside that specimen requirement.
Does a 6-inch mold make a test Method C?
Method C includes the specified material fraction and procedure as well as mold diameter. Identify the full method on the report; D698 expressly bars the 6-inch mold from Methods A and B.
Can every coarse fill be corrected into a D698 result?
The method's 30 percent retained-on-3/4-inch limit remains. D4718 also has applicability limits, including particle interference and degradation, so correction arithmetic does not extend the test to every soil-rock mixture.