ANVILFIELD Try FieldOS

Electrical

Wireways and auxiliary gutters field guide for electrical crews

Tell the wireway from the gutter, hold the 20 percent fill, keep splices under 75 percent, support it, bond it, leave the cover accessible, and size it for the bend.

WirewayAuxiliary GutterNEC 376NEC 366Electrical

Direct answer

A wireway is a sheet metal or nonmetallic trough with a removable or hinged cover that holds and routes many conductors with easy access. An auxiliary gutter is the same trough used to supplement equipment locally. NEC Articles 376 and 378 cover wireways, Article 366 covers gutters, and the 20 percent fill rule governs both.

Key takeaways

  • Conductors fill no more than 20 percent of a wireway or auxiliary gutter interior cross-sectional area (sum conductor areas over insulation, divide by 0.20).
  • Splices and taps are allowed but at any single point conductors, splices, and taps together stay under 75 percent of the cross-sectional area and remain accessible.
  • NEC Article 376 covers metal wireways, Article 378 nonmetallic wireways, and Article 366 auxiliary gutters; a sheet metal gutter is commonly limited to about 30 ft beyond the gear.
  • In a metal wireway, bundling ampacity derating applies only above 30 current-carrying conductors; nonmetallic wireway derates like conduit starting at a small handful.
  • Support the wireway on its own, not off feeding conduits: horizontal runs about every 5 ft plus each end, sized for loaded weight; bond metal continuous across every joint.

Wireways and auxiliary gutters, and where they fit

A wireway is a metal or nonmetallic trough with a removable or hinged cover, built to hold and route conductors where you need to get back into them. Take the cover off and every conductor inside is in your hand. That access is the whole reason the thing exists, and it is what separates it from conduit, where the conductors are sealed inside a pipe until you pull them out at a box.

You reach for a wireway or a gutter in three situations. The first is gathering: a wall of homeruns landing on a panel or a switchboard, where running each one in its own conduit would fill the wall with nipples and locknuts. The second is splicing or tapping, because the open trough gives you room to make connections and leave them accessible, which a conduit body never does well. The third is distributing, feeding several panels or machines off one common channel.

The terms get used loosely on the job, and that is fine until an inspector asks which article you installed to. A wireway is the raceway under NEC Articles 376 and 378. An auxiliary gutter is the local supplement under Article 366. They look identical, they are listed to the same standard, and the difference is mostly in how far they run and how they are marked. For the open support route where many cables share a path without a cover, that is cable tray, a different system covered in its own guide. For the enclosed pull, that is conduit, also its own guide.

What is the difference between a wireway and an auxiliary gutter?

A wireway is a raceway you can run across a building. An auxiliary gutter supplements equipment locally and, where it is the sheet metal type, is commonly limited to about 30 ft beyond the equipment it serves. That distance is the line. Once the trough needs to run farther than that, you are no longer building a gutter, and the install falls under the wireway articles instead.

Both are listed to the same product standard and the hardware on the shelf is often the same trough. The split is in how the code treats the run. The auxiliary gutter under Article 366 is meant to sit at or near the gear, carrying conductors the short distance from one piece of equipment to another and giving you a place to splice and tap. The wireway under 376 or 378 is the longer channel that moves conductors from point to point as a raceway in its own right.

On the floor, most people call any covered trough a wireway and most call the one bolted to the side of the switchboard a gutter, and the names track the use closely enough. Where it matters is the submittal and the inspection. Confirm the distance limit and any exceptions against the adopted code edition, because the figure and its exceptions have moved between cycles.

Wireway vs conduit vs cable tray

Three systems carry conductors along a route, and they are not interchangeable. The wireway is the accessible covered trough: easy to open, made for many conductors, splices, and taps. Conduit is the enclosed pull: a pipe that protects the conductors and seals them away, where you do not splice except inside a box or fitting. Cable tray is the open support: a ladder or trough that holds cables in the air, sized for far more cables than a wireway and dressed in the open rather than enclosed.

Pick by what the route has to do. If you need to get back into the conductors often, to add circuits, to splice, to land a wall of homeruns, the wireway wins because the cover comes off and the work is right there. If the conductors need physical protection and you will not touch them again, conduit wins. If you are running a heavy population of cables across a plant or a data hall and want them supported and serviceable in the open, cable tray wins.

The systems also mix. A cable tray run drops into conduit where it passes through a wall, and a wireway sits at the end of a conduit bank to gather the homeruns onto the gear. The cable tray and conduit choices have their own guides; this one stays on the covered trough.

What a wireway or gutter is actually for

The most common use is gathering many circuits at a panel or a piece of gear. A row of panelboards in an electrical room, each with a dozen homeruns, turns the wall above into a forest of conduit if every circuit gets its own pipe. Run a wireway along the top of the lineup instead, drop conduits into it, and the conductors travel the last stretch in the open trough to each panel. One trough does the work of a wall of nipples.

The second use is the splice and tap point. The open trough is the one place in a conduit system where you have room to make a tap, lay it out, and leave it where the next person can find it. A feeder tap to several panels, a set of splices extending a run, a distribution point off one large conductor to several smaller ones: the gutter is where that happens because the access is built in.

The third use is distribution, feeding several devices or machines off a common channel. On a machine line, a gutter along the equipment lets each machine tap what it needs without a separate raceway back to the panel for every one. The flexible part is that adds and changes happen with a screwdriver and a cover, not a new conduit run.

Types and materials

Wireways and gutters come in metal and nonmetallic. Metal is the common choice: steel for most indoor work, aluminum where weight or corrosion matters. Nonmetallic, usually PVC, goes in corrosive or wet areas where steel would not last, and it carries its own derating behavior that catches people, covered below.

The next split is the environment rating. The standard indoor trough is a NEMA Type 1, vented or solid, fine in a dry electrical room. Outdoors or anywhere water reaches it, you need a raintight type, commonly NEMA 3R, built so rain and sleet do not get inside and with a way for any condensation to drain. Putting a Type 1 wireway outside is one of the more common rating mistakes, and it shows up as rust and wet conductors within a season.

Covers come two ways. A removable cover lifts off entirely, screw by screw, which is cheap and fine for a run nobody opens often. A hinged cover swings open and stays attached, which you want anywhere the trough gets opened regularly, because a loose cover gets left off or dropped. Feed-through and pull sections, end plates, and reducing fittings round out the catalog. Match the type and the rating to the location, then confirm the listing covers the use.

What is the fill limit for a wireway?

The conductors in a wireway or an auxiliary gutter fill no more than 20 percent of the interior cross-sectional area. Add up the cross-sectional area of every conductor, including insulation, and that sum stays at or under one fifth of the trough's inside area. This is the rule that sizes the trough, and it is the one people violate first by stuffing a small wireway because it was what was on the truck.

The 20 percent figure is about heat and about room to work. Pack the trough full and the conductors cannot shed heat, so they run hotter than the ampacity table assumed. You also lose the room to lay conductors in and pull them back out, which defeats the access the wireway was installed to give you. The trough that is jammed to the lid is the one nobody can add a circuit to later without starting over.

Run the number off the conductor sizes you are actually installing, not a guess. The interior area is on the manufacturer's data sheet for the trough. Confirm the exact percentage and how it is measured against the adopted NEC, because the fill basis is the kind of detail that gets amended, but 20 percent has been the working figure for conductor fill in these articles for a long time.

Can you splice conductors in a wireway?

Yes. Splices and taps are allowed in a wireway and an auxiliary gutter, which is one of the main reasons to use one, but at any single point the conductors, splices, and taps together fill no more than 75 percent of the cross-sectional area. The 20 percent conductor fill is the through limit along the run; the 75 percent is the local limit where the splice bulks up the bundle.

The splice also has to stay accessible. A wireway splice buried behind drywall or above a hard ceiling with no access defeats the rule and fails inspection, because the entire point of splicing in the trough rather than in a sealed box is that you can open the cover and get to the connection. Make the splice, leave it where the cover reaches it, and do not bury the section.

This is the answer to why a gutter shows up at the gear in the first place. Tapping a large feeder to several smaller ones needs a place with room to land the connectors and leave them serviceable. The trough gives you that room up to the 75 percent point, where the conduit body and the standard junction box run out of space. Confirm the 75 percent figure against the adopted code, and keep the splice count honest at the busiest cross section, not the average one.

Ampacity and derating over 30 conductors

The conductor adjustment for fill behaves differently in a metal wireway than almost anywhere else, and it is worth knowing cold. In a metal wireway, the ampacity adjustment factors for bundled current-carrying conductors do not kick in until you have more than 30 current-carrying conductors at a cross section. Below that count, you do not apply the bundling derate in the metal trough, which is part of why the wireway is a comfortable place to gather a lot of circuits.

Nonmetallic wireway does not get that break. There the adjustment factors apply the same way they do in conduit, starting once you have more than a small handful of current-carrying conductors. So a PVC wireway in a corrosive area is sized and derated differently from the steel one in the dry room next door, and treating them the same is a quiet error that leaves the nonmetallic run undersized.

Count current-carrying conductors, not total conductors. A neutral that carries only the unbalanced current and an equipment grounding conductor are handled by their own rules in the count. When the population gets high, run the derate, because the same wire that was fine at 28 conductors is not at 32. Confirm the conductor-count threshold and the adjustment factors against the adopted NEC, since the count and the factors live in the ampacity rules that change between editions.

Supporting a wireway

A wireway is supported on its own, not hung off the conduits that feed it. Run horizontally, the common requirement is support at each end and at intervals on the order of 5 ft, with a hard ceiling on the gap between supports, unless the trough is listed for wider spacing. Run vertically, the intervals are different and there is usually a limit on joints between supports. The conduits dropping in are not the support; they are the load.

The failure here is predictable. A long trough hung on a couple of strut points sags between them, the cover stops sitting flush, water finds the gaps outdoors, and the conductors inside take the weight at the entry points. A sagging wireway is the one that looks fine the day it goes up and looks wrong a year later when the middle has drooped.

Support it like the heavy filled channel it is. Strut and threaded rod sized for the loaded weight, not the empty trough, because a full wireway of large conductors is not light. Confirm the exact horizontal and vertical spacing and the listing exceptions against the adopted code, because the support intervals are the kind of number that varies by article and by whether the product is listed for more.

Sizing the wireway or gutter

Sizing starts at the 20 percent conductor fill and then grows for everything the fill rule does not capture. Total the conductor areas, divide by 0.20, and that interior area is the floor, not the answer. A trough sized to exactly 20 percent with no thought to what happens at the splices and the terminations is a trough you will fight.

Add room for the splices and taps, because at those points the 75 percent local limit governs and a trough that was comfortable on through-fill can choke where the connectors land. Then add bending space, the dimension covered next, because a gutter that doubles as a junction needs the depth to turn conductors into the gear without cramping the bend. The gutter feeding a switchboard is sized as much by the bend as by the fill.

The practical move is to size up one trade size from the bare fill calculation on any run that splices, taps, or turns conductors into equipment. The cost difference between a 6 by 6 and an 8 by 8 trough is small. The cost of pulling a too-small gutter back off the wall after the inspector reads the bending space is not. Size for the work the trough actually does, not the conductor area alone.

Bending space where the gutter is a junction

When a wireway or a gutter acts as a junction, where conductors deflect at the ends, where conduits enter and leave, or where the run turns more than about 30 degrees, the conductors need bending space the same as they do at a terminal. The code points you to the wire-bending space tables, the same ones used for cabinets and gutters at terminals, commonly cited at NEC 312.6. The trough has to be deep enough to bring the conductor in and turn it without bending it tighter than its insulation allows.

This is the dimension the fill calculation misses entirely. A trough can pass the 20 percent fill and still be too shallow to make the turn, because fill is about area and bending space is about the depth across from where the conductor enters to the opposite wall. Large conductors are the problem. A 500 kcmil conductor turning into a switchboard needs real depth, and a gutter sized only on fill will not give it.

Pull the bending space from the table for the largest conductor and the number entering per terminal, then make sure the trough's clear inside dimension meets it. Confirm the table and the dimensions against the adopted code edition. The inspector reading a gutter at the gear checks this before the fill, because a cramped bend damages insulation where you cannot see it.

Conductors entering, leaving, and marked

Conductors come into the trough through conduits, fittings, and connectors, run the length of it, and leave the same way. Inside, they can be spliced and tapped as long as the access and the 75 percent rule hold. Where a single trough carries the conductors of several circuits, identifying them matters, because the next person opening the cover is looking at a bundle and needs to know which conductors belong together.

Mark the circuits at the trough. A piece of tape and a number at each entry and exit, or at the splice, turns an anonymous bundle into something serviceable. The gutter that gathers twelve homeruns onto a panel is far easier to work years later when each set is tagged at the trough, not just at the breaker.

Bare or covered conductors of different systems sharing a trough have their own separation and barrier rules, and so do conductors of different voltage classes. Where power and signal, or different voltage systems, share one gutter, check whether a barrier is required and keep them on their own sides. The open trough makes mixing easy, which is exactly why the separation rules exist.

Grounding and bonding the metal

A metal wireway or gutter is part of the electrical system and has to be bonded so its metal is at ground potential and can carry fault current. The sections bolt together, but the joint between sections is not automatically a reliable electrical connection, especially with paint, gaskets, or a raintight finish in the way. Bonding jumpers or listed connections make the metal electrically continuous from end to end and back to the equipment grounding system.

Whether the trough itself qualifies as an equipment grounding conductor depends on the listing and the install, and the safe default is to treat the metal as something to bond rather than something to rely on as the ground path. Run an equipment grounding conductor where the circuits need one, bond it to the trough, and make the metal continuous across the joints. Do not assume the painted bolted seam carries fault current.

The failure mode is a section that went up with the bonding skipped at one joint, so a length of trough sits isolated. It looks grounded, it is bolted to grounded sections, and it is not, because paint and a gasket broke the path. A fault to that isolated section energizes metal that the breaker cannot clear through it. Bond every joint, verify continuity, and treat the connection between sections as the thing that fails quietly.

Covers and keeping it accessible

The removable or hinged cover is the feature that defines the system, and the install has to protect it. The whole value of a wireway over conduit is that you open it and the conductors are right there, so anything that buries the trough or blocks the cover throws away the reason you used it.

Keep the trough accessible. It cannot be concealed behind finished construction or run where the cover cannot be opened, beyond what the listing allows. A gutter above a hard ceiling with no access panel, a wireway drywalled into a chase, a trough buried behind ductwork: each one fails the access requirement and each one defeats the splices and taps inside it that depend on being reachable.

Hinged covers earn their cost anywhere the trough gets opened more than once. A removable cover that comes off in twenty screws gets left off, or the screws walk away, or it gets set down somewhere and lost. The hinge keeps the cover with the trough and makes opening it a one-hand job, which is the difference between a gutter that gets serviced properly and one that gets left open.

Fittings and connections

A wireway is a system, not a single trough, and the fittings make the route. Elbows turn it, tees and crosses branch it, nipples and connectors join one section to the next and tie it into the gear and the conduits. Use the listed fittings made for the trough you are installing, because the bonding, the fit, and the rating all depend on the pieces being part of the same listed system.

Connections to equipment are where the trough meets the panelboard, the switchboard, or the conduit bank. The connector and the opening have to match, the bonding has to carry across the connection, and any raintight rating has to hold at the joint outdoors. A mismatched or field-modified connection is where the rating and the ground path both break.

Reducing fittings let a larger trough step down to a smaller one where the conductor count drops, which keeps you from running an oversized gutter the whole length. End plates close the ends. The catalog is deep; the discipline is staying inside one listed system rather than mixing pieces from different products and hoping the seam works.

Feeding panelboards and switchgear

The gear room is where the gutter does its best work. A switchboard or a lineup of panelboards needs conductors brought in, turned, and landed, often a lot of them, and the auxiliary gutter bolted to the gear is where that gathering and turning happens with the room to do it right. Feeders come up out of the floor or in from the wall, run the gutter, and tap off to each section.

The feeder tap from a gutter is a standard distribution move. One large set of conductors enters, and taps come off to feed several panels or sections, made in the trough where the 75 percent rule and the access requirement both apply. This is cleaner and far more serviceable than trying to land everything inside the gear's own wireway space, which is usually tight.

Size the gutter at the gear for the bend, not just the fill, because every conductor in it is turning into a terminal. The bending space governs here more than anywhere. A gutter that gathers a switchboard's feeders and cannot make the turn into the lugs is the one that gets rebuilt during commissioning. Get the depth right before the conductors are pulled.

Outdoor and wet locations

Outside, or anywhere water reaches the trough, the wireway has to be raintight, commonly a NEMA 3R, built so rain and sleet do not get in and with a way for condensation to leave. A standard indoor Type 1 trough outdoors fills with water at the first storm, rusts from the inside, and wets the conductors, and you find it when a circuit faults to the wet metal.

Raintight is more than the trough rating. The fittings, the connectors, and the joints all have to hold the rating, and a raintight wireway with a non-raintight connector or an open knockout is not raintight anymore. The water finds the one gap. Check every penetration and every joint, and use the gaskets and the listed raintight fittings made for the system.

Drainage matters even on a sealed outdoor trough, because condensation forms inside from the temperature swing regardless of how tight the seams are. Listed raintight wireway gives the water a path out at the low points. Mount the trough so those drains are actually at the bottom, not designed-in at a corner you installed high. The listing assumes the trough is oriented the way it was tested.

Long runs, expansion, and seismic bracing

A long metal wireway moves with temperature, and a long building moves in a seismic event, and both put load on a trough that was bolted up rigid. On long metal runs across temperature swings, expansion fittings let the trough grow and shrink without buckling the sections or shearing the supports. The outdoor run in the sun is the one that needs it most, because the swing is largest.

In seismic areas, the trough and its supports are part of the bracing the structural and electrical drawings call out, and the wireway full of conductors is a real mass swinging on rod. The bracing requirements come from the building code and the project's seismic design category, covered in its own material; here it is enough to say the supports are sized and braced for the loaded trough in motion, not the empty one sitting still.

Coordinate the expansion and seismic details with the structural drawings rather than improvising them in the field. The expansion fitting that bonds across the gap, the brace that ties the trough to structure, and the support that carries the loaded weight are an engineered set. Confirm the requirements against the adopted building code and the project's seismic category.

The code limits that govern

Three NEC articles cover these troughs, and knowing which one applies tells you which rules to read. Article 376 covers metal wireways. Article 378 covers nonmetallic wireways. Article 366 covers auxiliary gutters. They overlap heavily, because the products are nearly the same, but the fill, the splice allowance, the support intervals, and the distance limits are stated in each, and the nonmetallic and metal versions differ on derating.

The figures that drive the install are consistent enough to carry in your head: 20 percent conductor fill, 75 percent at splices and taps, support on the order of 5 ft horizontally, the metal-wireway break on derating below the conductor-count threshold, and the roughly 30 ft distance limit that turns a gutter into a wireway. Each of those is the working number, and each is the kind of figure that gets amended.

So cite the article that governs the point and hedge the specific number to the adopted edition. Write the requirement by article and topic on a submittal, then confirm the exact percentage, the exact distance, the exact support interval, and the exact conductor count against the code edition the jurisdiction has actually adopted and any local amendments. A wrong number on a submittal is the fastest way to lose the inspector.

What does the inspector check?

An inspector reads a wireway or gutter in a predictable order, and knowing it lets you check your own work the same way. Fill comes first on the through run: is the conductor area at or under 20 percent. Then the splices: are they under 75 percent at the busiest cross section, and are they accessible with the cover off. Then support: is the trough carried on its own at the right intervals, not hanging off the conduits.

Next is bonding: is the metal continuous across every joint and tied to the grounding system, with no isolated section behind a painted seam. Then access: can the cover be opened, is the trough reachable, is nothing buried or concealed beyond the listing. Then the rating: is an outdoor trough actually raintight at the trough and the fittings. At a gutter feeding gear, the bending space gets read hard, because a cramped bend damages insulation out of sight.

The fastest way through an inspection is to have the fill calculation, the conductor schedule, and the bending-space numbers ready before the inspector asks. The trough that passes is the one where the work matches a record you can show, not the one where the answers get worked out at the cover with the inspector waiting.

Wireway and gutter in gear rooms and data centers

In a data center or a heavy gear room, the wireway shows up at the distribution gear and the gutter shows up at the switchboards and the panel lineups, doing the same gathering and tapping job at a larger scale. The conductor counts are high, the feeders are large, and the changes are constant, which is exactly the case the covered trough was made for.

The high conductor count is where the derating rules bite. A metal wireway packed toward the 30-conductor threshold is fine until the count crosses it, and a busy data hall gutter is the place that happens. Count the current-carrying conductors honestly at the worst cross section and apply the derate when the count crosses the line, because the wire that was sized for 28 is not sized for 34.

The constant change is the other reason the system fits. A data hall adds and re-feeds circuits for the life of the room, and the covered trough makes that a cover-and-screwdriver job instead of a new conduit run every time. That only works if the original install left the fill honest and the access clear. The gutter packed to the lid on day one is the one nobody can add to when the room grows.

What to document

A wireway that nobody can show the fill on is a wireway the inspector takes apart. The record is what answers the fill question, the splice question, and the bending question without pulling the cover and counting. It is also what the next crew reads when the room grows and they need to know what is left.

Capture the trough size and interior area, the conductor schedule with sizes and counts, the calculated fill percentage, the splice and tap locations with their local fill, the bending space at any junction, the support type and spacing, the bonding method across joints, the environment rating against the location, and the article you installed to. If the run is nonmetallic, note the derating you applied, because it differs from the metal case and the reviewer will check it.

ItemRuleNote
Conductor fill20 percent of interior areaSum conductor areas, divide by 0.20
Splice and tap fill75 percent at any pointMeasured at the busiest cross section, accessible
Support spacingAbout 5 ft horizontal, per listingTrough on its own, not on the conduits
Bending spacePer wire-bending table (312.6)Governs the gutter that turns conductors into gear
DeratingMetal: over 30 CCC; nonmetallic: as in conduitCount current-carrying conductors at worst section
BondingContinuous metal, tied to groundVerify across every joint, not just at the ends
Environment ratingType 1 indoors, 3R raintight outdoorsFittings and joints must hold the rating
Article installed to376 metal, 378 nonmetallic, 366 gutterConfirm distance limit against adopted edition

Common mistakes

  • Filling the trough past 20 percent conductor area, so it runs hot and leaves no room to pull or add.
  • Letting splices and taps exceed 75 percent at a point, or burying the splice where the cover cannot reach it.
  • Hanging the wireway off the conduits that feed it instead of supporting it on its own at the right intervals.
  • Skipping a bonding jumper at a joint, leaving an isolated section that looks grounded through a painted seam and is not.
  • Concealing the trough behind finished construction so the cover cannot be opened and the access requirement fails.
  • Putting an indoor Type 1 wireway outdoors instead of a raintight 3R, so it fills with water and rusts from inside.
  • Sizing the gutter on fill alone with no bending space, so the conductors cannot turn into the gear without cramping the insulation.
  • Treating a metal wireway and a nonmetallic one the same on derating, leaving the PVC run undersized.

Field checklist

0 of 10 complete

Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.

Standards and references

The NEC, NFPA 70, is the framework. Metal wireways fall under Article 376, nonmetallic wireways under Article 378, and auxiliary gutters under Article 366. The conductor fill, the splice and tap allowance, the support intervals, and the gutter distance limit are stated in those articles, and the derating behavior differs between the metal and nonmetallic versions, so read the article that matches the product you installed.

The bending space where a trough acts as a junction comes from the wire-bending space rules, commonly cited at NEC 312.6 and the associated table, the same provisions used for cabinets and cutout boxes. The ampacity adjustment for bundled conductors comes from the ampacity rules in Article 310. The products themselves are listed to UL Standard 870, which covers wireways, auxiliary gutters, and associated fittings as a family, which is why they look and perform so much alike.

Cite the article that controls the point and hedge the figures to the adopted edition. The 20 percent fill, the 75 percent splice limit, the roughly 5 ft support interval, the over-30-conductor derating threshold for metal wireway, and the roughly 30 ft gutter distance are the working numbers, but the exact values, the exceptions, and the section numbers move between code cycles. Confirm them against the edition the jurisdiction has adopted and any local amendments, and follow the manufacturer's listed instructions for the specific product. The two figures to hold onto are the 20 percent fill and the access requirement, because those two are what the install lives or dies on.

Units, terms, and conversions

These troughs go by several names across a drawing set, a catalog, and a spec, and the same trough can read differently depending on who drew it.

A wireway is also called a wiring trough or, loosely, a gutter, and the auxiliary gutter is the code term for the local supplement at the gear. Cross-sectional area, the basis for the fill rule, is the inside area of the trough in square inches, on the manufacturer's data sheet. Conductor area for the fill total is the area over the insulation, not the bare copper. Trough sizes are given as the inside dimensions, commonly in inches, such as 4 by 4, 6 by 6, or 8 by 8. NEMA type is the environment rating, Type 1 for general indoor use and Type 3R for raintight outdoor use.

Wireway
A covered metal or nonmetallic trough used as a raceway for many conductors, NEC Article 376 or 378
Auxiliary gutter
A covered trough supplementing equipment locally, NEC Article 366, commonly limited to about 30 ft beyond the gear
Cross-sectional area
The interior area of the trough, the basis for the 20 percent conductor fill rule
Conductor fill
The summed area of all conductors as a fraction of the trough's interior area, held to 20 percent
Splice fill
Conductors plus splices and taps at one point, held to 75 percent of the area, kept accessible
Bending space
The clear depth a conductor needs to turn into a terminal without over-bending, from the wire-bending table
NEMA 3R
A raintight enclosure rating for outdoor use, keeping rain and sleet out with a path to drain condensation
Current-carrying conductor
A conductor counted for derating, the count that triggers ampacity adjustment when it crosses the threshold

Related tools

Calculators and readiness checks for this work

Compare your options

FAQ

What is a wireway?

A wireway is a metal or nonmetallic trough with a removable or hinged cover that holds and routes many conductors with easy access. It is used to gather circuits at gear, to splice and tap, and as a wiring channel. NEC Articles 376 and 378 govern metal and nonmetallic wireways.

What is the difference between a wireway and an auxiliary gutter?

A wireway is a raceway that runs across a building under NEC Articles 376 and 378. An auxiliary gutter under Article 366 supplements equipment locally and, where it is sheet metal, is commonly limited to about 30 ft beyond the gear. Past that distance the install becomes a wireway. Confirm the limit against the adopted edition.

What is the fill limit for a wireway?

Conductors fill no more than 20 percent of a wireway's interior cross-sectional area. Sum the area of every conductor over its insulation and keep it at or under one fifth of the trough's inside area. The same 20 percent applies to auxiliary gutters. Confirm the figure against the adopted NEC edition.

Can you splice conductors in a wireway?

Yes. Splices and taps are allowed in a wireway and an auxiliary gutter, but at any single point the conductors, splices, and taps together stay under 75 percent of the cross-sectional area, and the splice must remain accessible with the cover off. Burying a spliced section fails the access requirement.

How much support does a wireway need?

A wireway is supported on its own, not on the conduits feeding it. Run horizontally, the common requirement is support at each end and at intervals on the order of 5 ft unless listed for more, with vertical runs supported differently. Size the supports for the loaded weight and confirm the intervals against the adopted code.

Do you derate conductors in a wireway?

In a metal wireway, the bundling ampacity adjustment applies only when more than 30 current-carrying conductors share a cross section. A nonmetallic wireway derates the way conduit does, starting at a small handful of conductors. Count current-carrying conductors at the worst section and verify the threshold against the adopted NEC.

Does an outdoor wireway need a special rating?

Yes. Outdoors or anywhere water reaches it, a wireway must be raintight, commonly NEMA 3R, built so rain and sleet stay out and condensation can drain. The fittings and joints have to hold the rating too. A standard indoor Type 1 trough outdoors fills with water and rusts from the inside.

Why does a gutter at the switchboard need bending space?

When a gutter turns conductors into gear, the conductors deflect at the terminals, so the trough needs the depth to make the turn without over-bending the insulation. The wire-bending space tables, commonly NEC 312.6, set the dimension. A gutter sized on fill alone can still be too shallow to turn large conductors into the lugs.

How do you size a wireway?

Start at the 20 percent conductor fill, dividing the total conductor area by 0.20 to get the minimum interior area. Then add room for splices under the 75 percent local limit and for bending space where conductors turn into gear. On any run that splices or turns, size up a trade size, because the bend often governs over the fill.

Does a metal wireway need bonding?

Yes. A metal wireway must be bonded so the metal can carry fault current, and the bolted joints between sections are not automatically reliable because paint and gaskets break the path. Use bonding jumpers or listed connections at every joint and verify continuity. An isolated section looks grounded and is not, which a fault finds the hard way.

People also ask

Codes cited in this guide

This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.