ANVILFIELD Try FieldOS

Electrical

Wiring methods, raceways, and conduit types for electrical crews

Pick the raceway or cable by the location, the exposure, and the protection it needs, then support it, bend it, and ground it the way the method demands.

Wiring MethodsConduit TypesRacewayMC CableNEC Chapter 3Electrical

Direct answer

A wiring method is the code-approved way to run conductors: a raceway like conduit or tubing, or a cable assembly, chosen for the location, the exposure, the physical protection needed, and cost. NEC Chapter 3 governs which method is permitted where. The adopted code edition and the AHJ control the final call.

Key takeaways

  • NEC Chapter 3 governs wiring methods; location and exposure decide what is legal, and cost only breaks a tie between methods that both pass.
  • Total bends between two pull points cannot exceed 360 degrees, which is four quarter-bends, and every offset and kick counts.
  • EMT, RMC, and IMC support within 3 ft of a box and every 10 ft; MC cable every 6 ft, AC cable and FMC every 4.5 ft.
  • All underground and the inside of any exterior raceway above grade are wet locations, requiring wet-rated conductors like THWN-2, XHHW-2, or RHW-2.
  • NEC 250.118 permits RMC, IMC, and EMT as equipment grounding conductors only when every coupling and fitting is made up tight.

What a wiring method is, and the choice it forces

A wiring method is the approved way conductors get from one point to another: inside a raceway like conduit or tubing, or bundled into a cable assembly that carries its own protection. NEC Chapter 3 is the part of the code that lists the methods and tells you where each one is allowed. Every run on a job is one of these methods, and picking the wrong one is the kind of mistake that gets a whole feeder torn out.

The choice comes down to four questions you answer before you cut anything. What is the location: wet, damp, dry, corrosive, or hazardous. What is the exposure: out in the open where it can get hit, concealed in a wall, or buried in the ground. How much physical protection does the conductor need. And what does it cost to install, counting labor, not just material.

Those questions do not weigh the same. Location and exposure decide what is even legal. Cost only breaks a tie between two methods that both pass. The trap is reaching for the cheap, fast method out of habit and finding out at inspection that the location ruled it out. Decide the method from the conditions first, then let cost sort the survivors.

How do you choose a wiring method?

Choose the wiring method by reading the location and the exposure off the conditions, then matching them to a method the code permits there, then letting cost decide between the methods that qualify. The spec sets the floor, the code sets the rules, and the AHJ has the final word on the job in front of you.

Start with the worst condition the run sees anywhere along its length. A raceway that is dry for 40 ft and wet for 2 ft is a wet-location run, and it gets a wet-location method and wet-rated conductors for the whole length, because the conductors are continuous. The same logic applies to corrosion and physical damage: the harshest point on the route sets the method.

Then read the drawings and the spec. A spec will often call out the method by area, EMT in finished spaces, rigid for exposed exterior, PVC underground, and that callout governs even when a cheaper method would technically pass the code. The estimator priced the method on the drawings; the field that swaps it for something cheaper owns the change order and the argument with the inspector. Where the spec is silent, fall back to Chapter 3 and confirm the gray areas with the AHJ before the conductor is on the truck, not after it is in the pipe.

The metal conduit family: RMC, IMC, and EMT

Three rigid metal raceways cover most commercial work, and they are not interchangeable. Rigid metal conduit, RMC, lives in NEC Article 344. It is the thickest wall, threaded at the ends, and it takes the most physical abuse of the three. Reach for it on exposed exterior, on service risers, in areas that get hit, and anywhere the spec wants the heaviest protection. The price you pay is weight and labor, because every joint gets threaded and made up tight.

Intermediate metal conduit, IMC, is Article 342. It has the same outside diameter as RMC but a thinner wall, so it weighs less, costs less, and gives you a little more room inside for conductors. The code approves IMC for the same uses as RMC, which makes it the smart swap on a lot of jobs where rigid is specified out of habit. A foreman who knows the two are interchangeable for most uses can shave real labor off an exterior run.

Electrical metallic tubing, EMT, is Article 358. It is the thin-wall, the common indoor raceway, unthreaded and joined with set-screw or compression fittings. EMT is what you see in finished commercial spaces, above accessible ceilings, and running clean overhead in a data center. It is faster to install than rigid or IMC, but it is not built for severe physical damage, and it is the wrong call where the run can get crushed or rammed. Set-screw fittings are fine in a dry indoor space; where the location is wet or you need a raintight joint, use compression fittings rated for it.

Type / NEC articleWall and joiningWhere it fitsWatch for
RMC, Article 344Thickest wall, threadedExposed exterior, risers, severe physical damage, any occupancyHeaviest and slowest to install
IMC, Article 342Same OD as RMC, thinner wall, threadedSame uses as RMC, lighter and cheaperMore room inside than RMC, less than EMT
EMT, Article 358Thin wall, set-screw or compressionIndoor dry, finished commercial, data centersNot for severe damage; compression for raintight

PVC conduit: Schedule 40 and Schedule 80

Rigid PVC conduit, Article 352, is the workhorse for underground, wet, and corrosive runs. It does not rust, it is cheap, and it goes together fast with solvent cement. The two schedules you stock are Schedule 40 and Schedule 80, and the difference is wall thickness. Schedule 80 has a thicker wall and less interior room for the same trade size, so it holds fewer conductors than Schedule 40 of the same size.

Underground is where PVC earns its keep. Every underground installation is a wet location by definition in 300.5, so the conductors inside get a wet rating no matter how dry the soil looks. Schedule 40 handles standard direct burial. PVC is also permitted in wet locations above grade and in corrosive areas like wash-down spaces and water-treatment plants, where steel would not last.

The schedule split matters most where the conduit can get hit. Schedule 40 is permitted exposed where it is not subject to physical damage. Schedule 80 is the one identified for areas subject to physical damage, which is why the stub-up out of the ground and the exposed run up a wall are usually Schedule 80. The code calls for protection on the portion from the minimum cover depth up to about 8 ft above grade, and most jurisdictions read that as Schedule 80 for the stub-up. The common field move is Schedule 40 in the trench and Schedule 80 where it surfaces. PVC also moves a lot with temperature, so a long run needs expansion fittings, covered below.

The flexible: FMC, LFMC, and LFNC

Flexible raceway exists for the places a rigid pipe cannot go: the last connection to a motor that vibrates, the whip to a piece of equipment that has to be moved for service, the jog around an obstruction in a tight ceiling. There are two families, and the line between them is water.

Flexible metal conduit, FMC, Article 348, is the old Greenfield. It is a dry-location method. It is the right call for the final whip to a motor, a transformer, or a light fixture inside a building, where the flex absorbs vibration and lets the equipment be disconnected without cutting pipe. What it is not is watertight. The code does not permit standard FMC in wet locations, so it stays indoors and dry.

Liquidtight flexible metal conduit, LFMC, Article 350, is FMC with a watertight jacket over the metal core. Its nonmetallic cousin, LFNC, is Article 356. Both are made for wet, damp, and outdoor work, which is why the whip to a rooftop unit, an exterior motor, or a pump in a wet pit is liquidtight, not plain flex. Use liquidtight fittings made for the conduit, made up tight, or the jacket does nothing and water tracks into the equipment. The short rule: flex for vibration and final connections, liquidtight when any part of that connection sees weather or wash-down.

MC cable and AC cable, and how they differ from conduit and wire

Cable wiring methods carry their conductors and their armor in one assembly, so you pull the whole thing at once instead of running an empty raceway and then pulling wire. On commercial branch-circuit work, that speed is the reason MC cable is everywhere.

Metal-clad cable, Type MC, Article 330, is the common one. It is approved for a wide range: indoor and outdoor, exposed and concealed, in cable tray, and in some hazardous locations when the specific cable is listed for it. The branch-circuit homeruns and the whips to lights and devices above an accessible ceiling are usually MC. Armored cable, Type AC, Article 320, looks similar but is more limited. AC is generally a dry indoor method and is not for damp, wet, or corrosive spots. The two are not the same product, and substituting one for the other without checking the location is a quiet code violation.

MC versus conduit and wire is a real decision, not a default. Cable wins on labor in repetitive branch-circuit work and open ceilings, where pulling a finished assembly beats running pipe. Conduit and wire wins where you need physical protection, where conductors may change later, or where the spec demands a raceway. A lot of jobs run both: MC for the branch circuits, conduit for the feeders and the exposed work. Support requirements differ between the two cables and from conduit, which the support section below lays out, because that is where inspectors catch the cable methods most often.

Cable / NEC articleWhere permittedSupport intervalSecure near termination
MC cable, Article 330Indoor/outdoor, exposed/concealed, tray, some hazardous if listed6 ftWithin 12 in (4 or fewer conductors, #10 or smaller)
AC cable, Article 320Dry indoor; not damp, wet, or corrosive4.5 ftWithin 12 in

NM cable (Romex), and where it stops

Nonmetallic-sheathed cable, Type NM, Article 334, is Romex: conductors in a plastic jacket, no armor. It is fast and cheap, and it is a dwelling method. NM belongs in homes and similar residential occupancies, run concealed in walls and ceilings, in dry locations.

Where it stops is the part crews get wrong on a mixed job. NM is a dry-location method, so it is out of wet and damp spots. The code also restricts it by building construction type and largely keeps it out of commercial work, especially exposed. If you are pulling Romex across an open commercial ceiling because it was on the truck, an inspector who knows Article 334 will fail it, and the fix is MC cable or conduit and wire. On a job that is part residential and part commercial, the method has to change at the line, not ride the habit across it. Confirm what the adopted code and the AHJ allow for the specific occupancy and construction type before you commit a method.

What is the difference between a wet, damp, and dry location?

A dry location is normally free of moisture. A damp location is sheltered but subject to some moisture, like a covered exterior porch or a basement. A wet location is exposed to weather, washing, or saturation, and it includes anything underground and the inside of any raceway above grade that is out in the weather. The location category decides both the wiring method and the conductor insulation, so getting it right is upstream of everything else.

The conductor is where this bites. Common building wire, THHN, is rated for dry and damp locations only. In a wet location you need a wet-rated conductor: THWN-2, XHHW-2, RHW-2, or another type listed for wet use. The practical answer on most commercial jobs is THWN-2, because it is rated 90 degrees C in both wet and dry and covers the whole run without a second thought. THHN and THWN are often combined on the same conductor, but read the print and confirm the wet rating before you pull it through a raceway that is a wet location.

Here is the part that catches people: a raceway above grade out in the weather is a wet location inside, even when the pipe looks dry. Water gets in through fittings and condensation, so the conductors in that exterior EMT or PVC run are in a wet location and need a wet-rated conductor. Run the raceway so it can drain, and do not create a low spot that traps water against a fitting or a box. A water trap in an exterior conduit is a freeze-and-corrode problem waiting on the first cold snap.

How often do you support conduit and cable?

Support and securing intervals are set by the method, and they are two separate requirements: secure near every box or termination, and support along the run at the interval. For the rigid metal raceways, EMT, RMC, and IMC, the common rule is a support within 3 ft of each box, cabinet, or fitting, and at intervals not over 10 ft along the run. RMC for larger trade sizes is allowed a longer interval per its table, but 10 ft and within 3 ft is the figure to carry in your head.

Cable methods are stricter on the near-box distance. MC cable is secured within 12 in of a box or fitting for cables with four or fewer conductors no larger than #10, and supported at intervals not over 6 ft. AC cable is tighter still: within 12 in of a box and supported every 4.5 ft. Flexible metal conduit, FMC, follows roughly the AC pattern, secured within 12 in and at about 4.5 ft. PVC support is a table by trade size, with the small sizes supported close, around every 3 ft, and a support within 3 ft of each box.

Where the structure will not let you land a support within the required distance of a box, the code gives a little relief, commonly out to 5 ft, but that is an exception, not the plan. The mistake inspectors write up most is the long span: a run of EMT or MC sagging past the interval because the crew was chasing footage. The other one is the missing strap right at the box. Both are easy to fix before inspection and embarrassing to fix after.

Method / NEC articleMax support intervalSecure near box/termination
EMT, 358.3010 ftWithin 3 ft
RMC, 344.3010 ft (longer for large sizes per table)Within 3 ft
IMC, 342.3010 ftWithin 3 ft
PVC, 352.30Per Table 352.30 by size (about 3 ft for 1/2 to 1 in)Within 3 ft
MC cable, 330.306 ftWithin 12 in (small cables)
AC cable, 320.304.5 ftWithin 12 in
FMC, 348.30About 4.5 ftWithin 12 in

Bends and fill: the 360-degree rule and the radius

Between any two pull points, a box, a conduit body, or a piece of equipment, the total of all the bends in a raceway cannot add up to more than 360 degrees. That is four quarter-bends, and every offset and kick counts toward the total. The rule shows up in each conduit article: 358.26 for EMT, 344.26 for RMC, 352.26 for PVC, and so on. The reason is the pull. Past 360 degrees the friction climbs to where you are dragging insulation across the conduit wall and skinning the conductors, and you cannot get a clean pull.

The radius matters as much as the count. Each bend has to meet a minimum radius so the conductors are not kinked, and the radius values come from NEC Chapter 9, Table 2. A factory sweep is the easy way to hold the radius on larger conduit; a hand bender holds it on the small stuff if you set the shoe right. Tight, flattened bends are a workmanship reject and they wreck a pull.

Fill is the partner to bends and it has its own rules. The short version: conductors cannot take more than 40 percent of the conduit's interior cross-section for three or more conductors, with different limits for one or two, all from NEC Chapter 9. A legal fill is not automatically a good pull, and a run that is at maximum fill and near maximum bends is a run that fights you the whole way. The companion conduit-fill guide on this site walks the percentages, the conductor-area tables, and a worked example; size the raceway from the conductor schedule, not from what looks about right.

Boxes, fittings, and expansion joints

Every raceway and cable terminates in a box or an enclosure, and the box has to be big enough for what lands in it. Box fill is a real calculation in NEC 314.16: each conductor, device, clamp, and ground counts for a volume, and the box has to hold the sum. A jammed box overheats and makes the next person's splice a fight. Size it from the count, the same way you size the conduit from the fill.

Fittings have to be listed for the method and the location. A connector made for EMT is not a connector for MC cable, and a dry-location fitting in a wet box is a leak. Where water is present, the fittings are raintight or wet-location rated, and they are made up tight, because a loose fitting is both a water path and, on a metal system, a break in the ground. Use the bushing, the locknut, and the connector the method calls for, not whatever is in the bottom of the bag.

Long runs move with temperature, and that movement has to go somewhere. PVC is the big offender: it expands and contracts a lot, on the order of 4 in per 100 ft for a 100 degree F swing, so a long straight PVC run, especially exposed or in direct sun, needs an expansion fitting sized from the manufacturer's table for the temperature range. Long exposed metal runs and runs that cross a building expansion joint need expansion or deflection fittings too. Skip the expansion fitting on a long sun-baked PVC run and it will bow, pull out of a coupling, or crack a box. The code addresses thermal movement in 300.7 and the PVC expansion provisions in 352.44; confirm the figures against the product listing.

Hazardous (classified) locations

Where flammable gas, vapor, dust, or fibers can be present, the wiring method changes completely, and the code devotes Articles 500 through 516 to it. These are classified locations, sorted by Class (I gas and vapor, II dust, III fibers) and by Division or Zone, which describe how likely the hazard is present. A fuel-dispensing area, a paint booth, a grain facility, a chemical process line: each carries a classification that dictates the method.

The point of the method here is to keep an arc or a hot surface inside the wiring from igniting the atmosphere. In the more severe classified areas, that commonly means threaded rigid metal conduit or IMC, explosionproof fittings and enclosures, and sealing fittings, the seal-offs, installed where conduit crosses a boundary or enters an enclosure, so a flame cannot travel down the pipe. Certain MC cable types listed for hazardous use are also permitted in some areas.

Do not freelance in a classified space. The classification, the boundaries, and the permitted methods come off an area classification drawing and the specific articles for that occupancy, and the AHJ enforces them hard because the consequence is an explosion. Confirm the class, division, and group before you pick a fitting, and confirm the seal locations against the code section for that class, commonly the 501, 502, or 503 series, and the adopted edition.

Corrosion and dissimilar metals

Corrosive environments eat ordinary raceway, and the fix is either a nonmetallic method or a metal protected for the condition. PVC is the first answer in a lot of corrosive spots because it simply does not rust. Where you need the strength of metal in a corrosive area, PVC-coated rigid metal conduit, the bonded-coating rigid, gives you steel inside a sealed plastic skin, and it is the standard for wash-down plants, water treatment, and similar service. Stainless steel raceway and fittings cover the harshest chemical and coastal exposures where even coated steel struggles.

Dissimilar metals in contact are their own corrosion problem. Put aluminum and steel together in a damp spot, or aluminum fittings on a steel system in a wet location, and you set up galvanic corrosion that eats the more active metal. Aluminum conduit also reacts with the lime in fresh concrete and masonry, so it gets a protective coating where it is embedded or in contact. The code requires raceways and fittings to suit the corrosive condition in 300.6; the field habit that backs it up is matching metals and protecting the buried or embedded portion.

The failure shows up at the worst place: the fitting and the coupling, where the coating is thinnest and the threads are exposed. On a coated rigid system, touch up the cut threads with the manufacturer's compound before you make up the joint, or you have left a bare-steel ring to rust right at the connection.

Underground: burial depth and warning tape

Underground runs have a minimum cover, the depth of earth over the top of the raceway or cable, set by NEC Table 300.5 by method and by what is overhead. The values move, so read the table for the job, but the figures crews carry are these: rigid metal and IMC can go shallowest, commonly 6 in; PVC and other nonmetallic raceway listed for direct burial commonly want 18 in; direct-buried cable without a raceway commonly wants 24 in. Under streets, roads, and parking lots, almost everything goes to 24 in. Concrete encasement can reduce some of these depths.

Remember that underground is a wet location, every time, so the conductors in that buried PVC are wet-rated whether the trench is dry clay or standing water. Run the conduit so it drains toward the ends and does not belly into a low spot that fills and freezes.

Warning tape is the cheap insurance that the next backhoe does not find your feeder the hard way. The code requires a marking ribbon above certain underground runs, and it is good practice over any energized run, buried 12 in or so above the conduit so a future dig hits the tape before the pipe. The companion guides on this site cover conductor sizing and the heat side of buried runs; this guide is about getting the right raceway in the ground at the right depth. Confirm the cover values and the tape requirement against Table 300.5 and the adopted edition.

MethodTypical minimum coverNote
Rigid metal / IMC6 inGeneral; deeper under roads
PVC listed for direct burial18 inAll underground is a wet location
Direct-buried cable (no raceway)24 inWithout a raceway
Under streets, roads, parking lots24 inApplies to most methods
Concrete-encasedReduced per tableEncasement buys shallower cover

Can the metal conduit be the equipment ground?

Yes, a properly installed metal raceway is a permitted equipment grounding conductor. NEC 250.118 lists RMC, IMC, and EMT among the acceptable equipment grounding conductors, so when the pipe is steel, the couplings are made up tight, and every fitting is wrench-tight, the raceway itself carries fault current back to clear the breaker. That is why a lot of EMT branch circuits run with no separate green wire.

The word that does the work is properly. The ground path is only as good as its worst connection. A loose set-screw coupling, a fitting that backed off, a knockout missing its locknut, a length of pipe joined with a non-listed fitting: any one of those is an open in the ground that nobody sees until there is a fault and the breaker does not trip. On systems over 250 V to ground, and where concentric or eccentric knockouts are present, bonding bushings or bonding jumpers are required so the path is solid around those openings.

This is why many specs require a separate equipment grounding conductor pulled in the raceway even on metal systems, especially for feeders, isolated-ground circuits, and anything critical. The flexible methods make the case for the separate wire on their own: FMC and LFMC qualify as a ground only within tight limits on size, length, and overcurrent rating, so the safe default on flex is a separate EGC pulled with the circuit. Where the design relies on the raceway as the ground, the install has to earn that reliance at every joint. If you are not sure the path is unbroken, pull the wire.

Wiring methods in the data center

The data center is where the clean-overhead methods show their value. The distribution overhead is usually a mix of EMT for the branch raceway and overhead cable tray carrying the bulk of the cabling, with the runs kept straight, parallel, and squared so the room reads as orderly. Cable tray is a topic of its own, with its own fill and support rules, but it is the method that carries the volume above the racks.

MC cable does the last leg. The whips from the overhead distribution down to the racks, the PDUs, and the busway taps are commonly Type MC, because the assembly pulls fast and flexes into the rack without a separate raceway. On a floor that gets reconfigured as load changes, the MC whip is quick to add, move, and retire.

Two field points matter here. Air handling: where the overhead space is used as a return-air plenum, the wiring method and any cable have to be the plenum-rated, low-smoke type the code requires for that space, and the inspector checks it. And neatness is not cosmetic in this room. Sloppy overhead work blocks the cooling path, makes the next change a hazard, and reads as a quality problem to a client paying for uptime. Run it straight, support it to the interval, and label it.

Workmanship: what makes a run pass on looks alone

An inspector forms an opinion of an install in the first ten seconds, and it comes from the workmanship before a single measurement. Runs that are straight, level, and parallel, bends that match across a rack of conduit, supports landed on a line: that work earns the benefit of the doubt. Runs that wander and sag get every dimension checked twice.

The details that separate a clean run from a sloppy one are small and they are all on the conductor's side. Ream every cut so the sharp inside edge does not slice insulation on the pull. A bushing on the threaded ends does the same job where the code calls for it. Keep parallel runs evenly spaced and supported together, not strapped wherever a hole landed. Make up every fitting tight, both for the ground path and so the run does not rattle loose.

The burr is the one rookies leave. A reamer or a file takes ten seconds and saves the insulation; a hacksaw cut left raw is a knife edge inside the pipe waiting for the pull. The crew that reams as it cuts never thinks about it again. The crew that does not finds the damage at the megger, or worse, at the fault.

What to document

The record on a wiring method is what answers the question later: was this run done right for where it is. When a buried feeder gets dug up in five years or a wet-location run starts faulting, the documentation is what proves the method and the conductor matched the location.

For each run, capture the wiring method and its NEC article, the location rating that drove it, the conductor insulation type, how it is supported and secured, the equipment grounding path, the bends between pull points, and the burial depth where it applies. If you upsized the method or changed it from the drawings, write down why and who approved it, because the next person will ask.

Field to recordWhy it matters
Wiring method and NEC articleProves the method is approved for the use
Location rating (wet/damp/dry/corrosive/hazardous)Drives the method and the conductor
Conductor insulation typeMust suit the location (THWN-2 in wet)
Support spacing and securingWhat the inspector measures
EGC: raceway, or separate conductor and sizeConfirms the fault-current path
Bends between pull pointsStays at or under 360 degrees
Burial depth and cover, if undergroundMatches Table 300.5

Common mistakes

  • Running EMT outdoors or underground without the listing, fittings, and protection the location demands.
  • Using standard FMC in a wet location, where it is not permitted; the wet method is liquidtight LFMC or LFNC.
  • Putting more than 360 degrees of bends between pull points, which skins insulation and kills the pull.
  • Stretching support spacing past the interval, or leaving no strap within the required distance of a box.
  • Pulling THHN-only conductors through a raceway that is a wet location, where a wet-rated type like THWN-2 is required.
  • Relying on the metal raceway as the ground where a coupling is loose, a fitting is not made up tight, or a bonding bushing is missing.
  • Running NM cable exposed in a commercial occupancy, where the method is not permitted.
  • Using Schedule 40 PVC for a stub-up or exposed run subject to physical damage, where Schedule 80 belongs.
  • Skipping the expansion fitting on a long, sun-exposed PVC run, so it bows, cracks, or pulls out of a coupling.

Field checklist

0 of 11 complete

Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.

Standards and references

The NEC, NFPA 70, Chapter 3, is where the wiring methods live, and each method has its own article: EMT in 358, RMC in 344, IMC in 342, rigid PVC in 352, FMC in 348, LFMC in 350, LFNC in 356, MC cable in 330, AC cable in 320, and NM cable in 334. The general rules that cut across all of them sit up front: 300 for wiring methods and support, 300.5 for underground cover, 300.6 for corrosion protection, and 300.7 for thermal movement. The 360-degree bend limit appears in each conduit article, and the fill and bend-radius tables are in Chapter 9.

Grounding and the use of a raceway as an equipment grounding conductor come from Article 250, with 250.118 listing the permitted equipment grounding conductors. Classified locations are Articles 500 through 516. Wet-location and conductor-insulation rules come from Article 310. Box fill is 314.16.

Two cautions on citing all of this. Article and section numbers shift between code cycles, so confirm them against the edition the jurisdiction has actually adopted and any local amendments before you put a number on a submittal. And the products themselves are governed by UL listings and the manufacturer's instructions, which can be stricter than the general code rule and which the AHJ will hold you to. Cite the article that controls the point, and let the project specification override habit where it is more demanding.

Units, terms, and the location categories

Wiring methods carry a lot of acronyms and a few unit conventions, and the same idea can read differently across a drawing set, a spec, and a manufacturer sheet.

Conduit and tubing are sold by trade size, a nominal designation that is close to but not exactly the inside diameter, given in inches in the US and in metric designators on imported product. Support and burial dimensions are in feet and inches in the NEC and in millimeters in metric sources. The location categories, wet, damp, and dry, are defined terms in the code, not casual descriptions, and the method and conductor follow the category. Carry the location category in your head as the first thing you decide on any run, because it is the input every other choice depends on.

Raceway
An enclosed channel made to hold conductors, such as conduit or tubing
RMC / IMC / EMT
Rigid metal conduit, intermediate metal conduit, electrical metallic tubing
PVC (Schedule 40/80)
Rigid nonmetallic conduit; Schedule 80 has thicker walls for physical damage
FMC / LFMC / LFNC
Flexible metal conduit (dry), and liquidtight flexible metal and nonmetallic conduit (wet)
MC / AC cable
Metal-clad cable and armored cable, conductors with armor in one assembly
THWN-2 / THHN
Wet-rated building wire, and dry/damp-only building wire
EGC
Equipment grounding conductor, the fault-current path back to the source
Wet / damp / dry location
NEC location categories that decide the method and the conductor

Related tools

Calculators and readiness checks for this work

Compare your options

FAQ

What is the difference between EMT and rigid conduit?

EMT is thin-wall tubing joined with set-screw or compression fittings, made for indoor dry and finished commercial work. Rigid metal conduit (RMC) has a much thicker wall, is threaded, and takes severe physical damage and exterior exposure. EMT installs faster; rigid protects more. Match the wall to the abuse the run will see.

Can you use EMT outside?

EMT can be used outdoors when it is listed for the use, joined with raintight compression fittings, and the conductors are wet-rated, because an exterior raceway is a wet location inside. It is not for severe physical damage. Many specs send exposed exterior to rigid or IMC instead, so check the drawings and the AHJ.

MC cable vs conduit and wire: which do you use?

MC cable wins on labor for repetitive branch circuits and open ceilings, since you pull a finished assembly instead of running empty pipe and then wire. Conduit and wire wins where you need physical protection, expect to change conductors later, or the spec requires a raceway. Many jobs run MC for branches and conduit for feeders.

How often do you support conduit?

EMT, RMC, and IMC are commonly supported within 3 ft of each box and at intervals not over 10 ft. MC cable runs 6 ft with securing within 12 in of a box; AC cable and FMC run about 4.5 ft within 12 in. PVC follows a table by trade size. The adopted edition controls.

When do you use Schedule 80 PVC instead of Schedule 40?

Use Schedule 80 PVC where the conduit is exposed to physical damage, which is why stub-ups out of the ground and exposed runs up a wall are usually Schedule 80. Schedule 40 handles direct burial and exposed runs not subject to damage. The common move is Schedule 40 in the trench, Schedule 80 where it surfaces.

Can flexible metal conduit (FMC) be used in a wet location?

No. Standard FMC is a dry-location method and the code does not permit it in wet locations. For a wet, damp, or outdoor connection, such as a whip to a rooftop unit or an exterior motor, use liquidtight flexible metal conduit (LFMC) or LFNC with liquidtight fittings made up tight.

Can the metal conduit be the equipment ground?

Yes. NEC 250.118 lists RMC, IMC, and EMT as permitted equipment grounding conductors when the couplings and fittings are made up tight and the path is unbroken. A loose coupling or missing locknut opens that path. Many specs require a separate green EGC anyway on feeders and critical circuits for that reason.

How many bends can you put in a conduit run?

No more than 360 degrees of total bends between pull points, which is four quarter-bends, and every offset and kick counts. The rule appears in each conduit article, like 358.26 for EMT and 344.26 for RMC. Past 360 degrees the friction skins the conductor insulation and you cannot get a clean pull.

Can you run NM cable (Romex) in a commercial building?

Generally no, not exposed. NM cable is a dwelling method for dry, concealed residential work, and Article 334 restricts it by occupancy and building construction type. In commercial spaces the method is usually MC cable or conduit and wire. Confirm what the adopted code and the AHJ allow for the specific occupancy before you commit.

What conductor do you use in a wet location?

Use a wet-rated conductor such as THWN-2, XHHW-2, or RHW-2. Plain THHN is rated for dry and damp only. Remember that underground and the inside of an exterior raceway above grade both count as wet locations, so those conductors get the wet rating for the whole run, not just the wet section.

People also ask

Codes cited in this guide

This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.