IEEE Standards Association
IEEE 400: choosing the right shielded-cable field-test guide
Field insulation testing of shielded power cable systems rated 5 kV and above is the subject of IEEE 400-2023. The guide compares available test methods, their uses, advantages, limitations, and typical results. It is the overview document for a family of method-specific guides. A specification that cites only IEEE 400 has identified the subject but still needs to select the test method, cable-system application, test level, duration, and required diagnostic evidence.
Applies to
Utility and facility engineers, cable-testing contractors, commissioning teams, and asset managers use IEEE 400 when selecting acceptance or condition-assessment methods for shielded power cable systems. The voltage floor and shielded construction are part of its scope; a 600 V feeder megohmmeter test is not brought into that scope by calling it a cable test.
Use the MV cable testing guide for installation and acceptance planning. In the bid schedule, name the insulation construction, AC or DC service, test objective, and selected energizing waveform. Those four fields determine which method-specific reference the testing contractor needs.
Key topics
VLF guidance was revised in 2024
IEEE 400.2-2024 is the active VLF field-test guide and supersedes IEEE 400.2-2013. Its stated frequency boundary is below 1 Hz, and it includes withstand and diagnostic tests using VLF energization. Specify its edition and the selected waveform with the test package. The fact that a test set operates at a commonly used VLF frequency does not identify the complete acceptance test.
Partial discharge measurements have a separate scope
IEEE 400.3-2022 covers electrical partial-discharge detection, measurement, and location on installed shielded cable systems, including cable, joints, and terminations. It addresses online testing and testing with an external voltage source, and excludes compressed-gas-insulated cable or termination systems. A PD scope should therefore name the energization arrangement and the installed system being diagnosed, rather than treating every PD report as a VLF test report.
Laminated AC cable and DC-service cable use different HVDC guides
IEEE 400.1-2018 addresses HVDC field testing of laminated-dielectric shielded AC cable systems rated 5 to 500 kV. IEEE 400.5-2021 addresses high-direct-voltage testing of shielded cable systems rated 5 kV and above designed for DC service, including laminated or extruded construction. The service type matters: DC test guidance for an extruded DC cable does not authorize the same test on an extruded AC cable.
Keep RMS and peak voltage labels explicit
Megger's VLF Sinus 45 manual lists sinusoidal test output in both RMS and peak units. For a sine wave, peak equals RMS multiplied by √2: a specified 24 kV RMS corresponds to about 33.9 kV peak. This is a unit conversion, not a cable test-level selection. Keep the instrument's voltage convention with the approved waveform; the sine-wave factor is not a conversion rule for every VLF waveform.
DAC has a distinct guide and an inactive 2015 edition
IEEE 400.4-2015 addresses withstand testing and diagnostics with damped alternating current voltage on shielded power cable systems rated 5 kV and above. IEEE moved it to inactive-reserved status on March 26, 2026 and lists a P400.4 revision project. A DAC proposal should retain that waveform and document identity; it is distinct from a VLF test or a fault-locating surge operation.
How it is used in the field
Make each test-schedule row identify the circuit endpoints, phases, cable and accessory models, dielectric, rated voltage, service history, shield arrangement, selected IEEE document and edition, waveform, voltage convention, duration, and required outputs. Attach the termination and splice record so reviewers can see which installed accessories were included in the tested section.
For a mixed circuit containing legacy laminated cable, newer extruded cable, and several splice types, identify every construction before selecting a common test. The same conductor passes through all of them, but the dielectric and accessory application boundaries remain different. Resolve the selected method and ratings in the approved schedule before producing one result labelled simply 'IEEE 400 pass.'
Retain raw test data with the circuit diagram and final disposition. A diagnostic trace needs location references and the configuration used during testing so a future crew can compare the same physical circuit. A repaired termination or a changed sectionalizing point should be visible in the record, rather than appearing as unexplained movement in a later diagnostic trace.
Edition history
IEEE 400-2023 superseded IEEE 400-2012 and was published November 17, 2023. Its method-specific companions revise independently: the VLF edition is 400.2-2024, while the PD edition is 400.3-2022, published in 2023. Copying the overview's edition year onto every companion creates incorrect references.
Adoption
Owners and engineers select the required tests through cable specifications and acceptance plans. The overview helps choose the method; the selected method guide and approved equipment application establish the detailed test basis. A complete report names the specific document instead of relying on the family number as a pass criterion.
Cable-testing estimators can follow school, municipal, and state electrical solicitations in PorchRocket Bid Control to find projects whose bid documents define the required field-test package.
Frequently asked questions
Does IEEE 400-2023 contain one test voltage for every MV cable?
It compares test methods. The test package must identify the method-specific document, cable-system application, waveform, voltage convention, level, and duration used for the acceptance or diagnostic objective.
Does a DC-service test guide apply to an AC cable made from the same insulation material?
The intended service and the guide's application scope remain controlling distinctions. IEEE 400.5-2021 describes cable designed for DC service; matching an insulation material name does not make an AC cable that application.
Does a 24 kV RMS sine-wave requirement mean setting 24 kV peak?
No. The corresponding sine-wave peak is about 33.9 kV. A 24 kV peak sine wave is only about 17.0 kV RMS. Identify the display convention before comparing it with the approved test schedule.
Sources checked
- IEEE 400-2023: overview scope, 5 kV lower rating, method comparisons, and edition history
- IEEE 400.2-2024: active VLF guide, frequency scope, and superseded 2013 edition
- IEEE 400.3-2022: PD field detection, measurement, location, and application exclusions
- IEEE 400.4-2015: DAC scope, March 2026 inactivation, and revision project
- IEEE 400.1-2018: HVDC testing of laminated-dielectric shielded AC cable systems
- IEEE 400.5-2021: high-direct-voltage testing of shielded DC-service cable systems
- Megger VLF Sinus 45 operating instructions, technical data: sinusoidal RMS and peak output conventions