Electrical
Conduit bending fundamentals for electrical crews
Bend EMT, IMC, and rigid clean and accurate: set the stub from the deduct, the offset from the multiplier, the saddle from its marks, and stay under the 360-degree limit.
Direct answer
Conduit bending is shaping EMT, IMC, or rigid raceway to route it cleanly between two points without kinking or flattening the pipe. The four bends every electrician learns are the 90-degree stub, the back-to-back, the offset, and the saddle, each set from marks and a take-up or multiplier. The adopted code edition and the bender markings govern.
On this page
What conduit bending is, and what a good bend costsWhy clean, accurate bends pay off downstreamThe hand bender and the three marks on the headThe four core bendsHow do you bend a 90-degree stub?What is the take-up (deduct) for a 90?The back-to-back bendWhat is the offset multiplier?Offset shrink: why the run lands shortThe three-point saddleThe four-point saddleThe kickHitting the angle: the level and the bender as a protractorSpringback and gain: why the pipe fights your numberHow many bends does the NEC allow between pull points?EMT vs IMC and rigid: same geometry, more forceField layout: measure, mark, dry-fitLarger conduit: mechanical and hydraulic bendersRacking parallel runs: concentric bendsCommon bend errors and how to fix themThe bend math at a glanceField checklistWhat to document and coordinateCommon mistakesStandards and referencesUnits and termsOpen the related tool for the calculation, checklist, or packet.
FieldOS by AnvilfieldOffline-first FieldOS for job photos, proof packets, property memory, calculations, teams, billing, and owner-ready reports.Key takeaways
- The NEC caps total bend at 360 degrees (four quarter bends) between pull points; EMT is in 358.26, IMC 342.26, rigid 344.26.
- Bend a 90 stub by subtracting the bender take-up (deduct) from the stub height, marking from the end, and bending on the arrow.
- Typical EMT take-up: 5 in for 1/2 in, 6 in for 3/4 in, 8 in for 1 in; confirm against the casting.
- Offset distance between bends equals offset depth times the multiplier: 30 deg = 2, 45 deg = 1.4, 22.5 deg = 2.6, 10 deg = 6.
- Keep every offset and saddle bend in one plane; a pipe that rolls between bends makes a dog-leg you cut off and re-bend.
What conduit bending is, and what a good bend costs
Conduit bending is shaping a length of EMT, IMC, or rigid metal conduit so it follows the route you need without cutting the run into a dozen fittings. You do it with a marked bender, a few numbers in your head, and a feel for how the pipe moves under foot pressure. The work is part math and part muscle memory, and the math is the part people skip and then pay for.
A good bend does three things at once. It pulls easy, because the conductors slide through a smooth radius instead of fighting a sharp corner. It looks right, because a rack of conduit with matched bends is the first thing an inspector and a general contractor read as competent work. And it stays legal, because the code caps how much total bend you can stack between pull points and how tight the radius can get.
The thing a first-timer misreads is that bending is forgiving. It is not. A stub cut an inch short is scrap. An offset bent in the wrong plane is a dog-leg you cannot twist out. The bender does exactly what your mark and your angle tell it to, so the accuracy lives in the layout, not the pull on the handle.
Exposed conduit work is part of plant additions and machine relocations. PorchRocket's Ground Control returns manufacturing buildings selected by size for a contractor building a customer list for that installation work.
Why clean, accurate bends pay off downstream
Every degree of bend you put in a run is friction the wire crew has to overcome later. The code limits total bend for that reason, and a sloppy run hits the wall faster than a clean one because flattened or kinked bends bite the insulation. The conduit-fill picture matters here too: a tightly filled conduit through rough bends is the pull that jams. Our conduit fill guide covers the percent-fill side of that.
Appearance is not vanity on this trade. A parallel run where the offsets are not concentric, where the stubs land at different heights, where one saddle rides higher than the next, tells anyone walking the job that the crew was guessing. The reverse is also true. Tight, matched bends buy you the benefit of the doubt on everything the inspector cannot see.
Then there is rework. A bend that comes out wrong is not a quick fix. Metal conduit work-hardens when you bend it back, so straightening a bad bend and re-bending the same spot leaves a weak, deformed section that flattens or splits. Most of the time the honest move is to cut it off and start the piece over. Get it right the first time and the scrap pile stays small.
The hand bender and the three marks on the head
A hand bender is a cast shoe sized to one conduit diameter, with a long handle that gives the force and a foot pedal you press to seat the pipe and finish the bend. The size is stamped on it, and you do not mix them: a 1/2 in EMT bender will mar and mis-bend 3/4 in pipe. The numbers printed on the casting are the whole point, and three marks do most of the work.
The arrow is the reference for a stub-up. You line the arrow on your mark, and the bender's take-up is already accounted for in where the arrow sits relative to the bend. The star, sometimes a teardrop or a notch, is the back-to-back mark, used to set the second 90 of a back-to-back at the right distance. The rim notch, the dimple near the front of the shoe, is the center mark for the outer bends of a saddle and for offsets.
Most benders also carry degree references on the side, commonly 10, 22.5, 30, 45, and 60, and many have a cast-in level vial. Those are how you hit the angle without an angle finder. The hand sizes top out around 1 in or 1-1/4 in EMT. Past that, the force and the spring of the pipe push you to a mechanical or hydraulic bender, covered further down.
The four core bends
Four bends carry almost all hand work, and every other shape is a combination of them. Learn these and the layout for each, and the rest is arithmetic.
The 90-degree stub-up turns the run a quarter and stands a leg up to a box or a piece of gear. The back-to-back puts two 90s on one piece so both legs stand up a measured distance apart, like a U laid on its side. The offset steps the run over or around an obstacle with two equal-angle bends and returns it to the original line. The saddle jumps the run over something crossing its path, a pipe or another conduit, then drops back down.
The kick is the fifth one people forget to count: a single bend of less than 90 to nudge a run or raise a stub into a box. Each of these is set from a mark and an angle, and each has its own factor. Miss the factor and the bend is in the wrong place even when the angle is perfect.
How do you bend a 90-degree stub?
Subtract the bender's take-up from the height you want, mark the conduit that far from the end, set the bender arrow on the mark, and bend to 90 degrees. The take-up, also called the deduct, is the distance the bend itself eats up, so the stub finishes at the height you wanted measured from the surface to the end of the leg.
Work an example in 1/2 in EMT, where the take-up is typically 5 in. You want a 12 in stub. Mark at 12 minus 5, which is 7 in from the end. Put the arrow on the 7 in mark, foot on the pedal, and pull the handle until the leg stands at 90. Measure from the floor to the top of the stub and you land on 12 in, give or take springback you correct for as you go.
The two errors that ruin a stub: marking from the wrong end, and forgetting the deduct entirely so the stub comes out a full take-up too tall. Both are scrap, because you cannot add length back. Mark, then say the math out loud once before you step on the pedal. Five seconds of habit saves a stick of pipe.
What is the take-up (deduct) for a 90?
The take-up is fixed per bender size, and the common figures are typical values you should confirm against the casting in your hand. Read your bender. Manufacturers stamp the deduct on the shoe, and they do vary a little between makers and between EMT and rigid shoes.
The widely cited EMT numbers are in the table. They climb with diameter because the bend radius grows with the pipe. Treat them as a starting point, bend a test stub on an unfamiliar bender, and adjust if the first one lands off. Once you trust a bender's deduct, the stub math is the fastest bend you make all day.
| Conduit / bender size | Typical take-up (deduct) |
|---|---|
| 1/2 in EMT | 5 in |
| 3/4 in EMT | 6 in |
| 1 in EMT | 8 in |
| 1-1/4 in EMT | 11 in (confirm on the casting) |
The back-to-back bend
A back-to-back puts two 90s on one piece so both legs stand up the same direction a set distance apart, the shape you want for a conduit that drops out of one box, runs along a surface, and rises into another. The trick is setting the second bend so the distance between the two stubs is exactly what you measured.
Bend the first 90 as a normal stub. Then measure from the back of that first bend to where you want the back of the second bend, and mark there. Now flip the bender so the star, the back-to-back mark, sits on that mark with the handle pointing toward the first bend, and bend the second 90. The star is offset from the arrow by the bender's take-up, which is why it lands the second leg at the right distance instead of a take-up short.
The common miss is using the arrow for the second bend instead of the star, which puts the second leg one take-up off. The other is measuring to the inside of the first bend on one and the outside on the other, so the two legs do not match. Pick one reference, the back of the bend, and measure both the same way.
What is the offset multiplier?
An offset is two equal-angle bends that step the run over an obstacle and bring it back parallel to where it started, like going up a curb and continuing level. The multiplier turns the height you need to clear, the offset depth, into the distance you mark between the two bends. Distance between bends equals offset depth times the multiplier.
The multiplier comes from the bend angle, and four pairs cover most field work. A 30-degree offset uses a multiplier of 2, which is why it is the default: a 3 in offset needs marks 6 in apart, and the math is trivial standing on a ladder. A 45-degree offset uses 1.4 (1.414 exactly) and gives the shortest, tightest offset for a deep step in a short space. A 22.5-degree offset uses 2.6 for a gentle, easy-pulling bend, and a 10-degree offset uses 6 for a long, shallow nudge.
Bend the first angle on the arrow, slide the pipe through and rotate it 180 degrees so the second bend mirrors the first in the same plane, set the arrow on the second mark, and bend the matching angle. Keep both bends in one plane. The most common offset failure is letting the pipe roll between bends, which throws the second bend out of plane and gives you a dog-leg that no amount of twisting will straighten.
| Offset angle (each bend) | Multiplier | Shrink per inch of offset |
|---|---|---|
| 10 degrees | 6 | 1/16 in |
| 22.5 degrees | 2.6 | 3/16 in |
| 30 degrees | 2 | 1/4 in |
| 45 degrees | 1.4 (1.414) | 3/8 in |
Offset shrink: why the run lands short
Every offset shortens the conduit's reach along its original line, because the pipe travels up and over instead of straight. That lost length is the shrink, and it is the number that lands a stub-up off its box after a clean-looking offset. The shrink per inch of offset depth goes with the angle: roughly 1/4 in per inch at 30 degrees, 3/16 in at 22.5, 3/8 in at 45, and 1/16 in at 10.
Put it to work. A 30-degree offset 5 in deep shrinks about 5 times 1/4 in, so 1-1/4 in. If a box has to land at a fixed point past the offset, add that 1-1/4 in to your measurement before the offset, or the run comes up short and you are bending a correction nobody wanted.
Steeper angles clear more height in less length but shrink more. That is the trade. A 45 saves room along the run and is the move in a tight ceiling space, but it pulls harder and eats more length, so on a long run with sensitive end points the gentler 22.5 or 30 is usually the better call.
The three-point saddle
A three-point saddle hops the conduit over a single obstacle crossing its path, a water line or another conduit, then drops it back to the original surface. It is one center bend with two outer bends, and the classic recipe is a 45-degree bend in the middle flanked by two 22.5-degree bends, one on each side.
Lay it out from the obstacle's center. The center mark goes at the center of the obstruction plus the saddle shrink. Use the three-point saddle factor of 2.5 in of conduit per inch of obstruction height to set the two outer marks, measured 2.5 times the height on each side of the center mark. For a 3 in obstruction, that is 7.5 in to each outer mark. Saddle shrink runs about 3/16 in per inch of height.
Bend the center mark first, sitting it on the rim notch, pulled to 45. Then bend each outer mark on the arrow to 22.5, with the pipe rotated so all three bends sit in the same plane and the saddle rises straight up over the obstacle. Keep the center bend centered. If the center mark drifts, the conduit lands beside the pipe it was supposed to clear instead of squarely on top of it.
The four-point saddle
When the obstacle is wide, a flat duct or a beam, the three-point saddle's single center peak does not clear it cleanly. A four-point saddle solves it. It is two offsets back to back: the run steps up with one offset, runs level across the top of the obstruction, then steps back down with a matching offset on the other side.
Treat it as two separate offsets using the same multiplier and shrink rules. Pick an angle, usually 22.5 or 30 degrees, mark the first offset to step up by the height you need, run a measured flat across the top, then mark and bend the second offset to drop back down by the same height. The two offsets have to match in depth and angle or the run does not return parallel to where it started.
The flat section across the top is the part to measure carefully, because that length is what actually clears the width of the obstruction. Add a little so the conduit is not pressed against the corners it crosses. A four-point saddle that touches the obstruction at the bends transmits every vibration and is the rattling run someone complains about later.
The kick
A kick is a single bend of less than 90 degrees, used to nudge a run in a new direction or to raise a stub so it lands in a box that is not directly above the penetration. It is the quickest bend you make and the one with the least math, because you are not returning the pipe to a parallel line the way an offset does.
Set the angle you need and bend it on the arrow, watching the degree marks or a level. The thing to respect is that a kick changes where the end of the pipe lands in two directions at once, height and horizontal travel, so on anything tight you dry-fit before you trust it. A kicked 90, where a stub gets a small added angle to reach a box offset from the floor penetration, is the everyday version and worth practicing until it is automatic.
Hitting the angle: the level and the bender as a protractor
The mark sets where the bend goes. The angle sets the shape, and a few degrees off on an offset or saddle ruins the geometry even when the marks are perfect. So you need a reliable way to read the angle, not eyeball it.
Three ways cover the field. Read the degree marks cast into the bender and stop the handle at the line. Watch the level vial built into many bender heads, which reads true when you bend with the pipe on the floor and the handle coming up. Or set a magnetic angle finder or torpedo level on the free leg of the pipe and bend until it reads the angle you want. The angle finder is the most accurate and the one to reach for on a critical saddle.
A reliable trick for a 90: bend until the upstanding leg reads plumb on a level, then add a touch for springback. For partial angles, the cast marks get you close and the angle finder confirms. Whatever method you use, use the same one across a parallel run so the bends match. Mixing methods between pieces is how a rack ends up with offsets that almost line up.
Springback and gain: why the pipe fights your number
Two effects make a finished bend measure different from the geometry on paper, and both are predictable once you know them. Springback is the first. Metal conduit is springy, so when you release handle pressure the pipe relaxes open a few degrees from where you held it. You correct by overbending slightly, pulling a degree or two past the target so it settles on the angle when you let go.
Springback is small on EMT, often only a degree or two, and larger on IMC and rigid because the heavier wall stores more spring. On a rigid 90 you may overbend several degrees to land on square. Bend, release, check with the level or angle finder, and nudge it if it came back too far. Sneaking up on the angle beats blowing past it, because pulling a bend back open work-hardens the metal.
Gain is the other one, and it lives on the 90. The conduit sweeps a curve at the corner instead of meeting in a sharp point, so the pipe travels a shorter path through the bend than the two outside legs measured to the theoretical corner would suggest. That saved length is the gain. When you are cutting a piece to fit a fixed dimension between two 90s, you subtract the gain so the finished piece is not long. For single stubs it rarely matters; for a measured piece between two bends it is the difference between a fit and a re-cut.
How many bends does the NEC allow between pull points?
The NEC caps total bend at the equivalent of four quarter bends, 360 degrees, between pull points such as boxes and conduit bodies. The limit lives in the article for each raceway: EMT at 358.26, IMC at 342.26, rigid at 344.26, and the others in their Chapter 3 articles. Confirm the exact section against the adopted edition, since article and section numbers shift between code cycles.
The 360 is total, and it counts everything, not just the obvious 90s. A 30-degree offset is two 30-degree bends, so 60 degrees against your budget. Two 90s and a single offset already spend 240 degrees. Stack a saddle on top and you can blow past 360 on a run that did not look heavily bent. When the route needs more, you add a pull box or a conduit body to reset the count, which also gives the wire crew a place to pull from.
Radius is the other limit. The code sets a minimum bend radius so the pipe is not kinked or flattened, with the values in NEC Chapter 9, Table 2, and the field version is simpler: no kinks, no flattening, no reduction of the internal diameter. A hand bender's shoe is built to a legal radius, so a clean hand bend passes on radius by design. You fail radius by hand-forcing a bend the bender was not made for, or by flattening a bend with a worn shoe. The conduit-types guide carries the support and method rules that go with these limits.
EMT vs IMC and rigid: same geometry, more force
The math does not change between EMT, IMC, and rigid. The deducts, multipliers, and saddle factors are read off the bender for the conduit you are bending, and the layout is identical. What changes is the wall, the weight, and the force it takes to move the pipe, and that drives the tool you use.
EMT is thin-wall and bends by hand with foot pressure across the common sizes. IMC and rigid have thicker walls and threaded ends, so they resist the bend harder and spring back more. A hand bender shoe sized for rigid exists in the small sizes, but the effort climbs fast, and most crews move to a mechanical or hydraulic bender for rigid above the smallest diameters. The old hickey, a short-shoe bender, makes segmented bends in rigid by walking a series of small bends along the pipe, but it takes skill to keep those even and is mostly a repair and tight-spot tool now.
One detail that bites on rigid and IMC: the bend deforms threaded pipe near a coupling, so keep bends away from the threads and the fittings. And because springback is larger, overbend more and check the angle every time. A rigid run that has to be cut and threaded after bending leaves no room for a bend that came out a few degrees shy.
Field layout: measure, mark, dry-fit
The bend is only as good as the layout that precedes it, and the layout is where the time should go. Measure the run along the path the conduit will actually travel, not the straight-line distance, because every offset and saddle adds length the tape laid flat will miss. Account for the shrink of each offset and the take-up of each 90 before you commit a mark.
Mark clearly and consistently. A wrap of tape or a sharp pencil line all the way around the pipe so you can see it from any side, an arrow showing which way the bend goes, and the angle written next to the mark on a complex piece. On a saddle or a multi-bend run, lay the whole sequence out before the first bend, because once you bend the first one you have changed the reference for everything after it.
Then dry-fit before you trust it. On anything tight, anything that has to land in a fixed box, anything you cannot easily re-make, set the bent piece in place and check it before you cut the next one or call it done. The crews that bend fast are not the ones who skip the dry-fit. They are the ones whose layout is good enough that the dry-fit confirms instead of corrects.
Larger conduit: mechanical and hydraulic benders
Past about 1 in or 1-1/4 in, hand bending stops being practical, and the trade moves to mechanical and hydraulic benders. A mechanical bender, the ratchet or chain-drive type, multiplies force through a geartrain so one person can bend larger EMT and rigid. A hydraulic bender drives a ram against a shoe and bends the heavy sizes, up to several inches, that no person moves by hand.
The principles carry over, but the layout shifts. Big benders have their own deduct and gain figures, their own shoes per size, and many use a degree dial or a built-in indicator rather than the cast marks of a hand bender. The shrink and multiplier math for offsets is the same arithmetic; the take-up numbers are bigger and come off the machine's chart, not the small-bender stamps.
On the large sizes a single shoe bend is limited, so sweeping bends and factory elbows do a lot of the directional work, and the machine handles the offsets and saddles. This is a topic in its own right, and the field reality is that anyone running large rigid learns their specific machine's numbers cold, because a mis-bent 3 in rigid elbow is an expensive piece of scrap.
Racking parallel runs: concentric bends
Running several conduits side by side on a rack, the bends have to nest, not just match. When a group of parallel conduits turns a corner together, the bends are concentric, meaning each pipe's radius is centered on the same point so the spacing between conduits stays constant through the turn. The pipe on the outside of the turn needs a larger radius than the one on the inside, and the offsets along the run get staggered so they line up across the rack.
The practical method for offsets on a rack: shift each conduit's bend marks by the center-to-center spacing so the bends step across the group and the pipes stay parallel through the offset instead of crossing or bunching. For the 90s, the larger radius on the outer pipes is what keeps the spacing even around the bend. It takes layout and patience, and it is the work that separates a rack that looks engineered from one that looks improvised.
This is a topic crews specialize in, and the cleanest racks come from setting the spacing once, laying out every pipe's marks against that spacing, and bending the group in the same setup so the angles match. A rack where the conduits cross or the spacing wanders is the first thing a sharp inspector or PM notices, and it usually means the offsets were bent one pipe at a time without a common reference.
Common bend errors and how to fix them
Most bad bends fall into a few buckets, and knowing the symptom tells you the cause. The dog-leg is the classic: an offset or saddle whose two bends are not in the same plane, so the pipe twists out of line. It comes from letting the conduit roll between bends. There is no good fix once it is in. You cut it off and re-bend, and next time you mark a reference line down the pipe and keep it pointing the same way through both bends.
Bending the wrong direction, arrow backward, sends the bend the opposite way you needed. It is a layout and orientation error, caught by checking which way the bend goes before you step on the pedal, and uncorrectable after. A flattened or kinked bend, where the pipe ovals or pinches at the bend, comes from a worn or wrong-size shoe, too thin a pipe for the force, or forcing a radius the bender was not built for. A flattened bend reduces the internal diameter and fails on radius, so it gets cut out, not pulled through.
Then the measurement errors: a stub a take-up too tall because the deduct was skipped, a second back-to-back leg a take-up off because the arrow got used instead of the star, an offset that lands short because the shrink was never added. All of these are arithmetic caught by saying the math out loud before the bend. The expensive ones are the bends you cannot reverse, so the discipline is front-loaded into the layout.
The bend math at a glance
One table holds the numbers the four bends run on. The deducts are typical EMT values to confirm on your bender; the multipliers and saddle factor are standard trade math.
| Bend | Key mark or factor | How you set it |
|---|---|---|
| 90 stub | Take-up / deduct | Stub height minus deduct, mark from the end, bend on the arrow |
| Back-to-back | Star / back-to-back mark | First 90 on the arrow, second 90 on the star at the measured distance |
| Offset | Multiplier by angle | Distance between bends = offset depth x multiplier (30 deg = 2) |
| Three-point saddle | 2.5 per inch, center 45 | Center mark bent 45 on the notch, two 22.5 outer marks at 2.5 x height |
| Four-point saddle | Two offsets | Two equal offsets back to back with a measured flat across the top |
Field checklist
Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.
What to document and coordinate
Bending is mostly a field skill, but the parts worth writing down are the ones the next trade or the next phase depends on. On a parallel rack, record the center-to-center spacing and the bend radius used, so a tie-in run added later matches the rack instead of crossing it. On a run that is close to the 360-degree limit, note where the pull points landed and why, because that is the call an inspector or a wire crew will question.
Coordinate the route before you bend the long pieces. Conduit shares ceiling and wall space with duct, pipe, sprinkler, and structure, and a saddle bent to clear a line that later moves is wasted pipe. Walk the route, confirm the obstacles are where the drawing says, and check that your stub-ups land where the gear and boxes are actually set, not where the plan guessed. The bend you do not have to re-make is the cheapest one on the job.
| What to record or coordinate | Why it matters |
|---|---|
| Rack spacing and bend radius | A later tie-in run matches instead of crossing the group |
| Pull-point locations on long runs | Proves the run stayed under 360 degrees between boxes |
| Confirmed obstacle locations | A saddle bent to clear a moved line is scrap |
| Stub-up positions vs set boxes and gear | The leg has to land where equipment actually is |
Common mistakes
- Forgetting the deduct so the stub comes out a full take-up too tall.
- Using the arrow instead of the star for the second leg of a back-to-back.
- Reaching for the wrong multiplier, or mixing up the angle and its factor.
- Letting the pipe roll between bends, turning an offset or saddle into a dog-leg.
- Skipping the offset shrink, so a fixed end point lands short.
- Flattening a bend with a worn or wrong-size shoe, or forcing too thin a pipe.
- Bending the wrong direction with the arrow backward.
- Stacking offsets and saddles past 360 degrees between pull points.
Standards and references
The NEC, NFPA 70, sets the limits that govern a bend. Total bend between pull points is capped at the equivalent of four quarter bends, 360 degrees, in the article for each raceway: EMT at 358.26, IMC at 342.26, rigid metal conduit at 344.26, with PVC and flex in their own Chapter 3 articles. Minimum bend radius, so the pipe is not kinked or flattened, comes from NEC Chapter 9, Table 2. Article and section numbers move between code cycles, so confirm them against the adopted edition and any local amendments before you cite them.
The bend factors themselves, the deducts, multipliers, and saddle factor, are not code. They are bender geometry and trade math. The deduct comes from the manufacturer and is stamped on the tool, so the manufacturer's instructions for your specific bender are the authority on take-up and gain. The multipliers and the 2.5 saddle factor are standard across the trade and independent of the maker.
For workmanship expectations, NECA installation standards describe what a neat, accurate raceway installation looks like, which is the bar an inspector and a general contractor read your bends against. For which conduit is permitted where and how it is supported, see the wiring methods and conduit types guide; for sizing the raceway so a legal bend is also a good pull, see the conduit fill guide.
Units and terms
Bending has its own vocabulary, and the same shape goes by different names across regions and crews. The terms below are the ones that show up on a layout and in a bender's instructions.
Conduit diameter is the trade size, given in inches for the common raceways, and the bender is sized to match it. Angles are in degrees, read off the bender marks or a level. Stub height, offset depth, and saddle height are all measured in inches, and the take-up, shrink, and multiplier convert between the height you want and the marks you make.
- Stub
- A 90-degree bend that stands a leg up to a box or gear, set from the take-up
- Take-up / deduct
- The length a 90 consumes, subtracted from the stub height to find the mark, stamped on the bender
- Offset
- Two equal-angle bends that step the run over an obstacle and return it parallel
- Multiplier
- The factor by angle that turns offset depth into the distance between the two bends
- Shrink
- The length an offset or saddle loses along the original line, added back before marking
- Saddle
- A three- or four-point bend that jumps the run over something crossing its path
- Gain
- The length a 90 saves by sweeping a radius instead of a sharp corner, subtracted on a measured piece
- Springback
- The few degrees a bend relaxes open when pressure releases, corrected by overbending
Field notes
FAQ
How do you bend a 90-degree stub?
Subtract the bender's take-up from the height you want, mark the conduit that far from the end, set the bender arrow on the mark, and bend to 90 degrees. For a 12 in stub in 1/2 in EMT with a 5 in take-up, mark at 7 in. Overbend slightly for springback.
What is the deduct (take-up) for an EMT bender?
The deduct is the length a 90 consumes, fixed per bender size and stamped on the casting. Typical EMT figures are 5 in for 1/2 in, 6 in for 3/4 in, and 8 in for 1 in. These are common values, so read the number on your own bender and bend a test stub if it is unfamiliar.
What is the offset multiplier for each angle?
The multiplier turns offset depth into the distance between the two bends. A 30-degree offset uses 2, a 45-degree offset uses 1.4 (1.414 exact), a 22.5-degree offset uses 2.6, and a 10-degree offset uses 6. Distance between bends equals offset depth times the multiplier.
How do you bend a three-point saddle?
Bend a 45-degree center bend on the rim notch, then a 22.5-degree bend on each side. Set outer marks at 2.5 in of conduit per inch of obstruction height on each side of the center mark, and add about 3/16 in per inch of height as shrink to the center mark. Keep all three bends in one plane.
How many bends does the NEC allow between pull points?
The NEC caps total bend at the equivalent of four quarter bends, 360 degrees, between pull points such as boxes and conduit bodies, in the article for each raceway like EMT at 358.26. Offsets and saddles count toward the total. Confirm the section against the adopted code edition.
What is conduit shrink and how do I account for it?
Shrink is the length an offset loses along its original line because the pipe travels up and over. It runs about 1/4 in per inch of offset depth at 30 degrees, 3/16 at 22.5, and 3/8 at 45. Add the shrink to your measurement before the offset so a fixed end point still lands right.
Why does my offset come out as a dog-leg?
A dog-leg means the two bends are not in the same plane, almost always because the pipe rolled between bends. The fix is prevention: mark a reference line down the conduit and keep it pointing the same direction through both bends. Once a dog-leg is in metal pipe, you cut it off and re-bend rather than twist it out.
What is springback when bending conduit?
Springback is the few degrees a bend relaxes open when you release handle pressure, because the metal is springy. EMT springs back a degree or two, IMC and rigid more. You correct by overbending slightly past the target so the bend settles on the angle, then check it with a level or angle finder.
Can you bend rigid conduit by hand like EMT?
The geometry and math are the same, but rigid and IMC have thicker walls that resist bending and spring back more. Small sizes bend with a rigid hand shoe, but the effort climbs fast, so most crews use a mechanical or hydraulic bender above the smallest diameters. Keep bends away from threads and couplings.
What is gain on a 90-degree bend?
Gain is the length a 90 saves by sweeping a curved radius instead of meeting in a sharp corner, so the pipe travels a shorter path than the two outside legs measured to the corner suggest. When cutting a piece to fit a fixed dimension between two 90s, subtract the gain so the finished piece is not long.
People also ask
Codes cited in this guide
This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.