Electrical
GFCI and AFCI protection: where the NEC requires each
Two devices, two jobs: the GFCI protects the person from a shock, the AFCI protects the building from an arcing-fault fire. Know which the code wants where.
Direct answer
GFCI and AFCI are two different devices doing two different jobs. A GFCI protects a person from shock, tripping at 4 to 6 mA of current leaking to ground. An AFCI protects the building from fire by detecting the signature of an arcing fault. The adopted NEC edition and the AHJ control where each is required.
On this page
GFCI and AFCI, two devices doing two different jobsWhat is the difference between GFCI and AFCI?How does a GFCI work?How does an AFCI work?Where is GFCI required?Where is AFCI required?Which device do I use: receptacle, breaker, or dual-function?Line and load: the wiring that makes downstream protection workGFCI on two-wire systems with no groundWhy does my GFCI keep tripping?Testing GFCI and AFCI: the button, the self-test, the scheduleGFCI for temporary power on the jobsiteGFPE is not GFCIGFCI in commercial kitchens and data centersThe AHJ and the adopted edition governField example: protection map for a small remodelWhat to documentCommon mistakesField checklistStandards and referencesUnits, terms, and synonymsOpen the related tool for the calculation, checklist, or packet.
FieldOS by AnvilfieldOffline-first FieldOS for job photos, proof packets, property memory, calculations, teams, billing, and owner-ready reports.Key takeaways
- A GFCI protects a person from shock; an AFCI protects the building from an arcing-fault fire. They are not interchangeable.
- A Class A GFCI under UL 943 trips at 6 mA of leakage to ground and must not trip below 4 mA.
- NEC 210.8 governs where GFCI is required (near water and earth); NEC 210.12 governs where AFCI is required (dwelling living-space circuits).
- Reversing LINE and LOAD leaves the outlet powered but the GFCI protection gone, so always test feed-through after wiring.
- Press the GFCI/AFCI test button about every 30 days; the UL 943 self-test since 2015 is a backstop, not a replacement.
GFCI and AFCI, two devices doing two different jobs
GFCI and AFCI get talked about together and confused constantly, but they protect against different hazards and they do it with different physics. A ground-fault circuit interrupter, the GFCI, watches for current escaping the circuit and finding a path to ground, which is the path that runs through a person. An arc-fault circuit interrupter, the AFCI, listens for the electrical signature of an arc, which is the thing that starts a fire inside a wall.
The clean way to hold it in your head: the GFCI protects the person, the AFCI protects the building. One is about a shock. The other is about a fire. They are not interchangeable, and installing one where the code calls for the other is not protection, it is a failed inspection waiting to happen.
Where they overlap, you can get both functions in a single device, the dual-function AFCI-GFCI breaker, but that is one box doing two jobs, not one job covering both. The rest of this guide is about which job the code wants where, how each device actually works, and the wiring and testing that decide whether the protection is real or just present on the panel schedule.
What is the difference between GFCI and AFCI?
The difference is the hazard each one is built to stop. A GFCI stops electrocution. It compares the current going out on the hot against the current coming back on the neutral, and when those two stop matching, current is leaving the circuit somewhere it should not, often through a person, and the device cuts power fast. An AFCI stops fires from arcing. It samples the waveform and recognizes the erratic, high-frequency mess that an arcing connection or damaged cable makes, then trips before that arc ignites the wood and insulation around it.
Because they answer different questions, neither covers for the other. A GFCI will sit there untripped while a loose backstab connection arcs behind a receptacle, because the current going out still equals the current coming back. An AFCI will not save someone touching a faulted appliance, because a clean fault to ground through a body is not the arc signature it is looking for. That is exactly why the code requires them in different places, and why the dual-function device exists for the rooms that need both.
Sizing the circuit that feeds these loads is its own task. The load calculation that sets the branch-circuit and feeder ampacity is covered separately, and the protection here rides on top of conductors that were already sized for the load.
How does a GFCI work?
A GFCI works by measuring the imbalance between the hot and the neutral. In a healthy circuit every amp that leaves on the hot returns on the neutral, so the two are equal and the difference is zero. The device runs both conductors through a small current transformer that sums them. As long as they cancel, nothing happens. The moment some current leaves the circuit on a third path, to ground or through a person, the hot and neutral no longer match, the transformer sees the difference, and the electronics trip the device.
The trip point is what makes it a personnel device. A Class A GFCI under UL 943 has to trip when that imbalance reaches 6 mA and must not trip below 4 mA, and it does it fast, within tens of milliseconds. That 4 to 6 mA window sits below the current that locks up muscle control and stops a person letting go, which is the whole design intent. The GFCI does not care how big the load is. It cares only about the small difference between what went out and what came back.
One consequence trips up new hands: a GFCI does not need an equipment ground to function. It is watching the hot-to-neutral balance, not the ground. That is why a GFCI receptacle is the code-recognized way to provide protected, three-prong outlets on an old two-wire system that has no ground at all.
How does an AFCI work?
An AFCI works by recognizing the electrical fingerprint of an arc. Normal loads have signatures the device is trained to ignore: a motor starting, a switch making contact, a dimmer chopping the waveform. An arcing fault looks different. The current is erratic, broadband, full of the high-frequency noise that a small sustained spark throws off. The AFCI samples the waveform continuously and runs it through signal-processing logic that separates that arc signature from the normal load noise, then trips when it has enough evidence of a real arc.
There are two kinds of arc it has to catch. A series arc happens in a single conductor, at a broken strand or a loose terminal, where the current jumps the gap in line with the load. A parallel arc happens between conductors, hot to neutral or hot to ground, usually where insulation is damaged, a staple was driven too deep, or a nail or screw found the cable. A combination-type AFCI, which is what the code generally calls for, is built to detect both, and it does so at low arcing currents that an ordinary breaker would never see as an overload.
The hard part of the design is not catching arcs, it is not crying wolf. The whole game is telling a real hazardous arc apart from the harmless arcing inside a vacuum cleaner motor or a light switch, which is why early AFCIs had a reputation for nuisance trips and why the detection logic keeps getting refined.
Where is GFCI required?
GFCI protection is required by NEC 210.8 in the places where a person is near water or earth, the conditions that make a shock deadly. In dwellings the list has grown to cover bathrooms, kitchens, garages and accessory buildings at or below grade, outdoors, basements, laundry areas, and receptacles within a set distance of a sink. The driving idea is simple: wet skin and a grounded surface drop the body's resistance, so a fault that would be a jolt on a dry floor becomes lethal at the kitchen sink.
The thing to understand about 210.8 is that it expands almost every code cycle. Receptacles that needed no GFCI two editions ago need it now. Basements went from unfinished-only to all basements. The covered voltage range widened. Garages, accessory buildings, and outdoor outlets keep getting pulled in. So the honest answer to where it is required is: more places than the last edition you memorized, and the only reliable source is the edition your jurisdiction has actually adopted.
Do not work from the list in your head. Pull 210.8 from the adopted code and read it for the occupancy you are wiring, because the dwelling list at 210.8(A) and the other-than-dwelling list at 210.8(B) are different and both have moved.
Where is AFCI required?
AFCI protection is required by NEC 210.12 on the branch circuits that feed the living spaces of a dwelling. It started decades ago with bedroom circuits, on the logic that a fire that starts while people sleep is the one that kills them, and it has spread from there to cover most of the dwelling. Current editions reach the kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, and laundry areas, on the 120 V, single-phase, 15 and 20 A circuits supplying outlets in those areas.
Like GFCI, this is a list that has only grown. The protected circuit types and rooms have expanded edition to edition, and recent code added lower-amperage circuits to the requirement. The pattern across both 210.8 and 210.12 is the same: each cycle the protection reaches further, so the question is never just what does the NEC require, it is what does the adopted edition require.
Note the overlap. Several of the rooms that need AFCI, the kitchen and the laundry, also need GFCI for their receptacles. That overlap is exactly why the dual-function breaker is the practical answer for those circuits, and why the device-selection decision below is not academic.
Which device do I use: receptacle, breaker, or dual-function?
Four common form factors deliver this protection, and picking the wrong one is a cost and rework problem more than a code one. The receptacle GFCI protects at the outlet and, wired correctly, protects everything downstream of it. The breaker GFCI protects the whole circuit from the panel. The AFCI breaker does the same for arc protection. The dual-function AFCI-GFCI breaker combines both functions in one panel slot, which is the clean answer for a kitchen or laundry circuit that needs each.
There is also the deadfront GFCI, a device with no receptacle face, used to protect downstream outlets from a point in the run where you do not want a usable outlet, a common move at a panel or a junction feeding a string of standard receptacles. It works on the same line-and-load principle as the receptacle version.
The trade-off is usually cost against count. A single breaker GFCI or AFCI protects the entire circuit, but it costs more than a standard breaker and a nuisance trip kills the whole circuit. A receptacle GFCI is cheaper per device but you may need several. For arc protection there is no receptacle-only shortcut for whole-circuit coverage the way there is for GFCI, so AFCI usually lives at the breaker.
| Device | Protects | Where it is used |
|---|---|---|
| Receptacle GFCI | The outlet plus downstream on load side | Single locations, two-wire retrofits, kitchen counters |
| Deadfront GFCI | Downstream devices, no usable face | Feed point for a run of standard receptacles |
| Breaker GFCI | Entire branch circuit from the panel | Whole-circuit ground-fault coverage |
| AFCI breaker | Entire branch circuit for arc faults | Dwelling living-space circuits under 210.12 |
| Dual-function AFCI-GFCI breaker | Both arc and ground fault, whole circuit | Kitchen, laundry, and rooms needing both |
Line and load: the wiring that makes downstream protection work
A GFCI receptacle has two pairs of terminals, marked LINE and LOAD, and getting them right is the difference between protecting one outlet and protecting a run of them. The incoming power from the panel, or from the upstream device, lands on LINE. Any wiring that continues on to feed other receptacles lands on LOAD. Connect it that way and every standard outlet fed from the LOAD side is protected by that one GFCI, which is the feed-through trick that saves you buying a GFCI for every box.
Wire only the LINE terminals and the GFCI still protects itself and whatever plugs into its own face, but nothing downstream is covered. That is fine when you want it, and a hidden hazard when you did not. The classic miswire is reversing LINE and LOAD. Do that and here is the trap: the outlet still powers up and looks normal, but the GFCI protection is gone, and pressing the test button may not behave the way it should. A working outlet is not a protected outlet.
This is why you test feed-through after wiring, not just the device itself. Put a tester on the downstream outlets and confirm they trip when the GFCI trips. An outlet that keeps power after the upstream GFCI is tripped is telling you the load side never made it onto the LOAD terminals.
GFCI on two-wire systems with no ground
Old houses wired before grounding was standard have two-wire circuits with no equipment grounding conductor at the receptacle, and people want three-prong outlets on them. A GFCI is the code-recognized answer, and it works because the GFCI does not rely on the ground to function. It watches the hot-to-neutral imbalance, so it will still trip on a fault to a person even with no ground present, which is exactly the protection that ungrounded circuit lacks.
The rule that goes with it is the labeling. When a GFCI replaces a non-grounding receptacle on a two-wire circuit, the receptacle and any grounded-type outlets fed downstream from it have to be marked, commonly with a 'No Equipment Ground' label and, on the GFCI itself, 'GFCI Protected'. Those markers are not optional and the inspector looks for them. They tell the next person that the box has shock protection but no ground path, so anything that needs a real ground, a surge protector or some electronics, is not actually getting one here.
The trap is assuming the GFCI gave the circuit a ground. It did not. It gave the circuit shock protection. A three-prong tester that checks for a ground will read open ground at these outlets and that is correct, not a defect, as long as the labels are in place.
Why does my GFCI keep tripping?
A GFCI that keeps tripping is doing its job until proven otherwise, so the first question is always whether the trip is real. A real trip means current is actually leaving the circuit, through a worn appliance cord, a wet box, a damaged tool, or a deteriorated cable. Find that fault before you blame the device, because a device that trips on a genuine ground fault is not nuisance-tripping, it is working.
The nuisance causes are a short list. A shared neutral is the big one: a multi-wire branch circuit, or a neutral accidentally tied to another circuit's neutral, sends return current down a path the GFCI's sensor never sees, which reads as a permanent imbalance and a guaranteed trip. Long cable runs build up capacitive leakage between conductors that can accumulate past the 4 to 6 mA threshold on their own. Motor loads leak current through winding-to-frame capacitance. Moisture in outdoor boxes, and some older fluorescent and electronic ballasts, add leakage too.
AFCIs nuisance-trip for related but different reasons: a shared neutral confuses the arc-detection logic the same way, and the high-frequency noise from some motors and electronics can read like an arc. The fix for both is the same discipline. Isolate the circuit, unplug everything, and add loads back one at a time. What you do not do is defeat the device. Pulling the GFCI to stop the trips, or replacing an AFCI with a standard breaker because it keeps nagging, removes the protection and leaves the actual fault live.
Testing GFCI and AFCI: the button, the self-test, the schedule
Every GFCI and AFCI device has a test button, and it is not decoration. Pressing it forces an internal fault to confirm the device will actually trip when it counts. The trade lesson here is old and unglamorous: these are electronic devices, they fail, and a GFCI that has quietly died still passes power and still looks fine in the wall. The only way you know it will protect anyone is to trip it and reset it.
Since 2015, UL 943 has required GFCIs to include an auto-monitoring or self-test function that periodically checks itself, and depending on the failure mode the device either denies power or signals that it has failed. That self-test is a backstop, not a replacement for the manual test. UL still calls for testing the device about every 30 days with the button, and that monthly habit is what catches the unit that died between self-tests or never self-tested at all.
AFCI testing is its own note. The self-test requirement in the standard is written around the GFCI function, so do not assume the arc-detection electronics are being verified the same way. Use the device's own test button per the manufacturer's instruction, and where a circuit is dual-function, test it as both.
GFCI for temporary power on the jobsite
On a construction site the GFCI question is governed by OSHA, not just the NEC, and the rule is blunt: temporary 120 V, single-phase, 15 and 20 A receptacles that are not part of the permanent wiring either get GFCI protection or they get covered by a written assured equipment grounding conductor program. One or the other. There is no option where the crew runs neither.
GFCI is the path most jobs take because it needs no paperwork, just the device. The trouble is that the same long temporary feeders, welders, big pumps, and concrete saws that live on a site are exactly the loads that nuisance-trip a GFCI through leakage and inrush. When the trips get bad enough that crews start defeating the devices, that is the signal to run the assured equipment grounding conductor program instead, which keeps the ground path verified by testing rather than by the GFCI. That program, its two required tests, and its records are covered in the AEGCP guide.
Either way, the failure mode to watch on a site is the defeated device. A GFCI that has been bypassed because it kept tripping is worse than no plan at all, because everyone assumes the protection is there.
GFPE is not GFCI
Ground-fault protection of equipment, GFPE, gets confused with GFCI because the names rhyme and both watch for current going to ground. They are not the same device and they do not protect the same thing. A GFCI protects people, and it trips at 4 to 6 mA, a current too small to hurt the wiring but big enough to hurt a person. GFPE protects equipment and the building from the damage a sustained arcing ground fault does, and it operates at far higher currents, set to clear before a fault burns up gear.
The numbers tell the difference. GFPE for marina and dock circuits is commonly set at a level measured in tens of milliamps for equipment, while GFPE on large services operates in the hundreds or low thousands of amps with a deliberate time delay. The NEC requires GFPE on certain large solidly-grounded services, a requirement commonly cited around the service and feeder articles, with a maximum setting and a maximum clearing time written into the rule. Confirm the exact threshold, the ampere rating that triggers it, and the section against the adopted edition, because the values and the triggering service size have changed across cycles.
The practical mistake is assuming a service with GFPE protects the people downstream the way a GFCI does. It does not. GFPE will let a current through that would electrocute someone twenty times over, because that is not its job. People protection still rides on the GFCIs at the point of use.
GFCI in commercial kitchens and data centers
Outside dwellings the GFCI requirements live in 210.8(B), and that list has expanded hard in recent cycles to cover commercial kitchens, areas with sinks, food and beverage prep and serving areas, rooftops, indoor wet and damp locations, locker rooms, garages and service bays, and laundry areas. If you wire commercial work from a residential mental model you will miss outlets the code now requires to be protected, and the inspector will not.
The friction shows up in data centers and other sensitive-equipment spaces. The same code cycles that pulled more receptacles into 210.8(B) also caught circuits feeding equipment that does not tolerate a nuisance trip well, and the leakage from rows of switch-mode power supplies can sit close to the GFCI threshold all on its own. The result is a real tension between a protection requirement and equipment that trips it, which is a design conversation to have with the engineer and the AHJ before rough-in, not a field decision to make by leaving the GFCI out.
The move is to plan the branch-circuit layout so leakage-heavy loads are not stacked on a single protected device, and to confirm with the AHJ how the adopted edition applies to the specific equipment. Quietly omitting required GFCI because the gear nuisance-trips is the kind of shortcut that surfaces at inspection or after an incident.
The AHJ and the adopted edition govern
Every requirement in this guide is filtered through one fact: the NEC is a model code, and it only has force where a jurisdiction has adopted it. The edition your area enforces may be a cycle or two behind the latest published one, and it may carry local amendments that add or relax requirements. So the GFCI and AFCI rules that apply to your job are the ones in the adopted edition, not the newest book on the shelf and not the version you learned in a class three years ago.
This matters more for GFCI and AFCI than for almost any other topic, because 210.8 and 210.12 are among the fastest-moving sections in the code. Each cycle they reach more locations, more circuit types, and wider voltage and amperage ranges. Citing the rule from memory is how you end up arguing with an inspector who is reading a different edition than the one in your head.
When the question is whether a specific outlet or circuit needs protection, the answer is to read the adopted section and, where it is ambiguous, ask the AHJ. The authority having jurisdiction is the final word on how the code applies to your installation, and a quick call before rough-in is cheaper than a red tag after.
Field example: protection map for a small remodel
Here is how the decisions land on a typical dwelling remodel panel, mapping each circuit to the device and the code basis. The point is not the exact circuit list, which varies by adopted edition, but the habit of writing the basis next to the device so the panel schedule defends itself at inspection.
Notice the kitchen and laundry rows. They need GFCI for the receptacles and AFCI for the circuit, so the dual-function breaker does both in one slot rather than stacking a GFCI receptacle behind an AFCI breaker. Verify every one of these against the edition your jurisdiction enforces before you order devices, because the rooms and ranges shift each cycle.
| Circuit | Protection | Device used | NEC basis | Tested |
|---|---|---|---|---|
| Bathroom receptacles | GFCI | GFCI breaker or receptacle | 210.8 dwelling | Button and feed-through |
| Kitchen counter receptacles | GFCI plus AFCI | Dual-function breaker | 210.8 and 210.12 | Button, both functions |
| Bedroom lighting and receptacles | AFCI | AFCI breaker | 210.12 dwelling | Button |
| Garage receptacles (at grade) | GFCI | GFCI breaker or receptacle | 210.8 dwelling | Button and feed-through |
| Laundry area | GFCI plus AFCI | Dual-function breaker | 210.8 and 210.12 | Button, both functions |
| Outdoor receptacles | GFCI | GFCI breaker or receptacle | 210.8 dwelling and outdoor | Button and feed-through |
What to document
The record that matters is the one that lets the next person, an inspector, a future electrician, or you in two years, see what is protected, by what, on what basis, and that it was actually tested. A panel schedule that just says AFCI on a breaker is half a record. The basis and the test result are the other half.
Capture the circuit and the room it serves, the kind of protection (GFCI, AFCI, or both), the device form factor used, the code section that drove the requirement and the edition you worked from, and the result of the post-install test including the feed-through check on any GFCI feeding downstream outlets. If you left a circuit unprotected on purpose under an exception, write the exception down, because an unprotected circuit with no note reads as a mistake to anyone who finds it later.
| Field to record | Why it matters |
|---|---|
| Circuit and room served | Ties the protection to a location the inspector checks |
| Protection type (GFCI, AFCI, both) | Confirms the right hazard is covered |
| Device form factor | Receptacle, breaker, or dual-function for the next service call |
| NEC section and adopted edition | Defends the decision against a different code book |
| Test result and date | Proves the device actually trips, not just exists |
| Feed-through verified | Confirms downstream outlets are really protected |
| Exception used, if any | An unprotected circuit with no note reads as an error |
Common mistakes
- Leaving out GFCI where 210.8 now requires it, working from an older edition's location list.
- Skipping AFCI on a living-space circuit that 210.12 covers in the adopted edition.
- Reversing LINE and LOAD, so the outlet powers up but the protection and feed-through are gone.
- Calling a working outlet a protected outlet without ever pressing the test button.
- Defeating a nuisance-tripping device instead of finding the shared neutral or the real fault.
- Confusing GFPE with GFCI and assuming a service with GFPE protects people downstream.
- Installing an AFCI where the code wants GFCI, or the reverse, treating them as interchangeable.
- Stacking leakage-heavy loads on one GFCI in a commercial or data-center space, then omitting it when it trips.
Field checklist
Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.
Standards and references
The NEC, NFPA 70, is where the installation requirements live. GFCI protection is at 210.8, split into the dwelling list at 210.8(A) and the other-than-dwelling list at 210.8(B), with additional outdoor provisions. AFCI protection is at 210.12 for dwellings. Both sections expand most cycles, so cite them only against the edition the jurisdiction has actually adopted, with local amendments.
Ground-fault protection of equipment, a different animal from GFCI, is handled in the feeder and service articles, commonly referenced around 215 and 230 for the large-service requirement and in the specific occupancy articles for lower-current equipment protection. Confirm the exact section, the triggering service size, and the maximum setting against the adopted edition rather than from memory, because those values have moved. The general duty to install and use any device per its listing and the manufacturer's instructions comes from 110.3(B), and it controls when the instruction is stricter than the rule of thumb.
The product standards behind the devices are UL 943 for GFCIs, including the auto-monitoring self-test requirement, and UL 1699 for AFCIs, including the combination-type detection of series and parallel arcs. On construction sites, OSHA at 29 CFR 1926.404(b)(1) sets the GFCI-or-AEGCP choice for temporary power. The adopted code edition and the AHJ govern the install, and the manufacturer's instructions govern the device.
Units, terms, and synonyms
The same devices and ideas go by several names across drawings, spec sheets, and the trade, so the vocabulary is worth pinning down.
A GFCI is also written GFI in older and field usage, and a receptacle version is often just called a GFCI outlet. The current it watches is leakage or ground-fault current, measured in milliamps. An AFCI may be labeled an arc-fault breaker, and the type the code usually wants is the combination-type AFCI. The combined device is the dual-function or AFCI-GFCI breaker. GFPE, ground-fault protection of equipment, is sometimes called ground-fault protection or GFP, and it is the one to keep separate from GFCI.
- GFCI / GFI
- Ground-fault circuit interrupter, protects a person by tripping at 4 to 6 mA of leakage to ground
- AFCI
- Arc-fault circuit interrupter, protects the building by detecting the signature of an arcing fault
- Combination-type AFCI
- An AFCI that detects both series arcs and parallel arcs, the type the code generally requires
- Dual-function breaker
- One breaker providing both AFCI and GFCI protection, common on kitchen and laundry circuits
- Line and load
- LINE is the incoming supply terminals; LOAD feeds and protects downstream outlets
- GFPE / GFP
- Ground-fault protection of equipment, protects gear at much higher currents, not a personnel device
- Self-test / auto-monitoring
- A GFCI's built-in periodic check of its own ability to trip, required under UL 943 since 2015
Field notes
FAQ
What is the difference between GFCI and AFCI?
A GFCI protects a person from a shock by tripping when 4 to 6 mA of current leaks to ground. An AFCI protects the building from fire by detecting an arcing fault. They stop different hazards and cannot substitute for each other, which is why the dual-function breaker exists for circuits that need both.
Where is GFCI required in a house?
NEC 210.8 requires GFCI in dwellings near water and earth: bathrooms, kitchens, garages and accessory buildings at or below grade, outdoors, basements, laundry areas, and receptacles within a set distance of a sink. The list expands almost every code cycle, so read the adopted edition rather than an older location list.
Where is AFCI required?
NEC 210.12 requires AFCI on dwelling living-space circuits: kitchens, family and dining rooms, living rooms, bedrooms, sunrooms, closets, hallways, laundry areas, and similar spaces, on 120 V 15 and 20 A circuits. It started with bedrooms and keeps spreading. Confirm the rooms and circuit types against the adopted edition.
Why does my GFCI keep tripping?
First confirm it is not a real fault: a worn cord, a wet box, or a damaged tool will trip it correctly. Nuisance causes are a shared neutral, capacitive leakage on a long run, motor leakage, or moisture. Isolate the circuit and add loads back one at a time. Never just defeat the device.
Why does my AFCI breaker keep tripping?
An AFCI trips on a real series or parallel arc, so check for loose terminals and damaged cable first. Nuisance trips often come from a shared neutral confusing the detection logic, or high-frequency noise from a motor or electronics reading like an arc. Isolate loads one at a time. Do not swap it for a standard breaker.
Can a GFCI protect other outlets downstream?
Yes, if it is wired right. Land the incoming power on the LINE terminals and the wiring that continues to other outlets on the LOAD terminals. Every standard receptacle fed from the LOAD side is then protected. Reverse LINE and LOAD and the outlet still works but the protection is gone, so always test feed-through.
How often should I test a GFCI?
Press the test button about every 30 days, even though UL 943 has required a built-in self-test since 2015. The self-test is a backstop, not a replacement, because a GFCI can fail and still pass power while looking normal. The monthly manual test confirms it will actually trip when someone needs it.
Is GFPE the same as GFCI?
No. GFPE, ground-fault protection of equipment, protects gear at far higher currents and does not protect people. A GFCI trips at 4 to 6 mA for personnel protection. A service with GFPE will pass current that would electrocute someone, because that is not its job. People protection still rides on the GFCIs at the point of use.
Is a dual-function breaker the same as a GFCI?
No, it does more. A dual-function breaker combines AFCI and GFCI in one device, so it protects against both arcing faults and ground faults on the whole circuit. It is the practical choice for kitchen and laundry circuits that need both under 210.8 and 210.12. Test both functions after install, not just one.
People also ask
Codes cited in this guide
This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.