Electrical
Lightning protection system field guide (NFPA 780)
Give the strike a path around the building, bond everything to one ground, and protect the electronics with surge devices, not the rods.
Direct answer
A lightning protection system gives a lightning strike a low-impedance path to ground around a structure, using air terminals, down conductors, and grounding electrodes bonded into the building ground per NFPA 780. It does not stop a strike or protect electronics. Surge protection devices handle the transient that gets inside.
Key takeaways
- A lightning protection system gives a strike a low-impedance path to ground per NFPA 780; it does not stop strikes or protect electronics.
- NFPA 780 requires at least two down conductors on any structure, spaced averaging not more than 100 ft around the protected perimeter.
- Air terminals sit at least 10 in above the object, within 2 ft of edges and corners, and not more than about 20 ft apart on ridges.
- The rolling sphere method, commonly 150 ft radius for structures up to 75 ft, marks every point the sphere touches as exposed and needing a terminal.
- Bond the LPS ground to the building grounding electrode system and all metal; an isolated ground causes side flash, and surge devices protect the electronics.
What a lightning protection system does, and what it does not
A lightning protection system, an LPS, is a path. It gives a strike a deliberate, low-impedance route from the point it hits down the outside of the structure and into earth, so the energy goes around the building instead of through it. That is the whole job. Air terminals catch the strike, down conductors carry it down, grounding electrodes spill it into the soil, and bonding keeps everything at one potential while it happens.
Here is what an LPS does not do, and the part that gets people in trouble. It does not stop lightning from striking. Nothing a contractor installs prevents a strike, and the old marketing about rods that bleed off the charge and keep the cloud from firing was never true. It also does not protect the electronics inside. A direct strike to a properly built LPS still throws a massive electromagnetic pulse and drives a transient onto every wire entering the building, and that transient is what fries panels, drives, controllers, and servers.
The electronics are protected by surge protection devices, not by the rods. The LPS handles the direct strike. The SPD handles the transient that rides in on the power and data conductors. The two are a pair, and an LPS installed without coordinated surge protection leaves the most expensive thing in the building exposed. NFPA 780 treats surge protection as part of a complete system for exactly this reason. See the surge protection guide for how the SPD side is sized and installed.
The parts of a lightning protection system
An LPS is five functional parts working together, and a weakness in any one of them undoes the rest. Miss the strike at the top, choke it on the way down, fail to get it into the ground, skip the bonding, or leave the electronics unprotected, and you have an expensive roof ornament instead of a system.
Think of it as catch, carry, ground, equalize, and clamp. The strike termination catches it. The down conductors carry it. The grounding electrodes get it into earth. The bonding equalizes potential so nothing inside sees a dangerous difference. The surge devices clamp the transient that gets onto the building wiring. NFPA 780 specifies the materials, sizes, geometry, and connections for each.
| Part | What it does | Where it lives |
|---|---|---|
| Strike termination (air terminals) | Intercepts the strike at a known point | High points, ridges, edges, corners, projections |
| Down conductors | Carry strike current to ground | Down the exterior, two or more paths |
| Grounding electrodes | Discharge current into the soil | At each down conductor, plus ground ring |
| Bonding / potential equalization | Keeps everything at one potential | Between LPS, building ground, metal bodies, utilities |
| Surge protection (SPD) | Clamps the transient on building wiring | Service entrance, panels, data and signal lines |
Where do air terminals go and how high?
Air terminals, the rods or points, go on the high points and along the edges, because that is where lightning attaches. NFPA 780 puts a minimum height on them and a maximum spacing, and both numbers are commonly missed in the field. Terminals are commonly set at least 10 in above the object they protect, and they are placed at intervals averaging not more than 20 ft along ridges and around the roof perimeter for terminals up to 24 in tall. Taller terminals, 24 in and up, can be spaced out to about 25 ft. Confirm the spacing against the adopted edition.
Edges and corners are where the system earns its keep, because the strike attaches to the perimeter far more than the open field of the roof. Terminals go within 2 ft of outside corners and roof edges, and within about 24 in of ridge ends. On a flat roof the rule shifts: no point on the roof should be more than about 50 ft from a terminal, so a large flat roof gets a grid of terminals across the field, not just a ring around the parapet. This is the Faraday or mesh approach, a conductor grid with terminals at the intersections.
The rookie version puts a few tall rods at the corners and calls it done. That leaves the long edge runs and the roof field unprotected, and it ignores every rooftop projection, the vents, the stacks, the antennas, the rooftop units, each of which is a preferred attachment point and each of which needs its own terminal or has to fall inside the protected zone. The geometry is set by the rolling sphere, not by where the rods look balanced.
What is the rolling sphere method?
The rolling sphere method is how you decide where the air terminals have to be so the structure sits inside the protected zone. You imagine a sphere of a fixed radius rolling over and around the building, touching the air terminals and the high points. Anywhere the sphere can touch the structure itself is exposed and needs a terminal. Anywhere the sphere rides up and over without touching the building is inside the zone of protection.
NFPA 780 commonly uses a 150 ft rolling sphere radius for ordinary structures, those up to about 75 ft in height. Taller structures and higher protection levels can call for a smaller sphere, which is more demanding because a smaller sphere drops into more gaps and finds more exposed surface. The sphere radius is the design lever. Verify the radius for the structure class and the protection level against the standard.
The method is unforgiving about projections. A vent pipe, a small dish, a railing, anything that pokes up where the sphere can touch it, is exposed and either gets its own terminal or gets bonded and treated as part of the system if it is heavy enough metal. The common field error is placing terminals by eye and assuming a corner rod protects the whole face. Roll the sphere on paper first. The terminals go where the geometry says, and on a complicated roof that is more terminals than the estimate usually carried.
How many down conductors do you need?
At least two. NFPA 780 sets a floor of two down conductors on any structure, no matter how small, so the strike always has more than one path to ground. A single down conductor is a single point of failure, and lightning current splits across the available paths, so more paths means less current and less voltage rise on each one. That division is the reason two is a minimum and large buildings carry many more.
Around the perimeter, down conductors are spaced at intervals averaging not more than 100 ft of protected perimeter. Add up the perimeter, divide by 100 ft, and that sets the count before you even look at the corners. Conductors come down the outside of the structure on the most direct route, or concealed in a chase where the architecture demands it, and they tie the roof conductor network to the grounding at the base.
Routing is where installs go wrong. Lightning current does not like to turn, and a sharp bend or a U-shaped drip loop can flash over to the inside of the bend or push current off the conductor entirely. NFPA 780 sets a minimum bend radius of about 8 in and does not allow a bend to turn through more than 90 degrees, so the conductor runs down and out, never down and back up. No tight bends, no routing a conductor up and over a parapet and back down into a pocket. The most direct downward path, the fewest turns, the gentlest radius you can give it.
Grounding: electrodes at each down conductor and the ground ring
Every down conductor has to reach earth, so each one terminates at a grounding electrode. The common electrode is a driven ground rod, often 1/2 in diameter or larger and on the order of 8 to 10 ft long, set so it makes solid contact with moist soil below the dry surface layer. On a structure with many down conductors, the electrodes are tied together with a ground ring, a counterpoise conductor buried around the building at a depth of not less than 18 in. The ring ties the whole base into one electrode and keeps the down conductors at a common potential when current hits.
Soil is the variable nobody controls. Sandy, rocky, or dry ground has high resistivity, and a single rod in poor soil can read a resistance high enough that the current does not spill fast enough. The fixes are more electrodes, the ground ring, longer rods, or chemical and concrete-encased electrodes where the soil fights you. NFPA 780 is concerned with getting the current into earth efficiently and with keeping the LPS ground at the same potential as everything else, not with hitting one magic ohm number.
The connection that has to exist, and the one most often missed, is the bond between the LPS grounding and the building's grounding electrode system. The lightning ground, the electrical service ground, the telecom and antenna grounds, and the underground metal piping all get interconnected into one common ground. If the LPS has its own isolated ground island, a strike raises that island thousands of volts above the building ground and the difference jumps across as a side flash. See the grounding and bonding guide for how the building grounding electrode system is built and tied together.
Bonding and potential equalization
Bonding is what keeps a strike from tearing through the building looking for a difference in potential. When lightning hits, the LPS conductors and ground rise to a high voltage for a few microseconds. Anything metal that is not bonded to the system stays near earth potential, and that gap between the rising LPS and the grounded metal is exactly the voltage that drives a spark across the space between them. Bond the metal in and you erase the gap. Everything rises together, and there is nothing for the current to jump to.
The list of things that get bonded is long and the standard is explicit about it. The structural steel, the metal roof and parapet, the rooftop equipment, the metal handrails and ladders, the piping, the conduit, the electrical service ground, the telecom and antenna grounds. Anything substantial and metallic that a strike could reach gets tied to the LPS so the whole assembly sits at one potential. This is the single most important idea in lightning protection after the path itself, and it is the part that separates a system that works from a collection of rods.
The common failure is partial bonding. A crew bonds the obvious steel and the service ground, then leaves a metal stair, a gas line, or a new rooftop unit isolated because it went in after the LPS crew left. That isolated metal is now the side-flash target. Bonding is not a one-time task at install. It is something every later trade can break by adding ungrounded metal near the system, which is why the inspection looks for it specifically.
What is side flash and how do you prevent it?
Side flash is the spark that jumps from the lightning protection system to a nearby grounded metal body when the two are at different potentials during a strike. The LPS conductor rises to a high voltage, the nearby pipe or steel does not, and if they are close enough the air between them breaks down and the current arcs across. That arc inside a wall or near a gas line is how a strike that the system caught still starts a fire or finds a person.
Two things prevent it: distance or bonding. Keep the metal far enough from the conductor that the voltage cannot jump the gap, or bond the metal to the conductor so there is no gap in potential to jump. NFPA 780 gives a bonding-distance calculation that sets how far is far enough. The required separation grows with the height up the structure and shrinks as you add down conductors, because more parallel paths mean less current and less voltage rise on each conductor. Metal closer than the calculated distance must be bonded.
In practice you bond rather than chase the distance, because keeping every pipe and rail far enough from the conductors inside a real building is usually impossible. Run the bonding-distance number, and where you cannot make the separation, put in a bonding conductor. The hazard is highest where conductors run near plumbing, gas, and structural metal in tight chases, so that is where the bonding distance gets checked first.
Materials: copper, aluminum, class, and corrosion
LPS conductors are copper or aluminum, sized by conductor class. NFPA 780 sets two classes by structure height: a lighter Class I for structures up to about 75 ft, and a heavier Class II for structures over 75 ft, where the strike current and mechanical demands are larger. The conductor, the air terminals, the fittings, and the connectors all have to match the class. Mixing a Class I conductor into a Class II structure is a quiet way to fail an inspection.
Aluminum has rules copper does not. Aluminum conductors cannot contact earth and are kept up off grade, commonly at least 18 in above ground, because aluminum in soil corrodes away. Where an aluminum down conductor has to reach a ground rod, it transitions to copper through a bimetallic connector above grade, never a direct aluminum-to-copper splice exposed to weather. Aluminum is also kept off surfaces that hold moisture or alkaline runoff, like fresh concrete.
Dissimilar metals are the corrosion trap. Copper and aluminum in direct contact in a wet location set up a galvanic cell, and the connection corrodes until it is no longer a connection, which means the path is gone right where you needed it. Copper runoff onto aluminum below it does the same thing. Use listed bimetallic fittings at every copper-to-aluminum transition, keep copper from draining onto aluminum, and match the fitting metal to the conductors it joins. A corroded connection reads fine on the day of install and opens up two winters later.
Surge protection: the part that saves the electronics
The LPS catches the strike and carries it to ground. It does nothing for the surge that gets induced onto the building wiring at the same moment, and that surge is what destroys equipment. A nearby strike, or a direct strike to the LPS, couples a fast, high-energy transient onto the power conductors, the data lines, and the signal cabling. Without surge protection devices on those conductors, the transient walks straight into the panel, the drives, and the servers.
Surge protection is layered. A service-entrance SPD at the main takes the largest hit, panel-level devices catch what gets past it, and point-of-use protection guards the most sensitive loads. Data, signal, and antenna lines need their own surge protection, because a transient on a control or network cable kills electronics just as readily as one on the power side. The LPS and the SPDs share a ground, which is the whole point: the surge has to be shunted to the same low-impedance ground the strike is using.
Treat them as one system at design time. A building with a beautiful LPS and no coordinated surge protection still loses its electronics in the first close strike, and the owner blames the LPS for not doing a job it was never built to do. The surge protection guide covers SPD types, ratings, and the install details. The short version is that the LPS handles the direct strike and the SPDs handle the transient, and you need both.
Listing and certification: UL 96A, LPI, and the Master Label
The components and the installation are both subject to listing. Individual parts, the air terminals, conductors, fittings, and connectors, are evaluated to UL 96, the product standard for lightning protection components. The installation itself is covered by UL 96A, the installation requirements standard, and by NFPA 780. Using listed components installed to the standard is what makes the system certifiable.
Two certification paths dominate. UL Solutions inspects completed systems and issues a UL Master Label Certificate when the whole structure is inspected and complies, or a Letter of Findings when the scope is partial. The Lightning Protection Institute runs the LPI-IP inspection program, which certifies systems to LPI 175, the standard of practice, and uses LPI 177 as the inspection guide. An LPI Master Installation certified system carries a defined expiration, commonly on the order of three years, after which it is reinspected.
On a specified job, read which certificate the project requires before you bid, because it drives the components, the installer qualification, and the inspection. A Master Label or an LPI certificate is third-party proof the system was built right, and it is often what the insurer or the owner is actually buying. Substituting an unlisted component to save money is how a system that looks finished fails certification and has to be reworked.
Do you need a lightning protection system?
Whether a structure needs an LPS is a risk question, and NFPA 780 answers it with the risk assessment in Annex L. The method compares the frequency of lightning strikes the structure is expected to take against the frequency that is tolerable for that structure given what it is and who is in it. There is a simplified at-a-glance version and a detailed calculation, and the detailed one is the one that holds up when the answer is contested.
The expected strike frequency comes from the local lightning flash density, the size and height of the structure, and its surroundings, which set how large an area it collects strikes from. The tolerable frequency comes from the consequences: loss of life, loss of a critical service, loss of irreplaceable or historic contents, and economic loss. Run the numbers, and if the expected frequency exceeds the tolerable frequency, the assessment recommends protection.
Some structures skip the calculation because the answer is obvious or because a code, an insurer, or a spec already requires protection. A facility handling explosives, a structure storing flammable liquids, a hospital, a data center, or a building of historic value usually gets an LPS regardless of where the math lands. The risk assessment is most useful for the in-between buildings, where it turns an argument into a defensible number. Verify the assessment method against the adopted edition, since the annex is refined between cycles.
Special structures: stacks, tanks, and hazardous areas
NFPA 780 carries separate provisions for structures that are not ordinary buildings, because the geometry and the consequences change. A tall stack or chimney is a preferred attachment point and gets terminals around its rim and down conductors run down its height. A metal tank can sometimes serve as its own air terminal and down conductor if the shell is thick enough and the seams are electrically continuous, but the roof seals, the vents, and the gauging hatches all need attention.
Hazardous and explosive locations are their own category and the rules tighten hard. Where a flammable vapor can be present, the concern is not just the strike but any spark, including the side flash and the sparking at a poor bond, so bonding and potential equalization are taken further and isolated systems are sometimes used to keep conductors away from the hazard. Tanks holding flammable liquids have specific requirements for bonding the shell, the floating roof, the vents, and the piping so the whole assembly stays at one potential.
The common thread is that special structures fail in special ways. A vent on a flammable-liquid tank is exactly where you do not want a side-flash spark, so the bonding around it is not optional and not generic. When the structure is a stack, a tank, a silo, or anything storing or handling something that burns, read the specific provisions for that structure type rather than applying the ordinary-building rules and hoping.
What is different about a data center or mission-critical LPS?
A data center or mission-critical facility almost always gets an LPS, and the surge side matters as much as the structural side. The building is full of electronics that a transient destroys, the cost of downtime is enormous, and the rooftop is crowded with metal: chillers, condensers, dunnage steel, antennas, and conduit, every piece of which has to be bonded and either carries a terminal or sits inside the protected zone.
The grounding and bonding get more deliberate here. The LPS ground ties into the facility grounding system, the equipment grounding, and the telecom and signal reference grounds, so the entire site rises and falls together during a strike and the sensitive electronics never see a damaging potential difference across their references. A difference of a few hundred volts between two grounds in a server room is enough to take out a network of equipment, so the common-ground requirement is not a formality in this building.
Surge protection is layered aggressively in a mission-critical install, from the service entrance through the distribution panels to the rack and the data lines. The LPS handles the direct strike. The coordinated SPDs handle the transients on every conductor entering the white space. Treat the LPS, the grounding, and the surge protection as one coordinated design from the start, because the cost of getting it wrong in this building is measured in lost service, not just hardware.
Rooftop units and metal: bonding what is already up there
Every piece of metal on the roof is either part of the lightning protection system or a liability. A rooftop HVAC unit, a condenser, an exhaust fan, a satellite dish, a metal vent, a guardrail: each is a preferred attachment point, and each is grounded metal that a nearby conductor can side-flash to. The rule is the same as everywhere else. Bond it, and put it inside the protected zone.
Bonding means tying the equipment to the LPS conductor network so it rises with the system. A tall rooftop unit also usually needs its own air terminal, or it has to fall under the zone of a nearby taller terminal by the rolling sphere, because the unit itself sticks up where the sphere can touch it. A short curb-mounted unit might fall inside the zone already, but you check that with the sphere, you do not assume it.
The recurring problem is sequence. The LPS goes in, gets certified, and then the mechanical crew sets a new rooftop unit six months later and nobody bonds it or adds a terminal. Now there is unbonded metal sticking up through the protected zone, and the certificate no longer describes the building. Any time rooftop equipment is added or replaced, the LPS has to be revisited. See the rooftop equipment guidance for how units are set and the coordination that goes with them.
Coordinating with the roofer: penetrations versus adhesive bases
The LPS lives on the roof, and the roof is a waterproofing system that nobody wants punctured. The conflict is real and it is why the LPS install and the roofing install have to be coordinated, not run independently. Air terminal bases and conductor fasteners either penetrate the membrane or attach without penetrating, and which one you use is a roofing decision as much as an electrical one.
On most modern low-slope roofs, the LPS uses adhesive or membrane-bonded bases that attach to the roof surface without a penetration, so the waterproofing stays intact. On other assemblies, the bases penetrate and the penetration gets flashed by the roofer to keep it watertight. The wrong move is an electrician driving fasteners through a single-ply membrane with no flashing and no coordination, which buys the building a slow leak that surfaces long after both crews are gone.
Sequence and responsibility have to be settled before the LPS crew steps on the roof. Who supplies the bases, who sets them, who flashes any penetration, and whose warranty covers the result. The membrane manufacturer often dictates which attachment is allowed under the roof warranty, so the LPS attachment method is checked against the roofing warranty, not chosen by habit. A penetration that voids a roof warranty is a far more expensive mistake than the LPS itself.
Inspection and maintenance
An LPS is mostly outdoors, mostly metal, and mostly forgotten until it is needed, which is why periodic inspection is part of the standard and not an afterthought. NFPA 780 and the LPI inspection guidance call for inspection at intervals and after any event or modification that could affect the system. The inspection looks at the connections, the corrosion, the mechanical security of the conductors and terminals, and whether anything new on the roof has been left unbonded.
Connections are the first thing checked, because that is where the system fails. A loosened clamp, a corroded bimetallic fitting, a conductor that worked free of its fastener, any of these opens the path or adds impedance right where the current has to flow. Corrosion at copper-to-aluminum transitions and at the grounding connections gets specific attention, since those are the spots that look fine for a year and then open up. The ground resistance can be measured to confirm the electrodes still spill current the way they did at install.
Maintenance is also triggered by every other trade. New rooftop equipment, a re-roof, a facade change, a renovation that adds metal: each can break the system, and each should bring the LPS back for inspection. For the grounding side, the ground resistance testing follows the same approach used for the building grounding electrode system, and the grounding guide covers that test. The point is that a certified system stays certified only if it is maintained, and the building changes around it constantly.
What to document
An LPS is hard to inspect after the fact because so much of it is concealed, bonded, or buried, so the record made at install is what a later inspector, a certifier, or the next contractor has to work from. Capture the components and their listing, the geometry, the bonding, and the grounding, and tie each to a location. A drawing that shows where every terminal, conductor, bond, and electrode landed is worth more than any narrative.
Record the component class and listing, the air terminal locations and heights, the down conductor count and routing, the grounding electrode type and the ground ring, every bond and what it connects, the certification path and any certificate issued, and the surge protection installed. When a rooftop unit is added later, the record is what tells the next crew whether it falls in the protected zone or needs a terminal.
| Component | Location | Size / class | Bonding | Ground |
|---|---|---|---|---|
| Air terminals | Ridges, edges, corners, projections | Height and class per NFPA 780 | Tied to conductor network | Via down conductors |
| Down conductors | Exterior routes, two or more | Class I or II by structure height | Bonded at roof and base | To electrode at each base |
| Grounding electrodes | Base of each down conductor | Rod size and length | Tied to ground ring | Driven into soil |
| Ground ring | Buried around structure | Conductor at 18 in min depth | Bonds all electrodes | Common ground |
| Bonds | Steel, piping, RTUs, utilities | Bonding conductor size | Records what connects to what | To common ground |
| Surge protection | Service, panels, data lines | Type and rating | Shares LPS ground | Common ground |
Common mistakes
- Skipping the bonding, so a strike side-flashes from the LPS to unbonded steel, piping, or rooftop metal.
- Running a single down conductor, leaving the strike one path to ground when the standard requires at least two.
- Placing air terminals by eye instead of the rolling sphere, so projections and roof edges sit outside the protected zone.
- Leaving the LPS ground isolated from the building grounding electrode system, which guarantees a potential difference and a side flash.
- Installing the LPS with no coordinated surge protection, so the electronics still get destroyed by the transient.
- Tight bends or a conductor routed up and back down, forcing current to flash off the conductor at the bend.
- Direct copper-to-aluminum connections in wet locations, which corrode open and break the path two winters later.
- Setting new rooftop equipment after certification and never bonding it or adding a terminal.
Field checklist
Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.
Standards and references
NFPA 780, the Standard for the Installation of Lightning Protection Systems, is the controlling design document in the United States. It sets the air terminal placement, height, and spacing, the minimum of two down conductors and their perimeter spacing and bend rules, the grounding electrodes and ground ring, the bonding and side-flash provisions, the surge protection requirements, and the risk assessment in Annex L. Section and annex numbering is refined between editions, so confirm any reference against the adopted edition before citing it on a submittal.
UL 96 is the product standard for lightning protection components, and UL 96A covers the installation requirements, the basis for the UL Master Label inspection program. The Lightning Protection Institute publishes LPI 175 as the standard of practice and LPI 177 as the inspection guide, used by the LPI-IP third-party inspection and certification program. The international counterpart is the IEC 62305 series, used outside the United States and on some international and corporate specifications.
The building code, the insurer, and the project specification can all impose requirements on top of NFPA 780, and any of them can require an LPS regardless of where the risk assessment lands. Where a spec calls for a UL Master Label or an LPI certificate, that requirement drives the components and the inspection. Verify the adopted edition, the local amendments, and the project documents, and cite the standard that actually controls the point.
Units, terms, and conversions
Lightning protection mixes its own vocabulary with the grounding terms it shares with the rest of the electrical trade, and the same idea can read differently across the standard, a manufacturer sheet, and a drawing set.
Air terminals are also called lightning rods, strike termination devices, or points. The conductor network on the roof is the roof conductor or the main conductor; the vertical runs are down conductors or down leads. The buried perimeter conductor is the ground ring or counterpoise. Conductor class is Class I for ordinary structures up to about 75 ft and Class II for structures over that height. Distances run in both feet and meters, so the 150 ft rolling sphere is about 45 m, the 100 ft perimeter spacing is about 30 m, the 8 in bend radius is about 203 mm, and the 18 in ground ring depth is about 460 mm.
- Air terminal
- The rod or point that intercepts the strike, also called a lightning rod or strike termination device
- Down conductor
- A conductor carrying strike current from the roof network to the grounding electrodes, minimum two per structure
- Rolling sphere
- A design sphere, commonly 150 ft radius, rolled over the structure to find exposed points needing terminals
- Zone of protection
- The volume under the chord of the rolling sphere where the structure is shielded by the terminals
- Ground ring / counterpoise
- A buried conductor encircling the structure, at least 18 in deep, tying all electrodes to a common ground
- Side flash
- A spark jumping from the LPS to nearby grounded metal at a different potential during a strike
- Bonding distance
- The calculated separation within which metal must be bonded to the LPS to prevent side flash
- SPD
- Surge protection device, which clamps the transient on building wiring that the LPS itself does not address
FAQ
Does a lightning protection system stop lightning?
No. A lightning protection system does not prevent or attract strikes. It gives a strike that does hit a controlled, low-impedance path down and around the structure into the ground, so the energy bypasses the building. The old claim that rods bleed off the charge and stop strikes was never true.
How many down conductors do you need?
At least two. NFPA 780 requires a minimum of two down conductors on any structure so the strike always has more than one path to ground. Larger buildings need more, spaced at intervals averaging not more than 100 ft around the protected perimeter, so divide the perimeter by 100 ft to start the count.
What is the rolling sphere method?
The rolling sphere method places air terminals so a sphere of fixed radius, commonly 150 ft, can roll over the structure without touching it. Anywhere the sphere can touch the building is exposed and needs a terminal. Anywhere it rides over without contact is inside the protected zone. The sphere radius depends on structure class and protection level.
Does a lightning protection system replace surge protection?
No. The LPS handles the direct strike and carries it to ground, but it does nothing for the transient induced onto the building wiring, which is what destroys electronics. Surge protection devices on the power, data, and signal lines clamp that transient. NFPA 780 treats both as parts of one complete system.
How tall and how far apart do air terminals go?
Air terminals are commonly set at least 10 in above the protected object, spaced not more than about 20 ft along ridges and the roof perimeter for terminals up to 24 in tall, and within 2 ft of edges and outside corners. On a flat roof, no point should be more than about 50 ft from a terminal.
Do you need a lightning protection system for your building?
Run the NFPA 780 Annex L risk assessment. It compares the expected strike frequency, set by flash density and structure size, against the tolerable frequency, set by the consequences. If the expected frequency exceeds the tolerable one, protection is recommended. Hospitals, data centers, and explosive or flammable storage usually get an LPS regardless.
What is a UL Master Label for lightning protection?
A UL Master Label Certificate is third-party proof that a completed lightning protection system was inspected against UL 96A and built with listed components. UL issues it when the whole structure complies, or a Letter of Findings for partial scope. The LPI-IP program offers a comparable certification to LPI 175 and NFPA 780.
What is side flash and how do you stop it?
Side flash is a spark that jumps from the LPS to nearby grounded metal at a different potential during a strike, and it can start a fire inside a wall. Prevent it with distance or bonding. NFPA 780 gives a bonding-distance calculation; any metal closer than that separation must be bonded to the system.
Does an LPS protect rooftop HVAC units and antennas?
Only if they are bonded and inside the protected zone. Every rooftop unit, condenser, dish, and vent is both a strike attachment point and grounded metal that can side-flash. Each must be bonded to the conductor network and either carry its own air terminal or fall under a nearby terminal by the rolling sphere.
People also ask
Codes cited in this guide
This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.