Approach

Approach is a temperature gap whose reference points depend on the equipment: a tower delivering 85°F water into 78°F entering-air wet-bulb conditions has a 7°F approach. On a water-cooled chiller, 95°F saturated condensing refrigerant and 90°F leaving condenser water give a 5°F approach. Write the two readings beside the result; the same word describes different comparisons, and the maintenance limit belongs to the particular machine and operating conditions.

The difference between condensing refrigerant temperature and leaving condenser-water temperature; a rising condenser approach points to fouling or non-condensables

Used across 9 Anvilfield field guides, most in HVAC.
Updated

Read a 4°F maintenance allowance correctly

YORK's YMC2 Model A Operations Guide, Form 160.78-O1, April 2025, limits the increase in condenser approach to 4°F above the recorded new-unit difference. Apply the 4°F allowance to the increase from the startup baseline. The guide also identifies the displayed condenser saturation temperature as a calculation from the condenser pressure transducer.

A clean recorded approach of 2.5°F and a later reading of 7.0°F represent a 4.5°F increase, exceeding that YORK allowance by 0.5°F. Match load and water flow to the original readings before applying this comparison. Add those conditions to the chiller startup record so the next inspection has a usable reference.

Why a tower rating contains three temperatures

The 2024 ASHRAE Handbook, HVAC Systems and Equipment, defines a nominal cooling-tower ton at 3 gpm cooled from 95°F to 85°F with 78°F entering wet-bulb. Applied to that rating point, the two subtractions describe different parts of tower operation.

SPX Cooling Technologies' thermal paper TR-016, issued April 2016, explains that measurement errors become especially significant when testing approaches below 5°F. A specification for a close approach therefore needs a measurement arrangement as carefully selected as the tower. Preserve the manufacturer's selection with the tower commissioning results, including the entering-air measurement locations.

Quantity at the ASHRAE rating pointCalculationWhat it describes
Water range95°F - 85°F = 10°FCooling of the circulating water during one pass
Tower approach85°F - 78°F = 7°FGap remaining between cold water and entering-air wet-bulb

Separate inlet-air conditions from weather-station readings

Measure the air the tower actually receives. With 85°F cold water, an inlet wet-bulb of 80°F gives a 5°F approach. Substituting a remote weather-station wet-bulb of 78°F produces 7°F. The full 2°F shift comes from the reference location alone.

Record remote ambient and tower-inlet wet-bulb separately when discharge recirculation is suspected. The first describes the surrounding weather; the second belongs in the tower approach calculation. This distinction separates an air-path problem from the tower's thermal response to the air entering it.

Carry temperature differences through the controls correctly

NIST Special Publication 811 distinguishes temperature conversion from temperature-interval conversion. A 7°F interval equals approximately 3.9°C. Apply the 5/9 scale factor without subtracting 32, which belongs to conversion of an absolute Fahrenheit reading. A controls trend should retain the two original temperatures alongside the calculated interval so a swapped point, changed unit or sensor offset remains visible.

For condenser approach calculated as refrigerant saturation temperature minus leaving-water temperature, a water sensor reading 0.5°F high makes the result 0.5°F low. Thus a sensor offset can mimic the improvement expected after cleaning. Compare the transmitter and reference instrument at the same location, then retain both readings with the calculated approach.

Distinctions

Subcooling
For saturated refrigerant at 95°F, liquid refrigerant at 92°F and leaving condenser water at 90°F, subcooling is 3°F while condenser approach is 5°F. Recording the liquid-line reading separately prevents substitution of one measurement for the other.

Frequently asked questions

Why did approach fall when the building load dropped?

SPX TR-016 identifies heat load, tower size and airflow as governing variables. At reduced heat rejection, the tower can deliver water closer to entering wet-bulb without any cleaning or repair. Compare that point with the manufacturer's performance curve at the recorded flow and load.

Sources checked

Also defined as

  • Datacenter: How close the tower can bring the water to the outdoor wet-bulb; sets the waterside free-cooling threshold
  • Datacenter: The gap between the temperature a unit produces and the ambient wet-bulb