Field glossary · measurement
Ton
Tonnage on an HVAC submittal identifies nominal equipment size or reports heat-removal capacity. Carrier's 12.5-ton 38AXZ14/40RLA14 match is rated at 135,000 Btu/h, equivalent to 11.25 refrigeration tons, under its published conditions. NIST's 12,000 Btu/h-per-ton conversion translates the output; it does not turn the nominal size into a guaranteed rating. Keep thermal capacity, electrical input and shipping mass in separate columns: a short ton means 2,000 lb.
12,000 BTU per hour of cooling, the unit of plant and chiller capacity
Nominal tons versus the published net rating
Carrier lists its 38AXZ14/40RLA14 combination as 12.5 nominal tons with 135,000 Btu/h of net cooling, equivalent to 11.25 refrigeration tons. The nominal label corresponds to 150,000 Btu/h by unit conversion, so the published net output is 10 percent below that label's arithmetic equivalent.
Carrier publishes those cooling ratings at 80°F indoor dry-bulb, 67°F indoor wet-bulb and 95°F outdoor dry-bulb. The rating belongs to the named indoor-outdoor combination at those conditions. A replacement outdoor unit with the same nominal size does not establish the capacity of a different indoor match.
Against a 140,000 Btu/h total-capacity requirement at those rating conditions, the listed combination falls short by 5,000 Btu/h. Reading only 12.5 tons would suggest 10,000 Btu/h to spare. This reversal is why the submittal needs the actual net result alongside the size designation, after the system type has been selected.
| Carrier schedule field | Value | What it describes |
|---|---|---|
| Nominal capacity | 12.5 tons | Equipment size designation |
| Net cooling capacity | 135 MBH = 11.25 refrigeration tons | Heat-removal rate at the listed conditions |
| Total power | 12.3 kW | Electrical input at the listed conditions |
Read the capacity column before comparing two selections
Normalize the units first, then compare the conditions and equipment boundaries. A schedule in MBH uses thousands of Btu/h: 135 MBH becomes 135,000 Btu/h and then 11.25 tons. Preserve the manufacturer's net or gross label when transcribing it. Removing that label makes unlike capacities look interchangeable.
The sensible-capacity requirement also needs its own check. A total-capacity figure does not state how much of the output removes moisture and how much lowers air temperature. Retain selected airflow, entering-air conditions and the sensible result wherever the load calculation distinguishes them. Tonnage is only one field in a complete equipment selection.
For a chilled-water schedule, record the selected water temperatures and flows beside the capacity. The chiller commissioning guide addresses proving that selection in operation; the ton-of-refrigeration entry explains how measurement bias changes the delivered result.
A cooling ton cannot supply a rigging weight
NIST SP 1038 defines a short ton as 2,000 lb, a metric tonne as 1,000 kg, and a refrigeration ton as a heat-transfer rate of 12,000 Btu/h. A purchase order saying only tons leaves the physical quantity unresolved when it moves between HVAC, transport and structural work.
Request the equipment's published shipping or operating weight for the appropriate task. A cooling-size designation contains no mass information. In a shared schedule, spell out refrigeration tons for capacity and short tons or kilograms for weight; attach fluid-filled operating weight where that is the load the structure will carry.
Distinctions
- Nominal capacity
- A size designation used to identify the product. The matched equipment's performance data supplies the net output at the selected conditions.
Frequently asked questions
Does a larger model number always mean more tons?
Read the manufacturer's nomenclature and rating together. Carrier's 38AXZ14/40RLA14 designation is listed at 12.5 nominal tons; the digits 14 are not a direct tonnage conversion.
Can I convert cooling tons directly into electrical kilowatts?
Use the published electrical-input column. Carrier lists 12.3 kW total power for the 135,000 Btu/h match above. Using NIST's conversion, its cooling output is about 39.56 thermal kW, so the output-to-input ratio is about 3.22 at those rating conditions. Thermal kilowatts and electrical kilowatts describe different sides of that ratio.
Sources checked
Also defined as
- 12,000 BTU per hour of heating or cooling capacity