IEEE Standards Association
IEEE 1584: model limits, 600 V division, and study companions
IEEE 1584-2018 remains the active arc-flash calculation guide; its newer companions divide the supporting work into study specification under IEEE 1584.1-2022 and low-voltage data collection under IEEE 1584.2-2025. The calculation model applies directly to three-phase AC systems within defined input limits. Its fault-current ranges divide at 600 V, while the data-collection companion extends through 1,000 V. Keep those boundaries distinct when pricing a survey or reviewing a model.
Applies to
Owners buying an arc-flash study need a survey boundary and an agreed engineering deliverable. Study engineers then need enough source, device, and compartment data to establish calculation applicability at each location. Link the arc-flash study and label package to the input register so each published result remains traceable to its model and equipment.
Electrical contractors and commissioning teams supply equipment data and reconcile the installed system with the approved model. An inspector reviewing a label needs traceability to that installation. Neither the presence of a label nor a software report establishes that every modeled bus lies within the selected calculation method's domain.
Key topics
The fault-current ranges divide at 600 V
ETAP's IEEE 1584-2018 model summary gives 0.5 to 106 kA bolted fault current for 208 through 600 V, and 0.2 to 65 kA for voltages above 600 V through 15 kV. The model concerns three-phase 50 or 60 Hz AC systems. Use those numerical boundaries rather than a site's low-voltage label: equipment below 1,000 V can fall on either side of the calculation's 600 V division.
Specify the contracted study through IEEE 1584.1
IEEE 1584.1-2022 addresses the scope and deliverables an owner should specify for an IEEE 1584 calculation study. Name it when defining the engineering package, data responsibilities, and required outputs. The calculation guide and the procurement guide have different jobs: a reference to the equations alone leaves the owner without a defined agreement about the information and results the study contractor must deliver.
The 2025 data-collection guide stops at 1,000 V
IEEE 1584.2-2025 covers collection of study data for three-phase 50/60 Hz AC equipment at 1,000 V and below. A 690 V bus therefore fits this survey guide while using the above-600-V current range in the 2018 calculation guide. Keep the survey scope and calculation domain as separate fields in the study register.
Document geometry at the actual exposure location
Schneider Electric's presentation emphasizes that multiple electrode configurations can require consideration within equipment. A lineup name alone does not describe every conductor arrangement inside it. Tie the selected configuration to a compartment drawing or a safely obtained equipment record. When more than one configuration is credible, identify the cases the engineer analyzed instead of silently applying one geometry throughout the lineup.
How it is used in the field
A 480 V bus with 350 A bolted fault current fails the calculation model's 500 A minimum. A 690 V bus with the same 350 A passes the above-600-V current-window check because its minimum is 200 A. ETAP's published ranges support both comparisons. Neither comparison completes the applicability review: conductor gap, configuration, enclosure dimensions, and working distance still belong in the model record.
A 4.16 kV bus with 40 kA bolted fault current passes the voltage and current checks but lies beyond IEEE 1584.2's 1,000 V survey scope. Define the required data collection for that bus in the contract rather than assuming a low-voltage checklist covers it. List any unresolved inputs next to the bus identifier so the calculation contractor can price and close the gaps.
During closeout, require the model input register to distinguish field-observed data, manufacturer data, and engineering assumptions. Attach unresolved compartment geometry or missing source data to the affected equipment identifiers. The one-line reading guide supports the system map; the compartment evidence explains the geometry that the one-line cannot show.
Edition history
IEEE 1584-2018 superseded the 2002 calculation guide and was published November 30, 2018. IEEE 1584.1-2022 was published July 12, 2022. IEEE 1584.2-2025 was published September 19, 2025. A later date on a companion document does not mean the underlying calculation guide has acquired that edition year.
Adoption
Owners invoke the calculation and study-deliverable references in their electrical safety and engineering programs. The installation code, workplace safety requirements, and equipment certification address additional obligations. A calculated incident-energy value establishes a modeled thermal exposure; it does not by itself authorize energized work or certify an assembly's fault rating.
Frequently asked questions
Did IEEE 1584.2-2025 replace IEEE 1584-2018?
No. The 2025 publication concerns low-voltage data collection. IEEE 1584-2018 remains the active calculation guide, and IEEE 1584.1-2022 addresses the scope and deliverables for procuring a study.
Which current range applies to a 690 V bus?
The above-600-V range is 0.2 to 65 kA bolted fault current under the model limits published by ETAP. IEEE 1584.2 still covers data collection at 690 V because its separate ceiling is 1,000 V. Passing those checks does not complete the geometry and other model-input checks.
Sources checked
- IEEE 1584-2018: active calculation guide and edition history
- Schneider Electric IEEE 1584-2018 presentation: model ranges and electrode configurations
- IEEE 1584.1-2022: study scope and deliverable requirements
- IEEE 1584.2-2025: three-phase 50/60 Hz AC data collection at 1,000 V and below
- ETAP: IEEE 1584-2018 model ranges, exact 600 V division, and calculation inputs