Field glossary · component
Transverse joint
At a duct transverse joint, the end-to-end connector must satisfy both the structural schedule and the sealing detail. Inspect those as separate requirements: gasket continuity does not establish reinforcement capacity, and correct metal thickness does not establish airtightness. Identify the flange system before checking corner pieces, gasket width, overlap and cleats. A permanent joint and a fire-damper breakaway connection can require different assembly details on similar-looking flanges.
The connection between duct sections, perpendicular to airflow, such as slip-and-drive or a TDC flange
Identify the connector before inspecting its seal
SMACNA’s current HVAC Duct Construction Standards, Metal and Flexible, is the fourth edition, published in 2020. Put the specified joint designation beside duct width, height, metal thickness, pressure class and reinforcement spacing on the inspection sheet. The dimensional schedule identifies the construction to verify; the connector manufacturer supplies the proprietary assembly detail.
ASHRAE’s 2024 HVAC Systems and Equipment handbook explains that transverse joints and intermediate members can reinforce a duct. Joint spacing therefore affects structural construction as well as the number of leak paths. Replacing a connector with another flange of similar appearance does not establish equivalent reinforcement.
Corners and gasket joints deserve separate checks
Ductmate’s 25/35/45 instructions specify 5/8-inch 440 gasket for systems 25 and 35, and 1-inch gasket for system 45. The gasket width is a system-specific assembly requirement. It should appear on the inspection sheet beside the connector identity, not as a generic instruction for every flanged joint.
For its permanent 440-gasket connection, Ductmate calls for approximately 3/8-inch overlap where the gasket ends meet. Its corner detail carries the gasket across the duct edge and corner sealing points. A clean-looking straight flange face does not show whether those corner paths were covered.
A 24 by 18 inch rectangular duct has an 84 inch nominal girth. That is not the exact gasket cut length: the assembled flange dimensions, overlap and corner routing also affect the sealing path. Measure that path on the actual connector rather than cutting an 84 inch strip from the duct schedule.
Keep removable and breakaway details identifiable
Ductmate’s published fire-damper breakaway detail uses neoprene gasket and PVC cleats and excludes bolts and no-bolt corner clips. Its removable-duct detail, on the same instruction sheet, calls for corner bolts. Keep the selected connection detail with the damper’s listed installation instructions; hardware that makes a removable joint secure can defeat the specified breakaway arrangement.
Photograph the corners and gasket before closure, then retain the applicable connector detail with the duct fabrication record. Leakage acceptance belongs to the specified duct pressure test; appearance alone cannot establish a leakage result.
Distinctions
- Longitudinal seam
- A shell seam such as a Pittsburgh lock is fabricated along an individual duct section. Counting end connections for gasket procurement will not include that seam’s sealing work; carry seam footage and transverse-connection counts separately.
- Pavement transverse joint
- At an asphalt tie-in, the relevant acceptance checks concern mat density and surface smoothness. A duct connector designation or gasket width supplies neither. Keep the paving detail and its test records under the roadway scope.
Frequently asked questions
Are TDC and an attached flange connector the same assembly?
No. A formed duct-edge flange and a separately attached connector use their own corner and fastening details. Identify the installed system before borrowing instructions from another flange type.
Sources checked
Also defined as
- Paving: The seam across the mat where a paving run starts or stops, or meets existing pavement
- Datacenter: The connection between two duct sections, the place leakage concentrates most