ACI CODE-318-25 is the latest structural concrete code published by ACI, released in January 2025. It governs materials, structural design, detailing, and construction when selected by the controlling code and project documents. Its 2025 testing provisions distinguish standard-cured acceptance tests from field-cured evidence for stressing or support removal. The 2024 IBC still references ACI 318-19, so the permit basis and contract specification determine which testing requirements reach the laboratory.

Current edition: ACI CODE-318-25 (2025)
Updated

Official publisher page

Applies to

Designers select the code basis; contractors, producers, inspectors, and laboratories supply the construction and evidence it requires. Put the governing ACI edition and any separate ACI 301 specification on the testing plan. Use the cylinder handling guide for specimen logistics after that plan establishes each test's purpose and count.

A release to stress tendons, remove shores, or apply a construction load needs to identify the affected member and construction stage. A report labeled only concrete strength leaves the recipient to guess whether it answers that question.

Key topics

The 2025 definition changes the small-cylinder count

ACI 318-25 permits a standard-cured strength test using at least two cylinders of either 4-by-8-inch or 6-by-12-inch size, from one sample at 28 days or the designated strength age. For the smaller cylinders, that reduces the minimum from three under ACI 318-19. ACI 301-20 still specifies three according to ACI's cylinder-size FAQ. Reconcile both documents before changing laboratory orders, and schedule reserve and early-age specimens separately.

Standard-cured acceptance has two numerical checks

ACI 318-25 Section 26.12.3.1 requires each three-test moving average to reach the specified strength. ACI 318-25 limits a strength-test shortfall to 500 psi at specified strengths of 5000 psi or less, and to 10 percent of specified strength when it exceeds 5000 psi. These checks use strength-test averages, not individual cylinder breaks. They do not supply the acceptance rule for field-cured construction-stage specimens.

A field-cured average does not authorize support removal

ACI CODE-318-25 requires all field-cured cylinders from the same sample to meet the required construction-stage strength before prestressing or removal of beam and slab supports, unless the licensed design professional approves otherwise. Keep the individual results visible on the release request. A summary mean can hide the result that prevents release under this provision.

Mixture evidence has an age limit

NRMCA's March 2026 specification guide explains that ACI 318-25 requires trial-mixture strength data to be developed within 24 months of submittal. That time restriction applies to strength tests; durability tests can require a longer lead time. Put the trial dates beside the proposed mixture identifier. A recently signed cover sheet does not change the date of the underlying tests. Match material sources and proportions to the proposed work before treating the attachment as current evidence.

How it is used in the field

Create separate laboratory orders for mixture acceptance and construction-stage decisions. Identify specified design strength, required release strength, curing condition, test age, and member location. With 4-by-8-inch cylinders, include the resolved ACI 301 requirement on the order so a laboratory cannot infer the count from the design-code cover sheet alone.

At a stage requiring 3500 psi, two field-cured results of 3300 and 3700 psi average 3500 psi. Under the cited 2025 rule, that average does not establish release without an approved exception. Retain both results and obtain the design professional's disposition before acting on the report.

Trace every release to the current drawing revision and the load or activity being authorized. The concrete may be adequate for one construction operation while a different operation still needs review. Record the permitted area, activity, decision maker, and time so the next shift does not expand a limited release into permission for the entire floor.

When a specimen result is disputed, preserve the original report and the handling record. Any accepted replacement assessment should identify the question it answers and the affected placement. An unexplained replacement number removes the context needed to understand the original concern.

Edition history

ACI published CODE-318-25 in January 2025 following the 2019 edition. The 2025 code includes new appendixes on performance-based wind design and sustainability and resilience. Its publisher portal provides the edition's supporting information and updates.

Adoption

ACI's January 2026 testing explanation identifies ACI 318-19 as the reference used by the 2024 IBC. ACI 318-25 is a later publisher edition, not an automatic amendment to that model code or to an existing contract. Record the locally adopted building-code edition, referenced ACI edition, and accepted project modifications on the inspection plan. Resolve a differing construction specification before changing specimen counts.

Frequently asked questions

Can two 4-by-8-inch cylinders be ordered on every ACI 318-25 project?

Check the accompanying construction specification. ACI's published FAQ identifies a three-cylinder minimum under ACI 301-20, which remains separate from the 2025 code's two-cylinder minimum. The testing plan needs the project's accepted resolution plus specimens required for other ages and purposes.

Do the low-strength acceptance limits also permit early shore removal?

No. The 500 psi and 10 percent shortfall limits concern standard-cured strength tests for concrete acceptance. Construction-stage release uses the member's required in-place strength and the selected evidence. Under the cited 2025 field-cured rule, a passing mean does not override a low individual result without the design professional's approval.