ANVILFIELD Try FieldOS

Datacenter

Data center free cooling and economizer field guide

Using the outdoor air and water to cool the hall without the compressor: airside and waterside economizers, partial and full free cooling, the changeover, and the commissioning that proves changeover and capacity.

Free CoolingEconomizerASHRAE 90.4Waterside EconomizerData Center

Direct answer

Free cooling uses outdoor conditions to reduce or stop compressor cooling while fans and pumps continue operating. DOE’s July 2024 Best Practices Guide identifies waterside economizers as best suited to climates with wet-bulb temperatures below 55 F for at least 3,000 hours per year and chilled-water loops designed for 50 F or warmer supply. Actual full and partial cooling hours depend on load, tower and heat-exchanger performance, and the supply setpoint. Commissioning proves changeover behavior with logged triggers and verifies thermal capacity from measured conditions.

On this pageFree cooling, and what it actually isWhy does free cooling matter for PUE?The airside economizerHow does a waterside economizer work?Partial, full, and integrated free coolingAdiabatic and evaporative free coolingIndirect evaporative and the air-to-air heat exchangerHow does the ASHRAE envelope enable more free cooling?Climate, bin data, and free-cooling hoursControls and the economizer changeoverContamination, corrosive gas, and filtrationHumidity, dew point, and free coolingCommissioning the economizerChangeover transient test record: measured or simulated?High-density AI loads and warm-water free coolingThe energy code and the economizer requirementWhat the owner has to maintainWorked example: enable deadband and fallbackWhat to documentCommon mistakesField checklistStandards and referencesUnits, terms, and acronyms

Key takeaways

  • DOE's July 2024 guide identifies waterside economizers as best suited to at least 3,000 annual hours below 55°F wet-bulb and chilled-water supply designed for 50°F or warmer.
  • Airside economizers admit filtered outdoor air, while waterside economizers use a tower and heat exchanger to reduce compressor work during partial cooling and stop it during full cooling.
  • Partial waterside free cooling starts when the heat exchanger can cool return water, while full cooling requires meeting the supply setpoint and load after tower and heat-exchanger approaches.
  • Compare complete plant energy for series and parallel arrangements, since Trane's Engineers Newsletter 45-2 shows that added fan and pump energy can outweigh compressor savings during integrated operation.
  • Commission economizer changeover under load with measured weather recorded separately from simulated triggers, and establish test-point capacity from measured flow, temperatures and load.

Free cooling, and what it actually is

Free cooling is using cool outdoor air or water to remove the heat a data center makes, so the chiller's compressor runs less or not at all. The compressor is the part that costs the money. Take it out of the loop for the hours the weather allows, and the cooling energy drops hard, which is the whole point. Nothing about it is actually free. You still run fans, pumps, and tower water, and you still bought the economizer hardware.

What you stop paying for is the lift, the work the compressor does to pump heat from a cold space out to a warmer outside. When the outside is already cold, that work is wasted, and free cooling is the design that refuses to pay for it.

The device that makes it happen is an economizer, and there are two families. An airside economizer brings cool outdoor air into the hall or the air handler. A waterside economizer makes cold water with the cooling tower and hands the cooling to the chilled-water loop through a heat exchanger, reducing or stopping compressor cooling. The cooling pillar guide covers how the heat leaves the building in general; this guide is about the hours you get to do it without the compressor.

The input that decides how much you save is climate. A hall in a cool, dry climate can run free cooling most of the year. The same design in a hot, humid one gets a fraction of the hours. That is why siting and the free-cooling hours go into the business case before the first chiller is sized.

Why does free cooling matter for PUE?

Cooling is the biggest non-IT load in a data center, so cutting cooling energy is the fastest way to move PUE. PUE is total facility energy divided by the energy that reaches the IT gear, and in an older hall the cooling plant, fans, pumps, and heat rejection can eat nearly as much power as the servers. Drive that down and the ratio follows.

Free cooling goes after the largest single piece of that overhead, the compressor lift. A chiller spends most of its energy pumping heat uphill against the temperature difference between the chilled water and the outside. Run the tower or the outdoor air instead and that lift falls toward zero for those hours. A plant that free-cools a large share of the year holds an annualized PUE well below what the same plant on full mechanical cooling could ever reach.

The number that matters is annualized, not the reading on a cold day. A design can post a great instantaneous PUE in February and a poor one in August, and the operating cost is the weighted average across the year. The PUE field guide treats PUE as the operational scorecard. Here the point is narrower. Free-cooling hours are the input that drives the annual number, and they are set by the climate and the supply temperature you can hold.

The airside economizer

An airside economizer brings filtered outdoor air into the data center, either straight into the hall or through the air handler, and exhausts the hot return instead of recirculating and re-cooling it. When the outdoor air is cool enough, the dampers open, the outdoor air does the cooling, and the mechanical refrigeration backs off or shuts down. That is economizer mode. EPA ENERGY STAR’s airside economizer guidance describes mixing warm return air with very cold outdoor air to keep the delivered air within the equipment’s temperature and humidity limits.

The hardware is dampers and controls more than anything exotic: an outdoor-air damper, a return-air damper, a relief or exhaust path, the filter bank, and the actuators and sensors that decide when to open them and how far. A direct airside economizer dumps the outdoor air into the space. An indirect one keeps the outdoor air separate and moves the heat across a heat exchanger, which gets its own section below.

The trade-offs are filtration, humidity, and contamination, and they are real, not footnotes. Outdoor air carries particulate and, depending on the site, corrosive gases, salt near the coast, and smoke during fire season, so the filter bank steps up from what a recirculating room needs. Outdoor air also brings its own moisture, so the control has to watch dew point, not just temperature, or it will swing the hall's humidity around. Get the filtration or the humidity logic wrong and the energy you saved comes back as failed hardware or a humidity excursion. The contamination and humidity sections cover what the design has to handle.

How does a waterside economizer work?

A waterside economizer makes cold water with the cooling tower in cold weather and transfers that cooling to the chilled-water loop through a plate-and-frame heat exchanger, reducing compressor work during partial cooling and stopping it during full cooling. The tower rejects heat to the outdoors the way it always does, but when the outdoor wet-bulb is low enough, the condenser water comes off the tower cold enough to cool the chilled-water side directly. The plate-and-frame heat exchanger is the bridge: condenser water on one side, chilled water on the other, heat crossing the plates without the two streams mixing. EPA ENERGY STAR’s waterside economizer guidance shows the separate water loops and chiller bypass.

SPX Cooling Technologies defines tower approach as leaving cold-water temperature minus entering-air wet-bulb temperature. The tower responds to outdoor wet-bulb, but the enable decision also needs the tower approach, heat-exchanger approach, flow and load. Trane’s Engineers Newsletter 45-2 (2016) explains that tower approach changes with load and wet-bulb.

For full free cooling, add the tower and heat-exchanger approaches to outdoor wet-bulb and compare the resulting water temperature with the supply setpoint; partial cooling becomes useful when the heat exchanger can cool the return water. Warmer chilled-water setpoints push that threshold higher and buy more hours.

The chiller does not get removed; it gets bypassed. Valves route the chilled water through the heat exchanger instead of, or in series with, the evaporator, the compressor unloads in partial mode or stops in full mode, and the pumps and tower fans carry the load. That is where most of the savings live, because on a chilled-water plant the compressor is the largest energy user by a wide margin. The chilled-water hydro guide covers proving that loop holds before any of this runs; the economizer rides on the same piping.

Partial, full, and integrated free cooling

Free cooling is not a single switch. As the outdoor conditions cool, a well-designed plant moves through three states. In full mechanical cooling the chiller carries everything and the economizer is off. In partial free cooling the economizer pre-cools the return water and the chiller finishes the job at part load, unloading its compressor as the outdoor conditions improve. In full free cooling the economizer carries the whole load and the compressor is off entirely.

Series piping lets the economizer pre-cool return water before the chiller trims it to the supply setpoint, as DOE’s July 2024 Best Practices Guide describes. A non-integrated parallel arrangement transfers the load to the economizer when it can meet the required supply temperature and load. Count both partial and full modes, then compare total plant energy: Trane’s Engineers Newsletter 45-2 (2016) shows that added fan and pump energy can outweigh compressor savings during integrated operation.

This is what integrated economizer means: the economizer and the chiller working at the same time, not one or the other. The selected arrangement and sequence determine whether partial cooling reduces total plant power. The control has to hand off smoothly, which is the changeover, and a bad changeover that lets the economizer and the chiller fight each other burns more than it saves. The controls section covers that handoff.

Adiabatic and evaporative free cooling

Evaporative cooling extends the free-cooling hours by using water to drop the air temperature, and it earns its keep in dry climates where the air has room to take on moisture. Spray or wet-media evaporation cools the air as the water evaporates, so a hall that would otherwise need the chiller on a warm, dry afternoon can stay on free cooling because the evaporative stage knocks the supply air back down. Adiabatic cooling is the same idea used as a pre-cool: wet the incoming air or the heat-exchanger surface, drop its temperature toward the wet-bulb, and stretch the economizer hours past where dry free cooling alone would quit.

Direct evaporative adds the moisture straight to the supply air going to the hall, which cools it but raises its humidity, so it suits dry climates and has to watch the dew point it delivers. Indirect evaporative wets the outdoor side of a heat exchanger instead, cooling the hall air without adding moisture to it, which is the next section.

The cost is water, and it shows up in WUE, water usage effectiveness, the water used per kWh of IT energy. Evaporative free cooling trades electricity for water, and in a water-stressed region that trade is not automatically a win. Adiabatic pre-cooling, run only when it is needed rather than continuously, can hold most of the energy benefit while cutting the water draw sharply against full-time evaporation. The design has to weigh PUE against WUE for the actual site, because the cheapest answer on energy can be the worst on water.

Indirect evaporative and the air-to-air heat exchanger

Indirect evaporative cooling gets the benefit of outdoor air without letting that air into the white space, which is the contamination answer. Two airstreams pass on opposite sides of a heat exchanger, an air-to-air core or a heat wheel, so the hall's own air is cooled by the outdoor air across a wall it never crosses. The data center air recirculates in a closed loop; the outdoor air, with its dust, salt, and corrosive gases, stays on the other side and gets exhausted.

Add water to the outdoor side and the system goes from dry indirect to indirect evaporative: a thin film of water sprayed on the outdoor side of the core evaporates, pulls the surface temperature down toward the wet-bulb, and lets the core reject more heat from the hall air. The hall air still never touches the water or the outdoor air. That is the appeal for a dirty or coastal site, where a direct economizer would pull contamination into the room. You get a large share of the free-cooling benefit with the white space sealed.

The price is a heat exchanger between the two streams, which costs some efficiency against direct outdoor air, plus the water for the evaporative stage and its treatment. For a clean inland site a direct economizer can be simpler and cheaper. For a site with bad outdoor air, indirect is often the only economizer worth running, because the alternative is filtering and scrubbing the entire outdoor airflow.

How does the ASHRAE envelope enable more free cooling?

The wider the temperature and humidity the IT gear is allowed to see, the more hours the outdoor air or water can carry the load, so the ASHRAE envelope sets the free-cooling ceiling. ASHRAE TC 9.9’s 2021 Thermal Guidelines, reproduced in DOE’s July 2024 Best Practices Guide, give a recommended server-inlet temperature range of 18 to 27 C for classes A1 through A4.

The allowable envelopes are wider and depend on equipment class. A warmer operating setpoint increases the economizer window within the installed equipment’s limits.

The reason is direct. Free cooling works whenever the outdoor condition is cooler than what you need to deliver. Raise the chilled-water setpoint or the allowable server-inlet temperature and you have lowered the bar the outdoor air or wet-bulb has to clear, so more of the year qualifies. The expansion of the allowable envelopes to A3 and A4 in earlier editions was aimed squarely at this, opening near full-time economizer operation across much of the world's climate. The thermal values referenced here are from the 2021 guidance reproduced by DOE.

The trap is treating the wider envelope as free margin. Running warmer cuts your thermal ride-through when a chiller drops, because the hall starts closer to the limit and heats up faster. The cooling pillar guide covers the envelope and the ride-through gap in depth. The economizer point is narrower: confirm the actual equipment class and the edition the design referenced, then set the warmest supply the gear and the warranty allow, because that setting is what buys the hours.

Climate, bin data, and free-cooling hours

Hourly weather data retains the time order of outdoor conditions; bin data groups observations into temperature ranges and counts their hours. NREL’s Users Manual for TMY3 Data Sets, revised May 2008, describes a typical meteorological year assembled from selected historical months. Record whether the calculation uses that typical year or an actual measured year.

Use hourly data when modeling dwell times, changeovers and fallback, and use bins for a first availability comparison. DOE’s July 2024 Best Practices Guide uses at least 3,000 annual hours below 55 F wet-bulb as a waterside suitability screen; the plant’s full free-cooling hours come from its load, approaches and supply setpoint.

Wet-bulb drives the count for any evaporative or tower path, dry-bulb for a direct dry economizer, so the right bin data depends on the cooling type. A waterside or evaporative design lives on the wet-bulb bins, which is why a dry desert with high dry-bulb but low wet-bulb can still free-cool well, and a humid coast with moderate dry-bulb but high wet-bulb does worse than the thermometer suggests.

This is why siting decides so much before any equipment is picked. The same plant earns a different PUE in two cities, and the difference is the free-cooling hours the climate hands it. Run the bin analysis for the actual site and the actual supply temperature, not a generic map, because the hours are what the whole economizer investment is justified against.

Use Calculate data center free-cooling hours from an hourly weather file for weather provenance, hourly inclusion rules and approach sensitivity. Keep those calculated annual hours separate from the operating hours measured by the building automation system. This guide records the changeover test and the as-left controls that feed that calculation.

Controls and the economizer changeover

The economizer is only as good as the control that decides when to switch it on, and the decision rides on outdoor conditions. The changeover is the point where the plant moves between mechanical cooling, partial free cooling, and full free cooling. Set it badly and you either leave free-cooling hours unused or you let the economizer and the chiller fight each other across the boundary.

There are three common control strategies for an airside economizer, and they differ in how honestly they read the outdoor air. Dry-bulb control switches on outdoor temperature alone, which is simple and works in a dry climate where humidity is rarely the problem. Enthalpy control reads the total heat content of the air, temperature and humidity together, so it does not open the dampers to air that is cool but so humid it would cost more to dehumidify than it saves. Differential or comparative control compares the outdoor air to the return air directly and economizes only when the outdoor air is genuinely better. Enthalpy and differential beat fixed dry-bulb in humid climates; dry-bulb is fine where the air stays dry. On a waterside plant, compare predicted economizer leaving-water temperature with return water to enable partial cooling, and use measured supply temperature and available capacity to manage chiller staging.

The failure that wastes the most money is the economizer and the chiller working against each other. A clean control unloads the compressor as the economizer picks up load and holds a stable handoff with enough deadband that the plant is not hunting across the changeover every few minutes. No fighting the chiller. That handoff is a commissioning item, not just a design intent, and it is the first thing to put under load and watch.

Contamination, corrosive gas, and filtration

A direct airside economizer brings the outdoor air's contamination indoors with the cooling, so the filtration steps up from what a sealed, recirculating hall needs. The two threats are particulate and gas. Fine particulate fouls boards and connectors and bridges contacts. Corrosive gases attack the copper and silver in the electronics and drive creep corrosion that kills hardware over months, not minutes.

DOE’s July 2024 Best Practices Guide identifies MERV 13 filtration for outside-air economizing. Select particulate filters for the site’s contaminant loading and available fan pressure, and add gas-phase treatment where corrosive gases require it. Particulate filter ratings do not establish gaseous-contaminant removal.

The site decides how hard this is. Near a coast you fight salt. In an industrial corridor or a region with high sulfur air you fight hydrogen sulfide and other corrosive gases. During wildfire season you fight smoke, which can force a direct economizer offline and back onto mechanical cooling for days. High-contamination sites monitor corrosion with copper and silver coupons to track how aggressive the air actually is, and a result past the guideline severity is the signal to add filtration or move to an indirect economizer that keeps the outdoor air out. The contamination-control guide covers contamination as a general envelope concern; the economizer-specific point is that direct outdoor air is the thing that makes it a daily question.

Humidity, dew point, and free cooling

Outdoor air carries its own moisture, so an airside economizer is also a humidity control problem, and the number that governs is dew point, not relative humidity. Pull in cool, damp outdoor air and you can drive the hall's humidity up. Pull in cold, dry winter air and you can drive it down toward the static-discharge risk at the low end. Either way the economizer control has to hold the hall inside the moisture band, which on a wide modern design is a dew-point range with a relative-humidity ceiling.

The expensive mistake is letting the economizer chase temperature while ignoring what it does to moisture. Cold winter outdoor air is bone dry, and free-cooling on it without any humidification can pull the hall below its low dew-point limit, which raises electrostatic-discharge risk on the floor. Damp shoulder-season air can carry the hall up toward condensation if the control is not watching dew point. Condensation tracks dew point, not relative humidity, so a hall held by relative humidity alone can still sweat a cold coil or a cold surface.

The modern answer is to control to a wide dew-point band and let relative humidity float, which is also what saves the energy the old narrow-humidity habit wasted. The humidity-envelope guide covers the moisture limits. For the economizer, the point is that bringing outdoor air in is what makes humidity a live variable instead of a sealed-room setpoint.

Commissioning the economizer

Commissioning the economizer means proving three things under real conditions: that it enters economizer mode at the right outdoor condition, that the changeover between mechanical, partial, and full free cooling is clean, and that the free-cooling capacity is actually there when the plant calls for it. Reading the sequence of operations is not proof. You have to make the plant do it.

Record the actual weather and load separately from any overridden outdoor sensor or adjusted setpoint. A simulated trigger verifies the controller’s decisions and actuator responses; measured water flow, temperatures and load establish the capacity delivered during that test. For design-condition capacity, retain the actual test point and the manufacturer performance calculation used to translate it to design, then schedule seasonal testing for conditions still outstanding.

The keystone is the integrated test, where the cooling plant runs on load banks through utility-loss and failure scenarios. The economizer belongs in that test, because the changeover and the chiller restart interact. A plant in free cooling that loses power has to get the compressors back if the weather turns, and the ride-through has to cover the gap. The cooling pillar and the chilled-water hydro guide cover the broader commissioning sequence; the economizer's piece is the changeover and the free-cooling capacity, proven rather than assumed, with the as-left changeover setpoints recorded for operations.

The California Energy Commission’s 2016 Nonresidential Compliance Manual, Chapter 12 (January 2017) provides a useful test-record structure: prerequisites, instruments, sequence references, instructions, measurable acceptance criteria, actual responses, restoration and deficiencies. Use the approved project sequence to set acceptance limits and recovery times before the test. The record below applies that structure to economizer changeover.

Changeover transient test record: measured or simulated?

Test entry and exit through mechanical, partial and full free cooling under the approved load and available weather. Then test loss of economizer availability and return to automatic control. Log the initiating event and the complete response on a common clock, with a recorded trend interval short enough to resolve valve travel, compressor staging and the temperature peak. Record the approved abort condition and the available alternate cooling before injecting a fault.

Keep independent physical measurements alongside the values presented to the controller when a sensor point is overridden. A wet-bulb override changes the enable calculation; it does not make the tower water colder. Mark each result as a simulated-trigger functional test, a measured-condition capacity test, or a calculated design-condition result.

Anvilfield’s field record below separates command, proof and thermal response. Set the peak-temperature limit, allowable excursion duration and recovery band from the project acceptance criteria, and record their actual values with the test. A commanded valve position or chiller start is complete only when its feedback or operating proof arrives.

Record fieldWhat to enterWhat it establishes
Test identity and starting stateDate, test ID, sequence revision, instruments and trend interval, equipment available, IT/load-bank load, initial mode, chilled-water supply (CHWS) setpointRepeatable starting condition
Measured triggerActual outdoor dry-bulb/wet-bulb and water temperatures with units; independent readings for overridden points; sensor IDs and calibration recordsPhysical conditions during the test
Simulated triggerOverridden point, original value, forced value, start/end time and operator; record setpoint changes separatelyExact stimulus presented to the controller
Event timelineTrigger, mode request, valve commands and feedback, flow proof, compressor start/stop and run proof, tower/pump responseDelay and overlap across the handoff
Thermal transientAcceptance limits and recovery band with units; pre-test CHWS and hottest monitored rack inlet; peaks and timestamps; duration above limit; recovery time to bandMagnitude and duration of the excursion
Capacity evidenceMeasured flow, entering/leaving water temperatures, fluid properties, heat removal and uncertainty; actual load and weatherCapacity delivered at the measured test point
Fallback and interlocksFault injected, alarm timestamp, alternate cooling request and proof, supply-temperature responseCooling recovery and fault handling
Acceptance and closeoutExpected/actual response, pass/fail by criterion, deficiency and retest ID, restored points, as-left settingsTraceable disposition and return to automatic control

High-density AI loads and warm-water free cooling

Warm-water liquid cooling expands the economizer window because the plant can reject heat at a higher water temperature. DOE’s July 2024 Best Practices Guide lists ASHRAE’s W32, W40 and W45 liquid-cooling classes, whose upper supply-water temperatures are 32 C, 40 C and 45 C, respectively. Use the installed equipment’s declared class and coolant requirements to select the supply setpoint, then calculate free-cooling availability from the site weather and heat-rejection performance.

DOE’s July 2024 guide reports high-performance-computing rack densities surpassing 125 kW per compute rack and identifies direct liquid cooling as an early response to those loads. Moving heat into a warm-water loop increases the outdoor-temperature range available for free cooling. The plant still has to meet the rack’s heat load and the heat exchanger’s approach at that water temperature.

The liquid-cooling work, the cold plates, the coolant distribution units, and the loop chemistry, is its own commissioning cluster covered elsewhere. The free-cooling point is that warm-water cooling and free cooling pull in the same direction. The warmer the supply the load tolerates, the more the outdoor conditions can carry it, and AI's appetite for liquid is what makes the warm loop normal.

The energy code and the economizer requirement

ASHRAE Standard 90.4 uses energy-performance targets for data centers; an economizer is one way to meet them. Addendum e to Standard 90.4-2019, approved October 30, 2020 explains in an informative note that Standard 90.4 does not require economizer capacity for a shared system’s data-center portion when it meets the standard’s annual energy-performance targets using the shared-system calculation method. The non-data-center spaces retain their applicable Standard 90.1 obligations.

Record the adopted energy-code edition, the data-center compliance path, climate zone and local amendments in the design basis. Resolve the economizer obligation from that path, rather than treating climate zone alone as a mandate. Calculate the energy benefit using the complete cooling plant, including fans and pumps.

Treat the code as the floor, not the target. Meeting the minimum economizer provision is not the same as designing for the free-cooling hours the site actually offers, and the operating cost rewards going past the code minimum where the climate pays for it.

What the owner has to maintain

An economizer adds moving parts and wetted surfaces that the operations team has to maintain, and a neglected economizer quietly stops saving money. The owner inherits three maintenance items the recirculating-only plant did not have.

Dampers and actuators are first. An airside economizer's outdoor, return, and relief dampers cycle constantly, and a seized actuator or a damper that no longer seals leaves the plant stuck in one mode, either missing free-cooling hours or leaking unconditioned outdoor air into the hall. They get exercised and inspected, not assumed. Filters belong here too: the heavier outdoor-air filtration loads up faster than a sealed room's and has to be changed on a real schedule, or the pressure drop eats the fan energy the economizer was supposed to save.

The heat exchanger and the water side are the second and third. A plate-and-frame economizer heat exchanger fouls on the condenser-water side and loses transfer if the water treatment slips, so the same tower water chemistry, biocide, and cleaning the chilled-water plant needs now also protects the free-cooling capacity. An evaporative or adiabatic stage adds wet media, spray nozzles, and the treatment that keeps scale and biological growth, including Legionella risk, under control. Skip the water treatment and you lose capacity to fouling and inherit a health problem. The free-cooling savings are real, but they are earned every year through the maintenance, not banked once at commissioning.

Worked example: enable deadband and fallback

Lawrence Berkeley National Laboratory’s Buildings library v14.0.0 economizer controller implements ASHRAE Guideline 36-2021, Section 5.20.3. Its published defaults include a 2 K enable offset, a 1 K disable offset, a 1 K hysteresis width, a 1,200-second minimum on/off period and a 120-second disable delay. These are named controller defaults; the test record carries the installed values.

Anvilfield estimates the enable boundaries by subtracting and adding half the LBNL default 1 K hysteresis width to its 2 K enable offset: 1.5 K and 2.5 K. Apply these boundaries to upstream chilled-water return temperature minus predicted economizer leaving-water temperature. LBNL’s v14.0.0 hysteresis block turns the enable condition true above 2.5 K and false below 1.5 K; between the boundaries it retains its previous state. Record that condition separately from the economizer’s actual mode, which also depends on the timers, plant state and disable logic.

For normal loss of useful cooling, Anvilfield estimates the LBNL default disable boundaries from its 1 K disable offset and 1 K hysteresis width. The disable condition becomes true when measured upstream minus downstream water temperature falls below 0.5 K and clears above 1.5 K. The condition must persist for the 120-second delay, and the controller also checks the 1,200-second minimum enabled period. Record both timers and the separate enable condition, because either temperature path can remove the enable request.

Test sensor failure, lost flow and loss of cooling capacity separately from normal temperature disable. Anvilfield’s fallback test uses the approved sequence to request mechanical cooling, prove the required flow and chiller operation, and complete the valve handoff while recording the supply and rack-inlet transient. Match the alarm, abort condition and recovery limits to that sequence; match compressor restart and minimum-flow interlocks to the installed equipment instructions.

Record the as-found and as-left settings, timer states and reason for every mode change. Restore all overrides, confirm valid sensor inputs and automatic operation, and repeat the failing transition after a correction.

Test stepInput or eventExpected record
Enable boundaryCalculated temperature advantage rises above 2.5 K using the LBNL default hysteresisEnable condition becomes true; record remaining minimum off time, plant state and actual start
DeadbandTemperature advantage moves between 1.5 K and 2.5 KPrevious enable-condition state is retained; record actual operating mode separately
Reset boundaryCalculated advantage falls below 1.5 KEnable condition becomes false; log timer state and actual mode response separately
Normal disableMeasured upstream minus downstream water temperature falls below 0.5 K; disable condition clears above 1.5 KRecord the 120-second condition delay, 1,200-second minimum enabled period and actual mode response
Fault fallbackApproved sensor-failure or loss-of-flow testAlarm, mechanical-cooling request/proof, valve response, temperature peak and recovery
Return to serviceValid sensors, restored flow and cleared overridesAutomatic operation and as-left settings verified

What to document

A free-cooling design that was modeled but never documented leaves operations unable to tell whether the plant is hitting its hours or quietly running compressors it should not need. The record is what tells the next engineer how the economizer is supposed to behave and what it was proven to do.

Capture the economizer type and configuration, each operating mode and its measured or calculated trigger, and the changeover setpoints and deadbands as left. Keep calculated annual free-cooling hours with the weather-file basis and BAS-measured operating hours with the observation dates. Retain the measured test-point capacity and the water use for evaporative or adiabatic designs.

Tie the changeover setpoints to the sequence of operations so a future control change does not silently undo the commissioning. If the plant uses evaporative free cooling, record the WUE basis alongside the PUE, because the two trade against each other and the owner needs both to run the site.

What to recordWhy it matters
Economizer type and configurationAirside, waterside, indirect, or evaporative sets everything downstream
Operating mode and changeover triggerDefines when the plant should be free-cooling
Changeover setpoints and deadband, as leftStops a future control change from undoing the commissioning
Calculated annual hours and BAS-measured operating hoursRetain the weather-file and model basis separately from the dated operating record
Free-cooling capacity at the test conditionEstablishes delivered capacity at the recorded weather, flow and load; retain design-condition calculations separately
Water use / WUE for evaporative or adiabaticTracks the water traded for the energy saved

Common mistakes

  • Running no economizer where the climate would have paid for one, wasting free-cooling hours all year.
  • Pulling unfiltered or under-filtered outdoor air into the hall and bringing in particulate and corrosive gas.
  • Letting the economizer and the chiller fight across a changeover with no deadband, so the plant hunts and burns compressors.
  • Controlling an airside economizer on dry-bulb in a humid climate, opening the dampers to cool but damp air.
  • Ignoring dew point, so winter free-cooling air pulls the hall too dry or shoulder-season air drives it toward condensation.
  • Selecting a non-integrated parallel arrangement without comparing its annual plant energy with an integrated series arrangement.
  • Undersizing the plate-and-frame heat exchanger, so the economizer cannot carry the load it was credited with.
  • Running evaporative free cooling without weighing WUE, trading an energy win for a water problem in a stressed region.
  • Skipping the water treatment on the tower, heat exchanger, or evaporative media, losing capacity to fouling and inheriting a Legionella risk.
  • Treating the economizer sequence as proven from the drawings instead of forcing the changeover under load at commissioning.

Field checklist

0 of 12 complete

Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.

Standards and references

The thermal reference used here is ASHRAE TC 9.9’s 2021 guidance, reproduced in DOE’s July 2024 Best Practices Guide. It distinguishes the recommended inlet range from equipment-class allowable envelopes. ASHRAE Standard 90.4 addresses data-center energy performance; the adopted code and compliance path determine the project’s economizer obligation.

Contamination is governed by ASHRAE's gaseous and particulate contamination guidance for data centers, which informs the outdoor-air filtration class and the corrosion monitoring an economizing hall needs. The test-and-balance and functional testing draw on the AABC and NEBB procedures and the ASHRAE commissioning guidance, and where a facility chases a tier, the Uptime Institute Tier standards drive the witnessed redundancy and integrated-test demonstrations. The chilled-water and condenser-water piping a waterside economizer rides on is pressure-tested to the applicable ASME B31 section, which the chilled-water hydro guide covers.

Use the equipment ratings and the approved sequence for project acceptance limits. Retain the cited edition, sensor calibration records, functional test results and any outstanding seasonal tests with the turnover package.

Reviewed by Anvilfield on 2026-11-06. Sources checked with curl on 2026-11-06. Update log: corrected changeover triggers, enable and disable hysteresis, fallback records, test-point capacity wording and shared-system energy-code attribution; linked the separate annual weather-file calculation.

How to cite this page: Anvilfield, Data center free cooling and economizer field guide, 2026, https://anvilfield.com/field-guides/datacenter/data-center-free-cooling-economizer/.

Units, terms, and acronyms

Free cooling carries vocabulary from HVAC, from the central plant, and from data center efficiency, and the same idea reads differently across an energy model, a chiller submittal, and a controls sequence. The terms below travel across the whole economizer scope.

Free cooling
Cooling a data center with cool outdoor air or water so the chiller compressor runs less or not at all
Economizer
The dampers, valves, and heat exchanger that let outdoor conditions carry the cooling load
Airside economizer
An economizer that brings filtered outdoor air into the hall or the air handler
Waterside economizer
An economizer that uses a cooling tower and heat exchanger to reduce or stop chiller compressor cooling
Partial / full free cooling
Partial unloads the chiller while the economizer helps; full carries the whole load with the compressor off
Integrated economizer
Economizer and chiller running at the same time, capturing the partial-cooling hours
Dry-bulb / wet-bulb / enthalpy
The outdoor measurements that trigger changeover; enthalpy includes humidity, wet-bulb drives evaporative systems
PUE
Power usage effectiveness, total facility energy divided by IT energy; free cooling drives it down
WUE
Water usage effectiveness, water used per kWh of IT energy; evaporative free cooling raises it
Adiabatic / evaporative cooling
Using water evaporation to drop air or surface temperature and extend the free-cooling hours
Approach
How close the tower can bring the water to the outdoor wet-bulb; sets the waterside free-cooling threshold

Related tools

Calculators and readiness checks for this work

New towers extend the service territory for waterside economizers. Quarterly monitoring with PorchRocket's Asset Search reports visible additions, removals, and alterations in dated views.

Next step: Map cooling-tower accounts

FAQ

What is free cooling in a data center?

Free cooling uses cool outdoor air or water to remove the heat a data center makes, so the chiller's compressor runs less or not at all. It is not literally free, since fans, pumps, and tower water still run. What you stop paying for is the compressor lift, which is the largest cooling energy cost.

What is a data center economizer?

A data center economizer is the equipment that lets cool outdoor conditions carry the cooling load instead of the chiller compressor. An airside economizer brings filtered outdoor air into the hall; a waterside economizer makes cold water with the cooling tower and a heat exchanger. Both cut energy and PUE when the climate is cool enough.

Airside vs waterside economizer: what is the difference?

An airside economizer brings filtered outdoor air into the hall or air handler and exhausts the hot air, so filtration and humidity matter. A waterside economizer keeps the air sealed and makes cold water with the cooling tower and a plate-and-frame heat exchanger. Airside suits clean climates; waterside avoids pulling outdoor contamination indoors.

How does a waterside economizer work?

A waterside economizer runs the cooling tower in cold weather to make condenser water cold enough to cool the chilled-water loop directly through a plate-and-frame heat exchanger, reducing compressor work during partial cooling and stopping it during full cooling. The two water streams cross the plates without mixing. Partial cooling begins when the heat exchanger can cool the return water; full cooling requires it to meet the supply setpoint and load after tower and heat-exchanger approaches are included.

What is the difference between partial and full free cooling?

In partial free cooling the economizer pre-cools the water and the chiller runs at part load to finish the job, unloading as it gets colder out. In full free cooling the economizer carries the whole load and the compressor is off. Series piping captures partial cooling, but Trane’s Engineers Newsletter 45-2 (2016) shows that total fan, pump and chiller power determines whether that mode saves energy.

How many free-cooling hours can a data center get?

DOE’s July 2024 Best Practices Guide screens waterside suitability at 3,000 or more annual hours below 55 F wet-bulb. Calculate full and partial operating hours from the site weather file, cooling load, supply setpoint and equipment approaches. Raising the chilled-water setpoint widens the window.

Does free cooling require humidity and contamination control?

A direct airside economizer does, because outdoor air brings moisture and contamination indoors. DOE’s July 2024 Best Practices Guide identifies MERV 13 filtration for outside-air economizing; gaseous contamination needs separate treatment, and the control holds the approved moisture envelope. A waterside or indirect economizer sidesteps this by keeping the outdoor air out of the white space.

Is an economizer required by code for data centers?

ASHRAE Addendum e to Standard 90.4-2019 explains in an informative note that Standard 90.4 does not require economizer capacity for the data-center portion of a shared system that meets its annual energy-performance targets using the shared-system calculation method. The adopted compliance path sets the project requirement. Record the code edition, climate zone and local amendments; shared non-data-center spaces retain their separate obligations.

What is indirect evaporative cooling for data centers?

Indirect evaporative cooling passes the hall's air and the outdoor air on opposite sides of an air-to-air heat exchanger, so the outdoor air cools the hall air without ever mixing with it. Spraying water on the outdoor side boosts the cooling. It keeps dust, salt, and corrosive gas out of the white space.

Does free cooling save water or use more?

It depends on the type. A dry airside or dry waterside economizer saves both energy and water, but evaporative and adiabatic free cooling trade electricity for water, which shows up as a higher WUE. In a water-stressed region, weigh PUE against WUE; running adiabatic pre-cooling only when needed cuts the water draw.

People also ask

Codes cited in this guide

This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.

Sources checked