Roofing
Cool roofs: solar reflectance, emittance, SRI, and energy
What a cool roof is, how solar reflectance and thermal emittance combine into SRI, the aged-value catch, the cold-climate tradeoff, and the code numbers you have to hit.
Direct answer
A cool roof has high solar reflectance and high thermal emittance, so it reflects most of the sun and re-radiates the heat it absorbs. That keeps the surface and the building cooler and cuts cooling load. Solar Reflectance Index combines both into one number, but the adopted energy code and the CRRC listing control compliance.
Key takeaways
- A cool roof needs both high solar reflectance (reflects sunlight) and high thermal emittance (re-radiates absorbed heat); bare metal reflects well but emits poorly.
- Energy codes require the three-year AGED reflectance, not the brochure initial value; white membranes often drop from near 0.80 to 0.55-0.65 aged.
- SRI (per ASTM E1980) combines reflectance and emittance into one number: standard black is 0, standard white is 100, and the scale is not capped.
- The CRRC measures and publishes initial and aged SR, TE, and SRI but sets no pass/fail thresholds; products are CRRC-rated, not CRRC-passing.
- Reflective low-slope roofs over cooled spaces cut peak cooling demand roughly 10-15 percent; reflectance does not replace the separately-required insulation R-value.
What a cool roof is, and the two properties behind it
A cool roof is a roof that stays cooler in the sun because of two surface properties working together: high solar reflectance, so most of the sunlight bounces off instead of being absorbed, and high thermal emittance, so the heat that does get absorbed gets re-radiated away instead of soaking into the building. Color is the rough proxy people see, but the two numbers are what actually decide it.
The mechanism is straightforward. A dark roof absorbs the sun, heats up, and pushes that heat down through the assembly and back into the air above the city. A reflective roof sends most of that energy straight back to the sky before it ever becomes heat in the membrane. On a hot afternoon the difference at the surface is large. A black membrane can sit near 180 degrees F, roughly 100 degrees above the air, while a reflective surface on the same day can run close to the ambient temperature.
Two properties, not one. A white roof that reflects well but cannot shed the heat it absorbs runs hotter than its reflectance alone suggests. Bare shiny metal is the classic example: high reflectance, low emittance, hotter than you would guess. The cool roof you want is high on both.
What is solar reflectance?
Solar reflectance is the fraction of the sun's energy a surface reflects, on a scale from 0 to 1. A value of 0.65 means the surface reflects 65 percent of the solar energy that hits it and absorbs the other 35 percent. It is also called albedo, and on a CRRC label it shows up as solar reflectance, or SR.
The scale runs the full span of roofing. A standard dark membrane reflects only about 5 to 10 percent, so an SR near 0.05 to 0.10, which is why dark roofs hold more than 80 percent of the solar energy they see. A bright white single-ply or coating can reflect 70 to 80 percent, an SR of 0.70 to 0.80. Aged and dirty surfaces land lower than their fresh number, which is the catch covered later in this guide.
Solar reflectance measures the whole solar spectrum, not just the visible light your eye reads as color. That matters because near-infrared makes up roughly half the sun's energy. A roof can look medium-toned and still carry a respectable reflectance if it is built with infrared-reflective pigments, which is how colored cool-roof products beat plain dark paint of the same shade.
Thermal emittance: the heat the surface gives back
Thermal emittance is how well a surface re-radiates the heat it has absorbed, again on a 0 to 1 scale. A value of 0.90 means the surface sheds 90 percent of the long-wave heat a perfect emitter would at the same temperature. Most roofing materials, including the membranes and coatings used on low-slope work, sit high here, commonly 0.85 to 0.92.
The exception that trips people up is bare metal. Unpainted aluminum or galvanized steel can reflect a lot of sun but emit poorly, with emittance down around 0.05 to 0.25. That low emittance means the metal holds the heat it does absorb, so it runs hotter and gives a worse SRI than the reflectance alone would predict. Paint or a coating fixes the emittance, which is why painted metal beats raw metal for a cool roof even when the raw metal looks brighter.
For most single-ply and coated roofs, emittance is the property you rarely have to fight, because the material already emits well. You confirm the listed number and move on. It is on metal and on certain specialty surfaces that emittance becomes the deciding half of the equation.
What is SRI?
Solar Reflectance Index, or SRI, rolls solar reflectance and thermal emittance into one number so you can compare surfaces with a single figure. It is calculated by the method in ASTM E1980, which sets a standard black surface at 0 and a standard white surface at 100, then places every other surface between them by where its equilibrium temperature in the sun would fall.
The scale runs roughly 0 to 100, but it is not capped. A very hot dark surface can land negative, and a very cool surface, high reflectance plus high emittance, can exceed 100. A standard black with SR about 0.05 and emittance 0.90 anchors the 0. A standard white with SR about 0.80 and emittance 0.90 anchors the 100. The higher the SRI, the cooler the surface runs under the same sun.
SRI is convenient for codes and credits because it is one number, but it hides the two inputs. Two products can share an SRI while reaching it differently, one leaning on reflectance and one on emittance. When a spec or a code lets you comply by either an SRI value or a reflectance-and-emittance pair, read which path the product's listing actually documents, because the CRRC reports all three and the code may accept any of them.
The three numbers and what each one tells you
A cool-roof submittal lives on three values, and reading them in order tells you most of what you need. Solar reflectance says how much sun the surface turns away. Thermal emittance says how readily it lets go of the heat it keeps. SRI combines the two so one figure ranks the surface against a black-to-white scale.
The table below shows where common surfaces fall. These are representative ranges, not the value for any specific product. The number you cite for compliance is the one on that product's CRRC listing, initial and aged, not a generic figure from a chart.
| Surface | Solar reflectance (SR) | Thermal emittance (TE) | Approx. SRI |
|---|---|---|---|
| Standard black membrane (EPDM) | 0.05 to 0.10 | 0.86 to 0.90 | 0 to 6 |
| Aged gray / weathered membrane | 0.20 to 0.30 | 0.85 to 0.90 | 20 to 35 |
| White TPO or PVC, fresh | 0.70 to 0.80 | 0.86 to 0.92 | 100 to 110 |
| White reflective coating, fresh | 0.75 to 0.85 | 0.85 to 0.90 | 105 to 115 |
| Bare unpainted metal | 0.50 to 0.65 | 0.05 to 0.25 | Low, despite high SR |
Why a cooler roof surface matters
Drop the roof surface temperature and four things follow. The first is the building's cooling load. Less heat enters through the roof, so the air conditioning runs less, and the field data points to peak cooling demand reductions in the range of 10 to 15 percent for a reflective roof over a cooled space, depending on insulation and climate.
The second is membrane life. Heat ages a single-ply. A membrane cycling to 180 degrees F every sunny day embrittles, loses plasticizer, and weathers faster than the same membrane held 50 to 80 degrees cooler. Less heat at the surface is less thermal stress on the seams and the sheet, which is part of why reflective membranes hold up the way they do.
The third is the urban heat island. Cities run hotter than the countryside partly because dark roofs and pavement absorb the sun all day and release it at night. Reflective roofs cut that contribution, which is why many municipal energy codes push cool roofs in dense areas. The fourth is simply code: in many climate zones a low-slope roof over a cooled space has to meet a reflectance or SRI minimum, so the surface is not optional anymore.
Do cool roofs save energy?
Yes, in a cooling-dominated building a cool roof saves energy, and the savings come almost entirely from reduced air conditioning. Studies and field measurements put peak cooling demand reductions around 10 to 15 percent for a reflective low-slope roof, with annual cooling-energy savings that scale with how much sun the roof sees and how much of the year the building is being cooled.
The size of the saving depends on three things you can read off the building. How sunny and hot the climate is, because more sun means more energy to reflect. How well insulated the roof already is, because a thick insulation layer narrows the gap between a dark and a cool roof. And how much of the load is cooling versus heating across the year.
Insulation and reflectance are not interchangeable, and that is the point people miss. Reflectance cuts the heat that tries to enter on a sunny day. Insulation slows heat moving in either direction at all times. On a poorly insulated roof, reflectance does a lot of visible work. On a heavily insulated roof, the reflectance still helps but the swing is smaller, because the insulation was already blocking most of the gain. Both matter, and the energy code generally makes you carry both.
Does a cool roof work in a cold climate?
A cool roof can still come out ahead in a cold climate, but the case is closer and you should run the numbers instead of assuming. The concern is real: a reflective roof that turns away summer sun also turns away winter sun, so it can raise heating energy slightly. That is the winter heating penalty, and it is the one honest argument against cool roofs in the north.
The penalty is usually smaller than it sounds, for reasons that stack up. Winter sun is weak and the days are short, so in northern locations winter solar energy is only about 20 to 35 percent of the summer figure, which limits how much a dark roof could have gained anyway. Snow cover reflects sun and insulates the roof regardless of the membrane color underneath. And the heat the building loses in winter goes out through the assembly the same way for a dark or a cool roof at the same insulation level, so the penalty is mostly about lost solar gain, not added loss.
Modeling across cold-climate states generally shows a net annual saving even with the heating penalty counted, with the clear exceptions being the most extreme cold where heating dominates the whole year. The honest move in a heating-dominated climate is an energy model for that specific building, not a blanket yes or no. The code may also decide it for you, since some jurisdictions require a cool roof regardless of zone.
Initial vs aged reflectance: the roof gets dirty
The reflectance on the brochure is the fresh number, and the roof will not hold it. Dirt, soot, biological growth, and weathering all pull reflectance down, and most of the loss happens in the first couple of years. That is why the CRRC and the energy codes work in aged values, measured after three years of real outdoor exposure, not the initial value off a new sample.
The drop is not trivial. A white membrane that starts near 0.80 reflectance can settle into the 0.55 to 0.65 range aged, depending on the climate and how much the roof gets rained clean versus how much soot and pollen it collects. The codes set their thresholds against the aged value precisely because they care about the roof's behavior over its life, not the day it was installed.
This is the number a specifier gets wrong most often. Someone reads the initial reflectance, sees it clears the code, and writes it into the spec, when the code is asking for the three-year aged value that lands lower. Pull both numbers from the CRRC listing and check the requirement against the aged one. If the product is new enough that no aged value is published yet, the CRRC has a calculation path for that, and the code's adopted edition spells out how to handle it.
White membranes vs dark: TPO, PVC, and EPDM
On low-slope single-ply, the membrane chemistry tends to come with a reflectance built in. TPO and PVC are most often installed white, with fresh reflectance up around 0.70 to 0.80, so they meet cool-roof targets out of the roll. EPDM is most often black, with reflectance near 0.05 to 0.10, so a standard black EPDM roof is the opposite of a cool roof unless you choose a white EPDM or coat it.
That does not make EPDM the wrong membrane. It makes color a decision you fold into the membrane selection, which is its own topic covered in the low-slope membrane selection guide. EPDM has real strengths in cold flexibility and field track record, and white EPDM and reflective coatings exist for when you want black EPDM's chemistry with a cool surface. The point is to pick the chemistry on its merits, then handle reflectance deliberately, rather than letting the default color decide your energy compliance by accident.
If the building is in a cool-roof climate zone or under a cool-roof code, a white TPO or PVC clears the reflectance bar without extra steps, while a black membrane forces you to specify a reflective version or a coating to comply. That compliance path, white membrane versus coated dark membrane, is often what tips the membrane choice on a cooling-dominated building.
Reflective coatings on an existing roof
A reflective coating is a way to make an existing dark or aged roof cool without tearing it off. You apply a white liquid-applied coating over the prepared membrane, and a fresh coating delivers reflectance in the 0.75 to 0.85 range, often a higher SRI than a new white membrane. The catch is that a coating is a maintenance item: it is a surface treatment with a service life, and it loses reflectance as it ages and dirties, so it gets recoated on a cycle.
The two common chemistries split on water. Acrylic coatings are water-based, lower cost, and a sound choice on a roof that sheds water well, but they soften and can wash off under standing water, so they are a poor fit for a roof that ponds. Silicone coatings shed ponding water far better and hold up in wet exposure, but they hold dirt, which pulls the reflectance down faster, and they complicate any future recoat because little sticks to cured silicone except more silicone.
Coatings are a topic in their own right, including substrate prep, adhesion testing, and mil thickness, so treat this as the reflectance angle, not the full coating spec. The reflectance point is simple: a coating is the fastest route to a cool surface on an existing roof, the CRRC rates coatings the same way it rates membranes, and the number you document is the coating's aged value, not the day-one shine.
The CRRC rating and the label
The Cool Roof Rating Council, the CRRC, is the third party that measures and publishes the reflectance and emittance numbers everyone else relies on. Under its CRRC-1 program, a manufacturer submits a product to a CRRC-approved lab, which measures solar reflectance and thermal emittance on new samples, then again after three years of outdoor weathering at an approved exposure site. The results, initial and aged, go into the public CRRC Rated Products Directory.
Read what the CRRC does and does not do, because this is misunderstood constantly. The CRRC measures and reports the values. It does not set pass or fail thresholds. The codes and programs do that, and they point at the CRRC listing as the source of record. So a product is not CRRC-approved or CRRC-passing, it is CRRC-rated, with specific numbers you then check against whatever code or credit applies.
When you specify or verify a cool roof, the CRRC directory is where you confirm the numbers, by product, with the initial and aged values side by side. A spec that names a reflectance target without pointing at the CRRC listing leaves the verification undefined. Name the product, pull its CRRC numbers, and check the aged value against the adopted code.
Energy codes and programs that require reflectance
Cool roofs moved from optional to required in a lot of the country, and the requirement is keyed to climate zone, roof slope, and whether the space below is cooled. The numbers below are representative of recent editions, but the adopted edition in your jurisdiction and any local amendments control, so confirm them before you write a spec.
ASHRAE 90.1 has carried cool-roof provisions for low-slope roofs over cooled spaces in the hotter climate zones, commonly zones 0 through 3, with compliance offered either as a minimum three-year aged solar reflectance paired with a minimum emittance, or as a minimum aged SRI. The IECC carries parallel low-slope reflectance requirements tied to climate zone, again referencing aged values. California's Title 24, Part 6 is the strictest mainstream case, requiring cool roofs on commercial buildings across its climate zones, with low-slope aged reflectance and emittance minimums or an SRI path.
Two programs round it out. The legacy ENERGY STAR roof products program set initial and aged reflectance minimums for years and is widely referenced in older specs, though the program itself was discontinued, so treat an ENERGY STAR call-out as historical and verify against current code. LEED awards a heat island reduction credit for high-SRI roofs, with thresholds that have risen across versions. For all of these, the move is the same: find the adopted edition, read the threshold for your zone and slope, and check the product's aged CRRC value against it.
| Code / program | What it requires (representative, verify edition) | Basis |
|---|---|---|
| ASHRAE 90.1 | Low-slope over cooled space, hot zones: aged SR about 0.55 + TE about 0.75, or aged SRI about 64 | Aged, CRRC values |
| IECC | Low-slope reflectance minimums by climate zone | Aged, CRRC values |
| California Title 24, Part 6 | Commercial low-slope: aged SR about 0.63 + TE about 0.75, or SRI about 75 | Aged, CRRC values |
| ENERGY STAR (legacy, discontinued) | Low-slope initial SR about 0.65, aged about 0.50 | Historical reference only |
| LEED heat island credit | High SRI roof, threshold rises by version | SRI |
Reflectivity vs insulation: surface vs bulk
Reflectance and insulation are two different jobs, and a cool roof needs both. Reflectance is a surface property. It decides how much of the sun becomes heat at the top of the assembly in the first place. Insulation is a bulk property. It decides how fast whatever heat is present moves through the assembly, in or out, day or night, summer or winter.
Confuse the two and you make bad calls. A bright reflective surface over a thin insulation layer still lets heat through once the surface warms, because nothing is slowing the conduction. A thick insulation layer under a dark surface blocks most of the gain but leaves the membrane cooking, which shortens its life and adds to the heat island. The pair is what works: reflect what you can at the surface, then slow what gets absorbed with the insulation below it.
The energy code treats them as separate line items for this reason, with a roof insulation R-value requirement and, in many zones, a separate reflectance requirement. Meeting one does not buy you out of the other. The roof insulation and cover board guide covers the bulk side, R per inch, the polyiso cold de-rate, and attachment. This guide covers the surface side. You size both to the code and the climate, not one in place of the other.
Where do cool roofs help most?
Cool roofs pay off most on a hot, sunny, cooling-dominated building with a large low-slope roof. The more of the year the building is being cooled and the more sun the roof sees, the more energy there is to reflect, and the bigger the cooling-bill saving. The southern and southwestern United States is the heartland for this, which is why the strictest cool-roof codes sit in the hottest zones.
Roof geometry matters too. A low-slope roof is nearly flat to the sun for much of the day, so it absorbs heavily if it is dark and reflects heavily if it is light, which makes reflectance a strong lever. A large roof area over conditioned space, like a big-box store, a warehouse with cooled offices, a school, or a data center, multiplies a per-square-foot saving into a number worth chasing.
Add poor existing insulation and the case gets stronger still, because reflectance does the most visible work when the insulation is not already blocking the gain. A flat, dark, under-insulated roof on a cooled building in a hot climate is the textbook candidate, and a reflective recoat or re-roof there often shows the fastest payback you will see in this work.
Where a cool roof helps less
A cool roof gives back less on a heating-dominated building in a cold, cloudy climate, where the winter heating penalty eats into the smaller summer saving and the roof spends much of the year wanting solar gain rather than rejecting it. It also matters less on a heavily insulated roof, because the insulation is already blocking most of the heat the reflectance would have turned away.
Steep-slope roofs are a softer case than low-slope. A pitched roof presents less area square to the midday sun, and codes generally set lower reflectance thresholds for steep slopes than for low slopes. The energy stakes per square foot are lower, and aesthetics and material choice usually drive the call more than reflectance does. None of this means a cool roof is wrong in these cases. It means the energy argument is weaker, so the decision leans more on the code requirement, the membrane choice, and the building than on the cooling-bill math.
Ballasted, vegetated, and PV roofs
Reflectance is one way to keep a roof cool, but it is not the only roof-surface strategy, and on some buildings another approach fits better. Each is its own topic; the note here is how they relate to the reflectance question.
A ballasted roof covers the membrane with stone or pavers, which shields it from the sun and the heat, and light-colored ballast adds reflectance on top of the shading. A vegetated, or green, roof puts soil and plants over the assembly, which shades and cools the membrane through evaporation and gives a low surface temperature without depending on a bright color. A roof carrying photovoltaic panels shades the membrane under the array and turns part of the incoming sun into electricity, and a reflective surface under the panels can lift their output slightly by keeping the array cooler.
These overlap with cool roofs rather than competing head to head. A green roof or a PV array can satisfy or substitute for a reflectance requirement in some codes, while ballast changes the thermal picture without a high-reflectance surface. Where the energy model or the code allows one of these, weigh it as a different way to reach the same low surface temperature, and check how the adopted code credits it against the reflectance path.
Cool roofs on data centers and high-load buildings
A data center is the cleanest case for a cool roof, because it is cooling-dominated all year. The servers throw off heat continuously, so the building is rejecting heat in January the same as in July, and there is almost no winter heating season to trigger the cool-roof penalty. Anything that cuts the heat load entering through the roof helps the mechanical plant year-round.
The roof on a large data hall is also big and low-slope, so the per-square-foot cooling saving multiplies across a wide area, and the building runs a high enough cooling cost that a small percentage cut is real money. A reflective membrane or coating lowers the roof's contribution to the cooling load and shaves peak demand on the hottest afternoons, which is exactly when the cooling plant is most stressed.
The reflectance does not replace the roof's R-value or the mechanical design, and the cooling load is driven far more by the IT equipment than by the roof. But on a building that never stops rejecting heat, a cool roof has no offsetting heating season working against it, so the reflectance is close to pure benefit, and the usual climate tradeoff does not apply.
Keeping the reflectance: cleaning and maintenance
A cool roof is only as cool as its current surface, and reflectance is a maintenance item, not a one-time install. The same dirt, soot, and biological growth that drive the gap between initial and aged values keep working over the roof's life, and a roof left dirty drifts well below the number it was specified at. Most of the early loss is unavoidable weathering, but the slow creep after that is partly housekeeping.
Cleaning recovers a meaningful share of the lost reflectance. A periodic low-pressure wash of a reflective membrane or coating removes the surface soiling and brings the reflectance back toward, though not all the way to, the fresh value. How often is worth it depends on the climate and the local soiling, more in dusty or polluted air, less where rain rinses the roof regularly. Coatings add their own cycle, since a reflective coating gets recoated when its reflectance and film have worn down.
The practical habit is to read the cool roof as part of the roof's regular inspection, not a separate program. While the inspector is checking flashings, terminations, and drains, note the surface condition and the soiling. If reflectance is part of how the building meets code or earns a saving, a dirty roof is a quiet compliance and energy loss that nobody is tracking until someone re-tests it.
What to document
A cool-roof spec that nobody can verify later is a number with no backing. The record is what proves the installed roof meets the code, and it is what a re-test gets checked against years out when someone questions whether the surface still performs.
Capture the product and its CRRC listing, the initial and aged solar reflectance, the initial and aged thermal emittance, the SRI, the code or program requirement you were meeting, the climate zone and slope that set that requirement, and the date. Record the aged values explicitly, because the aged value is what the code is actually asking for, and write down which compliance path you used, the reflectance-and-emittance pair or the SRI, so a reviewer can follow the same path.
| Field to record | Why it matters |
|---|---|
| Product and CRRC listing ID | The source of record for every value |
| Solar reflectance, initial and aged | Aged is what the code requires; both prove the drop |
| Thermal emittance, initial and aged | Half of the SRI and a separate code line |
| SRI | The single-number compliance path where used |
| Code / program requirement met | What the numbers are being checked against |
| Climate zone and roof slope | Sets which threshold applies |
| Compliance path used (SR+TE or SRI) | Lets a reviewer reproduce the check |
Common mistakes
- Specifying a cool roof in a heating-dominated climate without an energy model that nets the winter penalty against the summer saving.
- Reading the initial reflectance off the brochure when the code requires the three-year aged value, which lands lower.
- Assuming reflectance replaces insulation, or insulation replaces reflectance, when the code requires both as separate items.
- Citing a generic reflectance from a color chart instead of the specific product's CRRC listing.
- Treating bare metal as a cool roof on its high reflectance alone, ignoring its low emittance and worse SRI.
- Missing the code SRI or reflectance threshold for the building's climate zone and roof slope.
- Letting the roof stay dirty, so the aged reflectance drifts below the number it was specified at, unnoticed until a re-test.
Field checklist
Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.
Standards and references
The measurement standards are ASTM. Solar reflectance is measured by ASTM C1549 with a portable solar reflectometer, by ASTM E903 by spectrophotometer, or in the field on an installed roof by ASTM E1918. Thermal emittance is measured by ASTM C1371 with a portable emissometer, or by ASTM E408. SRI is computed from the reflectance and emittance by the method in ASTM E1980. The CRRC bases its ratings on these methods.
The CRRC, through its CRRC-1 program and public Rated Products Directory, is the source of record for the values themselves, initial and three-year aged. It measures and publishes; it does not set pass or fail thresholds.
The thresholds live in the energy codes and programs: ASHRAE 90.1 and the IECC for the model energy codes, California Title 24, Part 6 for the strictest mainstream case, the legacy ENERGY STAR roof products criteria for older references, and LEED for the heat island reduction credit. The specific reflectance, emittance, and SRI numbers, and the climate zones they apply to, shift between editions, so confirm them against the edition the jurisdiction has actually adopted and any local amendments before citing them on a submittal. Cite the standard that controls the point, and let the project specification override a rule of thumb when it is stricter.
Units, terms, and conversions
Cool-roof values are unitless fractions and an index, so the confusion is rarely about units. It is about which value, initial or aged, and which property, reflectance or emittance, a number refers to.
Solar reflectance and thermal emittance are both reported on a 0 to 1 scale, and sometimes as a percentage, so 0.65 reflectance is the same as 65 percent. SRI is an index, not a fraction, running roughly 0 to 100 but not capped at either end. Reflectance is also called albedo, and on a label it appears as SR; emittance appears as TE or emissivity. Every value comes in an initial and a three-year aged form, and unless a number is marked initial, treat the code's requirement as the aged value.
- Solar reflectance (SR / albedo)
- Fraction of solar energy a surface reflects, on a 0 to 1 scale; higher reflects more sun
- Thermal emittance (TE / emissivity)
- How well a surface re-radiates absorbed heat, on a 0 to 1 scale; higher sheds heat faster
- SRI
- Solar Reflectance Index, combining SR and TE into one number per ASTM E1980, with black at 0 and white at 100
- Initial vs aged
- Initial is the fresh value; aged is measured after three years of exposure and is what codes require
- CRRC
- Cool Roof Rating Council, which measures and publishes SR, TE, and SRI but does not set thresholds
- Winter heating penalty
- The small rise in heating energy from a reflective roof turning away weak winter sun
FAQ
What is a cool roof?
A cool roof is a roof built to stay cooler in the sun, with high solar reflectance so it reflects most of the sunlight and high thermal emittance so it re-radiates the heat it does absorb. The two properties together keep the surface and the building below it cooler than a standard dark roof.
What is SRI on a roof?
SRI, the Solar Reflectance Index, combines solar reflectance and thermal emittance into one number computed by ASTM E1980. A standard black surface is 0 and a standard white is 100, with cooler surfaces higher and the scale not capped at either end. Codes often let you comply by an SRI value instead of separate reflectance and emittance figures.
Do cool roofs save energy?
Cool roofs save energy on cooling-dominated buildings, mainly by cutting air conditioning. Field data shows peak cooling demand reductions around 10 to 15 percent for a reflective low-slope roof. The saving grows with sun, heat, and a longer cooling season, and shrinks on a roof that already carries heavy insulation.
Does a cool roof work in a cold climate?
A cool roof can still net out positive in a cold climate, but the case is closer because of a small winter heating penalty. Weak short winter sun, snow cover, and insulation limit that penalty, and modeling usually shows net annual savings except in extreme cold. Run an energy model for the specific building rather than assuming.
What is the difference between initial and aged reflectance?
Initial reflectance is the fresh value off a new sample; aged reflectance is measured after three years of outdoor weathering. Dirt and weathering pull the value down, often from near 0.80 to the 0.55 to 0.65 range. Energy codes require the aged value, so specifying off the initial number is the most common cool-roof mistake.
Is a white TPO or PVC roof a cool roof?
A white TPO or PVC membrane is usually a cool roof out of the roll, with fresh reflectance around 0.70 to 0.80. Standard black EPDM is not, reflecting only about 5 to 10 percent, though white EPDM and reflective coatings exist. Confirm the specific product's aged CRRC value against the code rather than assuming by color.
Does a cool roof replace insulation?
No. Reflectance is a surface property that limits how much sun becomes heat at the top of the roof, while insulation is a bulk property that slows heat moving through the assembly in any season. A cool roof needs both, and energy codes generally require an insulation R-value and a reflectance minimum as separate items.
What does the Cool Roof Rating Council do?
The CRRC measures and publishes solar reflectance and thermal emittance for roofing products, both initial and three-year aged, in its public Rated Products Directory. It does not set pass or fail thresholds; codes and programs do that and point at the CRRC listing as the source of record. Products are CRRC-rated, not CRRC-passing.
What SRI or reflectance does the energy code require?
It varies by code edition, climate zone, and roof slope. Representative recent low-slope requirements run around an aged solar reflectance of 0.55 to 0.63 with emittance near 0.75, or an aged SRI in the mid 60s to mid 70s. Confirm the threshold against the adopted edition and local amendments before specifying.
People also ask
Codes cited in this guide
This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.