Seal class (A/B/C)

Read SMACNA's seal classes as an expanding scope of work: C covers connections across the duct run, B extends sealing to lengthwise seams, and A includes applicable duct-wall openings as well. Those locations drive sealing labor and material quantities. The letter does not set a leakage allowance; an acceptance test still needs a specified leakage criterion, test pressure, and physical boundary.

What must be sealed: A is everything, B is joints and seams, C is transverse joints only

Used across 2 Anvilfield field guides, most in HVAC.
Updated

Count sealing footage before pricing Class A, B, or C

Applying SMACNA's sealing-location definitions, a 4 ft rectangular section measuring 24 by 12 inches has a 6 ft perimeter and 12 ft around its two end connections. If fabricated from two L-shaped pieces, its two lengthwise seams total another 8 ft. Count each shared connection only once when extending the takeoff across a complete run.

With two applicable control-rod openings in this section, Class A adds those two sealing locations to the 20 ft of connection and seam work. Class B has the same 20 ft here; Class C has 12 ft. The quantities below describe this section's geometry, not a leakage allowance.

Work on this sectionClass CClass BClass A
Around two end connections12 ft12 ft12 ft
Along two lengthwise seamsNot in this class's scope8 ft8 ft
At two control-rod openingsNot in this class's scopeNot in this class's scope2 locations

Resolve the exceptions hidden by “seal everything”

SMACNA's duct-leakage presentation exempts spiral or helical seams from its longitudinal-seam sealing requirement. The exception concerns that seam construction; it does not exempt the round duct's transverse connections or other applicable sealing locations. A round fitting joined to the spiral run still needs its own joint treatment.

The same SMACNA presentation states that screws and other fasteners are not duct-wall penetrations for the purpose of Seal Class A. It also notes that sealing screws can still be necessary to pass leakage testing. The construction classification and measured performance are separate checks, so an exempt fastener is not permission to ignore an identified leak.

Include connection frames in the walkdown

SMACNA includes access-door and access-panel frames among transverse joints. Inspect the frame-to-duct connection as well as the door's gasketed closure. Sealing one interface does not establish that the other is complete.

Branch intersections, collar tap-ins, duct connections to louvers and terminals, and abutments to building structures also deserve explicit attention in the sealing walkdown. Mark inaccessible connections before concealment. A continuous-looking seal on the easy side of a duct does not establish continuity on the side against a wall or above a tight support.

Use the duct fabrication guide for construction details and the leakage-testing guide for performance verification. Tie each test section to the physical joints and components included in its boundary rather than assigning a result to an entire system by name.

Identify which SMACNA publication the specification uses

SMACNA's product guide identifies HVAC Duct Construction Standards, Metal and Flexible, as the fourth edition published in 2020. It separately lists the HVAC Air Duct Leakage Test Manual, second edition, 2012, and the System Air Leakage Test Standard, first edition, 2020. Construction, duct leakage, and whole-system leakage are related but different document scopes.

Record the specified edition and test boundary before calculating an acceptance allowance. A test including terminal units, access doors, dampers, and equipment contains leakage paths beyond bare duct seams. The component allowances and system method need to match that boundary; applying a duct-only allowance to an undefined assembly invites an argument after the test.

A submittal that states only 'Seal Class A' therefore leaves the acceptance method incomplete. It should also identify the applicable pressure and leakage requirements and the portions of the installation to be tested.

Distinctions

Leakage class
Leakage class expresses leakage performance on its defined pressure and surface-area basis. Seal class describes the required sealing locations.
Pressure class
Pressure class governs duct construction for its specified pressure duty; it does not replace either sealing scope or leakage acceptance.

Frequently asked questions

Does a passing leakage test excuse omitted required sealing?

No. A specified construction requirement and a specified test result are separate obligations. Document compliance with both rather than using one as a substitute for the other.