ASTM International

ASTM C309: compound types, coverage and curing-film acceptance

A curing-compound submittal under ASTM C309-25 establishes performance of a liquid membrane, including moisture retention and, for white-pigmented material, reflectance. It does not establish a complete curing schedule or traffic-release time. Review the submitted test rate, product classification and weather restrictions together. A compound that meets the laboratory material specification still needs the manufacturer’s field conditions to form and preserve the intended film.

Current edition: ASTM C309-25 (2025)
Updated

Official publisher page

Applies to

Concrete specifiers select material performance, suppliers submit test evidence, and inspectors connect the accepted formulation to the product applied. Coordinate the moisture-protection operation in the curing methods guide with the formulation’s tested rate and exposure limits. Those instructions determine what must happen between product approval and a serviceable film.

Key topics

Type describes pigment; class describes the binder

FHWA's C309 summary distinguishes clear or translucent Type 1, Type 1-D with a temporary dye, and white-pigmented Type 2. Class A places no restriction on the solids; Class B requires resin solids. Type 2 alone therefore does not identify the binder. Euclid labels KUREZ VOX WHITE PIGMENTED as Type 2, Class A and describes it as a wax emulsion. Preserve both designations when reviewing a proposed replacement.

Read the water-loss result with its application rate

FHWA-HRT-05-038 describes the C309 moisture-retention criterion as no more than 0.55 kg/m² water loss over 72 hours under C156 testing, at the specified test application rate. The result is moisture lost from the coated test specimen, not a percentage of water retained in a field slab. Require the rate with the reported result so the qualification can be related to the submitted field application.

White pigment has a measured reflectance requirement

ASTM’s C309-25 abstract identifies at least 60% daylight reflectance for Type 2 compounds and a maximum 4-hour touch-dry time for the compounds it covers. These are different properties. Reflectance addresses the white membrane’s response to sunlight, while touch-dry is a film condition. Neither number is the duration of curing or permission to open pavement to vehicles.

Drying and resistance to rain are different clocks

Euclid's KUREZ VOX WHITE PIGMENTED data sheet, revision 02.24, gives 1-hour drying at 73°F and 50% relative humidity, while prohibiting rain or water exposure for 12 hours after application. Its coverage is 200 square feet per gallon on textured concrete and 300 on smooth concrete. A forecast rain window belongs beside the coverage calculation: laboratory drying does not shorten the product's water-exposure restriction.

How it is used in the field

For 18,000 square feet of textured concrete, the cited KUREZ rate requires 90 gallons before application losses. Using the smooth-surface rate would produce a 60-gallon allowance, 30 gallons short of the textured-surface calculation. Keep the substrate condition with the quantity basis; the same product has two different published rates for these surfaces.

An application completed at 10 a.m. reaches the cited product’s 12-hour water-exposure interval at 10 p.m. Its 1-hour laboratory drying figure does not move that exposure limit to 11 a.m. Put the anticipated rain window against the finish schedule before selecting the curing operation. A dry-looking film and a film ready for the forecast exposure are separate observations.

The product file should join the exact formulation, type and class, water-loss test evidence, tested rate and application instructions. Preserve delivered lot identification and surface-specific material quantities with the accepted submittal. This makes it possible to distinguish a material qualification issue from a rate-selection or exposure-timing problem without treating every patch of damaged film as a failed concrete mixture.

Municipal pavement programs create a separate schedule of concrete work: PorchRocket's Bid Control tracks agency budgets and capital plans for contractors preparing for those public placements.

Frequently asked questions

Does a silicate densifier satisfy C309?

ASTM C309-25 distinguishes chemically reactive silicate-salt solutions from membrane-forming compounds and states that they do not meet the specification’s intent. Submit evidence for the specified membrane rather than substituting a surface-hardening claim.

Does C309 prove suitability for a later bonded finish?

C309 qualification does not clear the surface for a later adhesive. Euclid requires complete removal of the cited KUREZ wax compound before adhesives, carpet, tile or other coverings. Include that removal in the finish scope and coordinate the prepared surface with the finish manufacturer; treating touch-dry as bond-ready leaves the wax between the concrete and the adhesive.