Field glossary · equipment
VRF / VRV
VRF (variable refrigerant flow) names a system category; Daikin uses the VRV (variable refrigerant volume) trademark for its products in that category. Multiple room units share outdoor refrigeration capacity, so their combined nameplates can exceed the output available at one time. Daikin's R-32 VRV-S AURORA series permits a 50% to 130% connected-capacity ratio. Simultaneous heating and cooling is a separate architecture choice determined by the refrigerant-control components.
Variable refrigerant flow / variable refrigerant volume, the same modulating multi-split technology under different trademarks
What a 130% connection ratio actually means
Daikin's May 2025 R-32 VRV-S AURORA product sheet specifies a connectable indoor-unit ratio of 50% to 130% for that series. Connection ratio compares the sum of indoor capacity indices with the outdoor capacity index. A 130% connection ratio accommodates diversity among room loads; available simultaneous output comes from the corrected outdoor-unit selection.
Daikin lists the RXLA48AAVJU outdoor unit at 48,000 Btu/h nominal cooling capacity. Connected indoor units totaling 60,000 Btu/h produce a 125% nominal connection ratio: 60,000 / 48,000 × 100. That falls inside the published ratio band; approval of the indoor combination and available capacity at design temperatures and piping conditions remain separate selection checks.
Two refrigerant pipes can still serve heat recovery
Mitsubishi Electric's CITY MULTI R2 Main Branch Circuit Controller uses a two-pipe refrigerant network to provide simultaneous heating and cooling. Its liquid-gas separation and branch controls direct the required refrigerant phase to the connected zones.
Read the outdoor model, branch-controller model and approved piping schematic as one assembly. The R2 controller's phase-separation function is the distinction that a simple pipe count misses. Put its model number in the VRF commissioning record so a later mode complaint can be traced to the equipment actually serving the room.
Which equipment combination does the efficiency rating cover?
AHRI 1230-2023 covers electrically operated VRF multi-split systems; its scope includes air-source systems with cooling capacities of at least 65,000 Btu/h and water-source VRF systems of any cooling capacity. AHRI explicitly excludes separate indoor or condensing-unit assemblies from this system-rating standard. The efficiency rating belongs to the tested system combination.
Match the submitted rating to the outdoor combination, indoor equipment and applicable test standard. Attach the listed indoor/outdoor combination to its rating on the submittal. The HVAC system selection guide compares distribution choices; the certification record resolves which complete combination supports a particular published performance figure.
Refrigerant generation determines replacement compatibility
Daikin's May 2025 VRV-S AURORA sheet states that its R-32 outdoor heat pumps require R-32 indoor units and are incompatible with R-410A indoor units. Model compatibility takes priority over cabinet style, pipe diameter or the VRV name.
For a partial replacement, schedule each retained indoor unit and branch component against the proposed outdoor model and refrigerant. Daikin's sheet separately permits larger existing refrigerant pipes to be reused through a field setting; that pipe allowance does not extend its compatibility statement to R-410A indoor units. Record pipe reuse and equipment reuse as separate selections.
Distinctions
- Independent zones versus independent circuits
- Room-by-room control can coexist with a shared refrigerant circuit and outdoor capacity. Circuit drawings identify which rooms share the equipment affected by a repair or shutdown.
Frequently asked questions
Can I apply the same connection-ratio limit to every VRF family?
Each product family defines its approved indoor combinations and connection-ratio limits. The cited 50% to 130% range belongs to Daikin's R-32 VRV-S AURORA series; another series has its own approved combinations and limits.
Sources checked
- Daikin Global: VRV history and trademark ownership
- Daikin R-32 VRV-S AURORA product sheet, PF-VRV-S-Aurora, May 2025: connection ratio and indoor-unit compatibility
- Mitsubishi Electric CMB-M-MA-SV Main BC Controller: R2 two-pipe simultaneous heating and cooling
- AHRI 1230-2023 (I-P): VRF multi-split system-rating scope and exclusions
Also defined as
- Variable refrigerant flow, one outdoor unit feeding many indoor units, often with heat recovery