Field glossary · measurement
Power factor
Power factor (PF) expresses how much apparent input power supplies real power: a load importing 100 kW at 125 kVA has a PF magnitude of 0.80. At the same kW, improving PF to 0.95 reduces apparent demand to 105.3 kVA. Total PF includes harmonic effects; displacement PF describes the fundamental-frequency relationship. Interpret a displayed minus sign using the meter's convention, because it can identify export or lagging behavior.
Real power divided by apparent power, 0 to 1, low when the load is reactive or distorted
Calculate the kVA that the feeder must carry
Using the real/apparent-power relationship in Fluke's Power Quality Troubleshooting guide, a steady 100 kW import at 0.80 PF requires 125 kVA, while 0.95 PF requires 105.3 kVA. Calculate apparent demand as kVA = kW / PF magnitude, using measurements from the same operating state. Separate peak kW and peak kVA records need not describe the same load.
The comparison releases 19.7 kVA of apparent capacity. That subtraction does not calculate kWh savings: changes in real losses, operating hours, and load determine energy savings. Use the utility's actual reactive-power or power-factor billing quantity when turning the measurement into a savings estimate.
Why a negative power factor can be normal
Schneider Electric's PM2100 manual, revision NHA2779002-12, defines an IEC display convention in which power-factor sign follows real-power direction. Positive kW import produces positive PF; negative kW export produces negative PF.
Schneider's IEEE display convention instead makes lagging, inductive power factor negative and leading, capacitive power factor positive. A motor importing power at 0.85 lagging can therefore display +0.85 under the IEC convention and -0.85 under the IEEE convention without any wiring change. Read kW direction and the meter setting together before treating the minus sign as reversed CT polarity.
On the PM2100, Schneider also identifies the displayed i prefix with inductive or lagging behavior and c with capacitive or leading behavior. Include that indication in a screenshot or exported record. The submetering guide then provides the phase-matching and CT checks when the complete set of readings is inconsistent.
True power factor reveals current the phase angle misses
Fluke's Power Quality Troubleshooting guide distinguishes displacement power factor at the fundamental frequency from total power factor that includes harmonic current. A nearly aligned fundamental voltage and current can coexist with a significantly lower total PF. That is why a drive's favorable displacement figure does not establish the apparent power drawn from the feeder.
For a sinusoidal voltage and a current waveform containing harmonics, the relationship is total PF = displacement PF / sqrt(1 + THDi squared), with THDi expressed as a decimal relative to fundamental current. These conditions matter: a three-phase unbalanced system or materially distorted voltage needs the analyzer's appropriate total-power calculation rather than this reduced relationship.
A 100 A fundamental with 50 A of harmonics
Take a 230 V single-phase load with 100 A fundamental current in phase with the voltage and 50 A RMS of combined harmonic current. Total RMS current is sqrt(100 squared + 50 squared) = 111.8 A. Real power is 23.0 kW, apparent power is 25.71 kVA, and total power factor is 0.894 despite a displacement power factor of 1.00.
The additional current explains why the harmonic assessment matters alongside the power-factor reading. A correction decision made from the displacement value alone misses the distortion contribution.
Distinctions
- Efficiency
- Efficiency compares useful output with real input power. Power factor compares real input with apparent input; the two ratios have different denominators.
- Insulation power factor
- An insulation test uses dielectric loss to characterize insulation condition. Do not apply a facility-load PF target to that test result.
Frequently asked questions
Can I average the three phase power factors?
An arithmetic average does not generally produce total system power factor. Use total real power and the analyzer's apparent-power calculation for the actual wiring and load balance.
Is a low power factor always a billing penalty?
The utility rate determines the billing consequence. Use the measured quantity and interval named in that rate, then follow the correction guide for the equipment decision.
Sources checked
Also defined as
- Datacenter: Real power divided by apparent power; a low value at the meter can earn a utility penalty
- The ratio of real power to apparent power; included in the three-phase power formula