Plumbing
Flushometer and flush valve types field guide for commercial plumbers
What a flushometer is, diaphragm versus piston and manual versus sensor, the water closet and urinal gpf, why the valve must match the fixture, and how to rebuild one that runs or short-flushes.
Direct answer
A flushometer is a valve that delivers a measured, pressurized flush straight from the supply line to a commercial toilet or urinal, with no tank. It uses line pressure for a fast, high-volume flush and recharges in seconds for high-traffic use. It needs adequate flow and pressure, and the valve gpf must match the fixture.
Key takeaways
- A flushometer delivers a measured, pressurized flush straight from the supply line to a commercial toilet or urinal, with no tank.
- Flushometers need a 1 in or 1-1/4 in supply and adequate flowing pressure, often around 20 to 25 psi minimum per the model data sheet.
- The valve gpf must match the fixture's design gpf: water closets commonly 1.6 or 1.28 gpf, urinals 0.5, 0.25, or 0.125 gpf.
- Flush volume is set by the diaphragm or piston kit, not the control stop; the stop only shuts off and trims flow.
- A continuously running flushometer almost always has a fouled bypass orifice (about 0.020 to 0.030 in) or a worn diaphragm or piston.
What a flushometer is and why commercial work uses it
A flushometer is the valve that flushes a commercial toilet or urinal directly off the supply line, with no tank in between. Pull the handle or trip the sensor and the valve opens a path from the pressurized supply straight to the fixture, lets a measured slug of water through, and closes itself. There is no cistern to refill and wait on. That is the whole point of the design.
Because it flushes on line pressure instead of stored water, a flushometer recharges in seconds and is ready for the next person almost immediately. That fast recycle is why you see them in restrooms that take heavy traffic, where a tank toilet would still be filling while the line backs up at the door. The cost of that speed is a demand on the supply. The valve needs real flow and pressure behind it or it will not flush right.
This guide covers the valve, not the fixture it bolts to and not the pipe behind the wall. Which water closet or urinal to choose, and the gpf and gpm limits that decide it, live in the fixtures and water-efficiency guide. The rough-in dimensions, the spud, and the supply stub-out live in the fixture rough-in and setting guide. Read the three together, because the valve, the bowl, and the rough-in are one decision split across three stages of the job.
Flushometer vs tank toilet
The split is simple. A flushometer is the commercial answer and a tank is the residential one. A tank toilet stores a flush worth of water in a cistern, drops it through the bowl by gravity, then takes 30 to 60 seconds to refill from a small supply. A flushometer skips the storage and pulls the flush straight from the line under pressure.
That difference decides where each one belongs. A house flushes a toilet a handful of times a day, so the slow refill never matters and the small 1/2 in supply is fine. A busy public restroom flushes the same fixture hundreds of times a day, and a tank that has to refill between every use cannot keep up. The flushometer's pressurized, fast-recycle flush is built for exactly that load.
The other reason commercial work leans on flushometers is durability and service. There is no fill valve, flapper, or float to fail, and a worn valve is a rebuild kit and 10 minutes, not a new toilet. The tradeoff is the supply demand, which is the next section, and the plain fact that a flushometer will not work at all on a residential-size supply line.
What flow and pressure does a flushometer need?
A flushometer needs adequate flow and pressure at the valve or it will not flush right, and this is the most common reason a new install or a remodel disappoints. The valve flushes on line pressure, so if the pressure sags or the line cannot deliver the flow, you get a weak or short flush no matter how good the valve is.
Manufacturers publish a minimum flowing pressure for each model, and it is the flowing pressure at the valve while it is open, not the static pressure you read at rest. Common figures land around 20 psi for siphon-jet water closets and 25 psi for blowout fixtures and many low-consumption 1.6 gpf models, with a usable operating range often quoted from about 10 to 100 psi. Confirm the number against the specific model's data sheet, because it varies by valve and fixture.
Flow is the other half, and it is why the supply to a flushometer is a 1 in or 1-1/4 in line, not the 1/2 in or 3/4 in that feeds a tank toilet. The valve dumps a high flow rate for a short burst, and a starved line cannot deliver it. Put a flushometer on an undersized supply and it short-flushes every time. No amount of adjusting fixes a pipe that is too small.
What is the difference between a diaphragm and a piston flushometer?
Every flushometer works by holding water pressure above a movable part to keep the valve shut, then briefly relieving that pressure to let it open. The two designs differ in what that movable part is. A diaphragm flushometer uses a flexible rubber diaphragm. A piston flushometer uses a molded cup, often called a piston or clapper, that slides in a cylinder.
The diaphragm is the more common design and the one most people picture. It recovers fast between flushes, which suits high-traffic restrooms, and parts are everywhere. The piston tolerates dirty water better, because its sealing surfaces are less fussy about grit and debris than a thin diaphragm and its bypass. That makes the piston the pick where the supply is well water, reclaimed or rainwater, or anything that is not clean municipal water.
Both share the same core parts: an upper control chamber, a lower supply chamber, a relief valve tripped by the actuator, and a tiny bypass orifice that lets the valve repressurize and shut itself. The next two sections walk through each one, because knowing which is in front of you decides which rebuild kit you buy and what failure to expect.
How a diaphragm flushometer meters and shuts off
At rest, supply pressure fills the upper control chamber above the diaphragm and holds it down against the seat, sealing the valve. The diaphragm carries a tiny bypass orifice, a hole on the order of 0.020 to 0.030 in, that bleeds water from the lower chamber up into the upper one to keep that holding pressure topped off.
Trip the handle or the sensor and the relief valve tilts off its seat. That dumps the pressure in the upper chamber faster than the bypass can refill it, so the higher pressure under the diaphragm lifts it off the main seat and water flows straight to the fixture. The valve is now open and flushing.
It shuts itself by metering. With the relief valve reseated, water bleeds back through the bypass orifice into the upper chamber, pressure builds again, and when it equals the supply the diaphragm settles back onto the seat and the flush ends. The flush volume is set by how long that takes, which is governed by the diaphragm and its bypass, not by the handle. Here is the failure to know cold: plug that bypass with debris and the upper chamber never repressurizes, so the valve never shuts and runs continuously. That one clogged hole is behind most running flushometers.
How a piston flushometer works and where it wins
A piston flushometer does the same job with a molded cup riding in a cylinder instead of a diaphragm. The cup seals at the main seat at the bottom, at a lip seal around the cylinder, and at the relief valve, so it has more than one sealing surface doing the work. Supply pressure above the piston holds it down and shut. Relieving that pressure lets the piston rise and flush. The bypass refills the upper volume and reseats it.
Where the piston earns its place is dirty water. A diaphragm and its small bypass are sensitive to grit, scale, and debris, and they foul. The piston's surfaces and passages handle that abuse better, so on well water, reclaimed water, rainwater catchment, or any supply that is not clean, the piston is the more forgiving choice and stays in service longer between rebuilds.
The tradeoff people argue about is recovery speed. Diaphragm valves tend to recover a touch faster between flushes, which is why they dominate clean-water high-traffic restrooms, while the piston trades a little of that for tolerance to bad water. Pick the mechanism for the water you actually have, not for habit.
Manual handle vs sensor actuation
A flushometer is tripped one of two ways: a manual handle or an infrared sensor. The mechanism that meters the flush, diaphragm or piston, is the same underneath. Only the trigger changes.
The manual handle is the oscillating or push lever you have used a thousand times. Push it any direction and a plunger inside tips the relief valve to start the flush. It is simple, has nothing to power, and works as long as water is on. It is also the part a sick building's worth of hands touch, which is the hygiene argument against it.
The sensor version is touchless. An infrared eye sees the user arrive and leave and fires the flush on departure, with no handle to touch. That buys hygiene, and it buys water control, because the valve flushes once per use instead of on a habit of double-pushing. It also adds a power source, electronics, and a solenoid that can fail, which the manual valve does not have. Most sensor models keep a manual override button on the cover so the fixture still flushes when the power or battery dies.
Sensor flushometers: power, solenoid, and the sentinel flush
A sensor flushometer replaces the handle's mechanical plunger with a solenoid that the electronics fire. The infrared sensor detects the user, and on departure the controller pulses the solenoid, which acts on the relief valve the same way the handle would. Everything downstream of that is ordinary diaphragm or piston operation.
Power comes three ways. Battery models, often a set of lithium cells or a small pack, are the easiest retrofit because they need no wiring. Hardwired models run off a low-voltage transformer and never need a battery change. Turbine or hydro-powered models generate their own power from the flush itself, charging a cell or capacitor so there is no battery to replace and no wire to pull. Which one fits depends on what is already in the wall and how many valves you maintain.
One behavior to know is the sentinel or automatic flush. Many sensor valves flush themselves on a timer if a fixture has gone unused for a day or so, to keep the trap seal from drying out and letting sewer gas into the room. If a urinal in a quiet wing flushes on its own at 3 a.m., that is the sentinel flush working, not a fault.
Water closet vs urinal flushometers
A flushometer is built and rated for one fixture or the other, and they are not interchangeable. A water closet flushometer moves much more water per flush than a urinal flushometer, and the internals, the spud size, and the rated volume all reflect that.
Water closet flushometers run at toilet flush volumes: commonly 1.6 gpf, with high-efficiency models at 1.28 gpf, and older valves still in service at higher legacy figures. Urinal flushometers run far lower: commonly 0.5 gpf, with high-efficiency models at 0.125 gpf, the pint-per-flush valve, and 0.25 gpf in between. Confirm the exact gpf against the valve and fixture data sheets, because the catalog is full of variants.
The spud and the rough-in differ too. Water closets usually take a larger top or back spud and a bigger valve body. Urinals take a smaller spud and a smaller valve. You cannot make a urinal valve flush a toilet or the other way around. Match the valve to the fixture by type first, then by gpf.
Flush volume and water efficiency
The flush volume, gpf, is where a flushometer meets the water code and the building's water bill. The federal and code ceilings have come down over the years, and the valve you install has to meet the limit the project and the jurisdiction set.
The common figures: water closets at 1.6 gpf, high-efficiency at 1.28 gpf; urinals at 0.5 gpf, high-efficiency at 0.125 gpf, with 0.25 gpf as a middle step. WaterSense, the EPA's labeling program, certifies high-efficiency fixtures and valves that meet a tighter volume while still passing a flush-performance test, so a WaterSense water closet sits at or below 1.28 gpf and a WaterSense urinal at or below 0.5 gpf. The full picture of fixture-level water efficiency, the gpm faucet and shower limits included, is in the fixtures and water-efficiency guide.
The number on the valve is only half the system. A 1.28 gpf valve only delivers a working 1.28 gpf flush on a bowl designed for it, which is the fixture-match point a few sections down. Confirm the required gpf against the project specification, the adopted code, and any WaterSense or local rebate requirement before you order valves.
Dual-flush flushometers
A dual-flush flushometer gives the user two flush volumes from one valve: a full flush for solids and a reduced flush for liquids. On a manual valve, the handle does it by direction. Lift the handle up for the reduced flush and push it down for the full flush, or the reverse depending on the maker. Sensor dual-flush models choose the volume automatically from how long the user was present.
A common pairing is 1.6 gpf full and 1.1 gpf reduced on a water closet, which averages well below a straight 1.6 gpf valve over a day of mixed use. The savings are real in a high-traffic restroom where most flushes are liquid only.
The catch is the same as any flushometer. The fixture has to be designed for dual-flush operation and for both volumes, and the reduced flush still has to clear the bowl. A dual-flush valve on a bowl that needs the full volume to clear just means more double-flushing, which gives the savings back. Match the valve to a fixture rated for it.
The flushometer gpf must match the fixture
This is the one to get right. The valve's rated gpf has to match the fixture's design gpf. A water closet bowl is engineered to clear on a specific flush volume and a specific delivery, and the flushometer has to deliver that volume. Mismatch them and the fixture does not work, no matter how good either piece is on its own.
Put too little water to a bowl that needs more, a 1.28 gpf valve on a 1.6 gpf bowl, and you get a weak flush that does not clear and a fixture that clogs. Put too much to a bowl designed for less and you can overflow it, or just waste the water you were trying to save. The bowl and the valve are a matched pair, and the data sheets state the volume each expects.
The mistake shows up most on retrofits, where someone swaps in a lower-gpf valve to save water on a bowl that was never designed for it. The water bill drops and the complaints start. Check the fixture's rated gpf, match the valve to it, and only drop the volume if the bowl supports the lower number.
The vacuum breaker and backflow
Every flushometer has a vacuum breaker in the tailpiece between the valve and the fixture, and it is there to stop backflow. The flushometer connects pressurized potable water directly to a fixture, which is a cross-connection, and if the supply ever loses pressure the water in the bowl could be siphoned back into the potable system. The vacuum breaker breaks that siphon by admitting air.
It is a wear part. A vacuum breaker that is cracked, fouled, or assembled wrong can leak or spit during the flush, and a failed one is a real cross-connection, not a cosmetic problem. On a flushometer the vacuum breaker sits in the chrome tailpiece and is replaceable on its own.
Backflow prevention is its own subject with its own devices, test procedures, and standards, and the flushometer's vacuum breaker is one small piece of it. Where the local code or a backflow program governs, follow it.
Installing a flushometer
A flushometer ties three points together: the control stop on the supply, the valve body, and the spud on the fixture. The supply comes through the wall to the control stop, the valve hangs off the control stop, and the tailpiece drops into the fixture spud and seals there. Get those three at the right height and orientation and the rest is straightforward.
The rough-in sets it up. The supply stub-out comes through the finished wall at the height and offset the valve and fixture call for, and the spud height on the fixture has to match. Those dimensions come off the valve and fixture sheets, and the rough-in stage is where they have to be right, which is the fixture rough-in and setting guide's subject. Set the supply too low or off to the side and the valve will not line up clean.
Watch the control stop orientation so the adjusting screw and the stop are reachable after the cover and the wall finish are on. Make up the spud coupling square and snug so the tailpiece seals without cocking. And leave the protective cap on the sensor or the handle until the restroom is done, so it survives the finish trades.
What the control stop does, and what it does not
The control stop is the angle-stop valve where the supply meets the flushometer, and it does two jobs. It shuts the water off to that one valve for service, and it throttles the flow into the valve. It is a spring-loaded stop, much like a check, and it is the only shutoff for that fixture, so every flushometer should have one that works.
Here is the myth worth killing: the control stop does not set the flush volume. Plenty of techs crank the control stop in to try to cut a flush short, or open it up to fix a weak flush, and all they really do is starve or flood the valve. The flush volume is set by the diaphragm or piston kit, specifically its bypass and metering, not by the stop. Throttle the stop down far enough and you do change behavior, but you are choking the valve, not adjusting its volume the way it was designed to be adjusted.
If you need a different flush volume, you change the diaphragm or piston kit to one rated for that volume. The control stop is for shutting off and for a coarse flow trim. Treat it as a volume knob and you chase your tail.
Why does my flushometer keep running?
A flushometer that runs continuously almost always has a fouled bypass orifice or a worn diaphragm or piston. The bypass is the tiny hole that lets the upper chamber repressurize and shut the valve. Plug it with debris or scale and the chamber never builds pressure, so the valve never reseats and water runs until you fix it. Pull the kit, clear the bypass, and replace the diaphragm or piston if it is torn or hardened.
A weak or short flush is the other common call, and it splits two ways. If the kit is good, suspect the supply: low flowing pressure or an undersized or throttled line cannot deliver the flush. If the supply is good, the kit is worn or the bypass orifice has enlarged from corrosion, which lets the valve close too soon. An enlarged bypass shuts the valve early and short-flushes.
No flush at all is usually the control stop closed, the handle or solenoid not tripping the relief valve, or a dead battery on a sensor model. A double flush, where the valve fires twice, points to a relief valve not seating cleanly or a diaphragm starting to fail. Work it in that order: supply, then the kit, then the actuator.
Rebuild kits: diaphragm, piston, genuine vs universal
The standard service on a flushometer is a rebuild, not a replacement. The wear parts are the diaphragm or piston kit, the relief valve, and the seals, and they come as a kit you swap in 10 minutes with the water off at the control stop. Shut the stop, take the cover off, lift the old kit, drop the new one in, and reopen the stop. That single repair fixes most running, weak, and short-flush complaints.
Buy the kit for the valve and the volume. A diaphragm flushometer takes a diaphragm kit, a piston takes a piston kit, and the kit is rated for a specific gpf, so a 1.6 gpf valve gets a 1.6 gpf kit. Drop in the wrong-volume kit and you have just changed the flush volume by accident, which is the legitimate way to change volume but a problem when it is unintended.
Genuine versus universal is a real choice. Genuine manufacturer kits, Sloan in a Sloan and Zurn in a Zurn, fit and meter exactly as designed and hold the rated volume. Universal kits fit a range of valves and can get a dead fixture flushing in a pinch, but they do not always hold the exact gpf or last as long. On a water-efficiency job where the gpf has to be exact, use the genuine kit for the valve. While the kit is out, clean the bypass and the seat. That is half the repair.
Maintaining sensor flushometers
Sensor valves add two failure points the manual ones do not have: the power source and the solenoid. Most sensor problems are one of those, not the flush mechanism.
A battery model that stops flushing, flushes erratically, or sits with a blinking sensor light usually wants a battery. Keep a record of which restrooms have battery valves and change them on a schedule instead of waiting for complaints, because a dead battery is a dead fixture until the override is used. Hardwired models point you at the transformer and the wiring instead. Turbine models scavenge power from the flush, so a valve that stops flushing can stall its own charging, which makes the failure look worse than the cause.
When power is good and the valve still will not fire, the solenoid is the usual suspect. It is a replaceable part, and on most models it comes out without pulling the whole valve. The infrared sensor and lens want an occasional wipe, because a lens fouled with hard-water film or grime can misread and either flush constantly or not at all.
Hard water, scale, and debris
The small passages that make a flushometer meter itself are also what make it sensitive to bad water. The bypass orifice is 0.020 to 0.030 in, and scale, grit, or pipe debris is all it takes to plug it or wear it open. A plugged bypass runs the valve. An enlarged one short-flushes it. Either way the water quality is the root cause and the kit is the symptom.
Hard water leaves scale on the seat, the bypass, and the relief valve, and in a hard-water building flushometers need their kits cleaned or replaced more often. New construction is the other big debris source. Solder, pipe dope, cutting chips, and thread-tape shavings ride down the new line and lodge in the first thing with a tiny orifice, which is the flushometer. Flush the supply lines before you set the valves, and expect to clean kits during the first months of a new building.
This is where the piston earns its keep. On well water, reclaimed water, or any supply that carries solids, the piston tolerates the debris better than a diaphragm and goes longer between services. Pick the mechanism for the water.
Retrofitting a lower flush volume
Cutting a building's water use by dropping flushometers to a lower gpf is a common retrofit, and it works only if the fixture supports the lower volume. Swapping a 1.6 gpf diaphragm kit for a 1.28 gpf kit is a 10-minute change per valve, and it is the cheapest water-saving move on a flushometer fixture. The trap is the bowl.
A water closet bowl designed for 1.6 gpf may not clear on 1.28 gpf, and a urinal built for 1.0 or 0.5 gpf may not clear on a pint. Drop the volume below what the fixture needs and you trade a lower flush for double-flushing and clogged bowls, which uses more water and generates complaints. Check the fixture's rated gpf before you change kits, and on older bowls test a few before you do the whole building.
The clean version of this retrofit is replacing valve and fixture together as a matched high-efficiency pair, so the bowl and the gpf are designed for each other. If budget forces a kit-only change, confirm the existing bowls will clear on the lower volume first.
ADA and the flush actuator
Where a fixture is on an accessible route, the flush control has to be usable, and the rule people miss is the handle side. The flush handle has to be on the open or wide side of the fixture, the side away from the wall, so a person in a wheelchair can reach it without reaching across the bowl. Mount the valve with the handle on the wrong side and it fails the accessibility check even if everything else is right.
The mounting height of the control also has to fall within the accessible reach range. A sensor flushometer sidesteps the handle-side question, because there is nothing to reach, and the automatic flush is itself an accessibility benefit. The specific dimensions and which fixtures must comply come from the accessibility standard the project is built to, so confirm them against that standard and the local code rather than from memory.
Where flushometers belong
Flushometers live anywhere a restroom takes traffic a tank toilet cannot keep up with. Office buildings, schools, airports, stadiums, arenas, hospitals, factories, and any high-use public restroom run on them, because the fast recycle and the no-tank durability are what that load needs. The busier the restroom, the stronger the case for a flushometer over a tank.
Large commercial facilities and data centers are worth a note, because their restrooms are flushometer territory for the same traffic and durability reasons, and because the facility's water and maintenance are managed tightly. Sensor valves with a sentinel flush suit a building where some restrooms sit unused for stretches and a manager wants the trap seals kept and the water tracked. In any of these, the supply has to be sized and pressured for the valves from the start, which is a design decision, not a field fix.
The pattern across all of them is the same: high or unpredictable traffic, a premium on uptime, and water that has to be accounted for. That is the case a flushometer answers.
Inspection and flush-performance check
Commissioning a flushometer is a short list, and it is worth doing on every valve before the restroom opens. Flush it under real supply and watch the bowl or urinal clear in one flush. A bowl that needs two flushes to clear is a gpf-match or a supply problem, not a quirk to live with.
Check that the valve shuts itself cleanly with no run-on, no drip at the spud, and no spitting at the vacuum breaker. Confirm the control stop is reachable and works as a shutoff. On sensor models, walk the sensor to confirm it fires on departure, test the manual override, and note the power type for the maintenance record. On water-efficiency jobs, confirm the kit gpf matches the fixture and the project's required volume, because that is what an inspector or a rebate auditor will ask for.
The two failures that slip through are a valve that short-flushes on a marginal supply, which only shows under real use, and a vacuum breaker that spits, which only shows during the flush. Run a real flush, not a dry trip, to catch both.
What to document
A restroom full of flushometers is a maintenance record waiting to happen, and the time to capture it is at install, not when a valve fails. Record what each valve is so the next tech buys the right kit without pulling a cover to find out.
For each fixture, capture the valve make and model, whether it is diaphragm or piston, water closet or urinal, the rated gpf, the actuation, manual or sensor, and on sensor valves the power type and battery size. Note the kit part number, genuine or universal, and the date of the last rebuild. That record turns a service call into a kit off the truck instead of a diagnosis on the floor.
| Type | Where it fits | Note for the record |
|---|---|---|
| Diaphragm WC, manual | Clean-water high-traffic toilet | Fast recycle; common 1.6 or 1.28 gpf kit |
| Piston WC | Well, reclaimed, or dirty water | Tolerates debris; match piston kit and gpf |
| Sensor WC or urinal | Touchless, hygiene-driven restroom | Note power type, battery size, override |
| Urinal flushometer | Urinal only | 0.5 or 0.125 gpf; smaller spud and body |
| Dual-flush WC | Mixed-use high-traffic toilet | Full and reduced volume; fixture must support it |
Common mistakes
- Putting a valve gpf that does not match the fixture, which gives a weak flush, clogs, or an overflow.
- Trying to set the flush volume at the control stop, when the volume lives in the diaphragm or piston kit.
- Leaving debris or scale in the bypass orifice, which runs the valve continuously.
- Using a diaphragm valve on dirty or reclaimed water where a piston would last, or the wrong kit for the water.
- Skipping or mis-assembling the vacuum breaker, which leaves a real cross-connection.
- Feeding the valve from an undersized 1/2 in or 3/4 in supply, or a line with too little flowing pressure, so it short-flushes.
- Dropping in a universal kit that does not hold the fixture's rated gpf on a water-efficiency job.
- Retrofitting a lower gpf kit onto a bowl that was never designed to clear on it.
Field checklist
Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.
Standards and references
The valve itself is covered by ASSE 1037, harmonized as ASME A112.1037 and CSA B125.37, the performance standard for pressurized flushing devices, which sets the design, materials, and test requirements for flushometers on water closets and urinals. The vitreous china fixtures the valves serve fall under ASME A112.19.2, the standard for ceramic plumbing fixtures. Cite the edition the jurisdiction has adopted, because these are revised on a cycle.
Water efficiency is set by federal limits and by the adopted plumbing code, the IPC or the UPC depending on the jurisdiction, with WaterSense, the EPA program, certifying high-efficiency fixtures and valves that meet a tighter volume and still pass a flush-performance test. The plumbing code also governs the fixture connection and the backflow protection the vacuum breaker provides.
The flush volume and the minimum flowing pressure are model-specific, so hedge them to the manufacturer. Sloan, Zurn, and Toto publish the gpf, the pressure range, and the exact rebuild kit for each valve, and that data sheet is the number that controls, alongside the project specification and the adopted code. Match the kit to the valve, match the valve gpf to the fixture, and remember the control stop is a shutoff and a flow trim, not the volume adjustment.
Units and terms
A flushometer carries a few names and a few units that show up across a spec, a data sheet, and a parts list, and they all point at the same handful of ideas.
- Flushometer
- The valve that flushes a fixture directly off the pressurized supply line, with no tank; also called a flush valve.
- gpf
- Gallons per flush, the volume the valve delivers; the WaterSense and code limits are set in gpf.
- Diaphragm kit
- The rubber diaphragm, relief valve, and bypass that meter a diaphragm flushometer and set its flush volume.
- Piston / cup
- The molded cup that meters a piston flushometer; more tolerant of dirty water than a diaphragm.
- Bypass orifice
- The tiny hole, about 0.020 to 0.030 in, that repressurizes the upper chamber and shuts the valve.
- Control stop
- The angle stop at the supply that shuts off and trims flow to the valve; not the volume adjustment.
- Vacuum breaker
- The backflow device in the tailpiece that admits air to stop back-siphonage into the potable supply.
- Spud
- The threaded fixture connection the flushometer tailpiece seals into; larger on water closets than urinals.
- Sentinel flush
- An automatic timed flush on a sensor valve that keeps the trap seal from drying out when a fixture sits unused.
FAQ
What is a flushometer?
A flushometer, also called a flush valve, is the metering valve that flushes a commercial toilet or urinal off the supply line instead of a tank. Manual or sensor-actuated, it opens, lets a rated volume through, and closes itself. Diaphragm and piston are the two internal designs. Plumbers use them where traffic is heavy.
What is the difference between a diaphragm and a piston flushometer?
Both hold supply pressure above a moving part to stay shut, then relieve it to flush. A diaphragm flushometer uses a flexible rubber diaphragm and recovers fast for high traffic. A piston flushometer uses a molded cup that tolerates dirty, well, or reclaimed water better. Pick the mechanism for your water quality.
Why does my flushometer keep running?
A flushometer that runs continuously usually has a clogged bypass orifice or a worn diaphragm or piston. The bypass is the tiny hole that repressurizes the valve to shut it; plug it with debris or scale and the valve never reseats. Shut the control stop, pull the kit, clear the bypass, and replace worn parts.
How do you adjust the flush volume on a flushometer?
You change the flush volume by changing the diaphragm or piston kit to one rated for the volume you want, not by turning the control stop. The control stop only shuts the valve off and trims flow. A 1.6 gpf valve needs a 1.6 gpf kit; drop to a 1.28 gpf kit only if the fixture clears on it.
What is the gpf for a water closet vs a urinal flushometer?
Water closet flushometers commonly run 1.6 gpf, or 1.28 gpf high-efficiency. Urinal flushometers run far lower, commonly 0.5 gpf, 0.25 gpf, or 0.125 gpf, the pint-per-flush valve. The two are not interchangeable. Confirm the exact gpf against the valve and fixture data sheets and the project's required volume.
Why won't my flushometer flush properly?
A weak or short flush is usually the supply or the kit. Low flowing pressure or an undersized line cannot deliver the flush, so check the supply first. If the supply is good, the diaphragm or piston is worn or the bypass orifice has enlarged from corrosion, which closes the valve too soon. Rebuild the kit.
Do I need a special supply line for a flushometer?
Yes. A flushometer flushes on line pressure and needs a 1 in or 1-1/4 in supply, not the 1/2 in or 3/4 in that feeds a tank toilet. It also needs adequate flowing pressure, often around 20 to 25 psi minimum depending on the model and fixture. Confirm both against the valve's data sheet.
Can I put a lower-gpf kit in my flushometer to save water?
Only if the fixture clears on the lower volume. Swapping a 1.6 gpf kit for a 1.28 gpf kit is a quick change, but a bowl designed for 1.6 gpf may not clear on less, which causes double-flushing and clogs. Check the fixture's rated gpf first, and on older bowls test a few before doing the whole building.
What powers a sensor flushometer?
Sensor flushometers run on batteries, a hardwired low-voltage transformer, or a turbine that generates power from the flush itself. Batteries are the easiest retrofit; hardwired never needs a change; turbine needs neither battery nor wiring. Most keep a manual override button so the fixture still flushes if the power or battery dies.
People also ask
Codes cited in this guide
This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.