ANVILFIELD Try FieldOS

International Organization for Standardization and International Electrotechnical Commission (ISO/IEC)

ISO/IEC 30134: PUE, ERF, WUE and the evidence behind each KPI

ISO/IEC 30134 is the data-centre key-performance-indicator series for reporting energy and resource performance. Its separately maintained parts cover facility efficiency, renewable energy, server efficiency and utilization, energy reuse, cooling, carbon and water. Part 2:2026 is the current PUE standard. A defensible report identifies the applicable parts and editions, then connects each published result to its measurement boundary, inputs and reporting method.

Current edition: Part 1:2016 + Amd 1:2018; Part 2:2026; Part 3:2016 + Amd 1:2018; Parts 4 and 5:2017 + Amd 1:2025; Part 6:2021; Part 7:2023; Parts 8 and 9:2022
Updated

Official publisher page

Applies to

Operators, energy managers, sustainability teams and reporting reviewers use the series to define repeatable metrics. Procurement teams also use those definitions when specifying meters and reporting services. Select the parts that answer the owner's reporting questions, and distinguish the measured KPI from a contractual target or a legal filing requirement. A named standard supplies the method's technical basis; the owner's agreement or applicable reporting scheme establishes where it is required.

Key topics

Annual PUE uses energy totals, not averaged dashboard ratios

The Data Center Metrics Task Force recommends annual kWh totals for PUE reporting, including supporting infrastructure and all energy types inside the declared boundary. For an all-electric site, 24,000 MWh total and 16,000 MWh IT gives PUE 1.50, an Anvilfield calculation. Add the underlying energy readings before dividing; an unweighted average of monthly PUE values gives low-load months the same influence as high-load months. ISO/IEC 30134-2:2026 supplies the current PUE standard, including measurement categories and reporting. Task Force measurement guidance hosted by ENERGY STAR

Energy reuse needs an accepted numerator at the delivery boundary

ISO/IEC 30134-6:2021 defines ERF against total data-centre energy consumption. With 6,000 MWh reused and 24,000 MWh consumed, ERF is 0.25, an Anvilfield calculation. Dividing the reused energy by the 16,000 MWh IT consumption from the PUE example would instead give 0.375 and use the wrong denominator. Record the receiving use and measured reused quantity. Reuse remains a separate KPI; subtracting its credit from PUE's numerator changes the metric being reported. ISO's ERF definition

WUE includes a measurement category and a use-phase boundary

IEC describes ISO/IEC 30134-9:2022 as a water-use KPI for the operating phase, with defined measurement categories. The Commission's reporting annexes calculate WUE from water consumption in cubic metres and IT energy in MWh. An input of 8,000 cubic metres with 16,000 MWh IT yields 0.50 cubic metres/MWh, equivalent to 0.50 L/kWh. Using 16,000,000 kWh while leaving water in cubic metres produces 0.0005 cubic metres/kWh; labeling that result L/kWh creates a thousandfold unit error. These are Anvilfield calculations. Commission reporting annexes, Annex III

A regulatory reporting scheme is a separate specification

Article 1 of Commission Delegated Regulation (EU) 2024/1364 sets its reporting scope at installed IT power demand of at least 500 kW. That threshold refers to installed IT power, not a month's energy consumption or the entire site's utility capacity. Keep the reporting obligation separate from ISO publication dates and from minimum-performance legislation still being prepared as of November 5, 2026. Map each filing field to the site's measurements and the method required by that scheme. Commission act transmitted to the Council Commission policy status

How it is used in the field

Build an input register with each meter, included loads or water streams, unit, period and calculation revision. In the worked figures above, PUE and WUE share the 16,000 MWh IT denominator; ERF uses the 24,000 MWh facility total. Store those denominator identities in the calculation, not just the resulting dashboard numbers. Identify estimates separately from measured inputs.

During a meter replacement or plant expansion, capture the last old reading, first new reading, multiplier and effective boundary change. Reconcile the transition with the reporting ledger before publishing the next KPI. A dashboard that silently joins different physical boundaries creates a trend without a consistent meaning. Put ownership of those transitions in the operating handover.

Edition history

ISO's catalogue lists separate 2025 amendments to the Part 4 server-efficiency and Part 5 server-utilization standards. Part 2:2026 replaces the 2016 PUE edition and its 2018 amendment. Preserve the part, amendment and calculation revision implemented by each reporting tool so a software update does not silently change a historical series.

Frequently asked questions

Is there one current year for the entire 30134 series?

The parts have independent edition and amendment records. ISO's catalogue includes documents from several years that remain published together. Record the part and amendment implemented by each calculation, including those embedded in reporting software.

Does a good KPI establish compliance with every reporting obligation?

A KPI answers its defined measurement question. A filing also needs the scope, fields, evidence and reporting period required by its governing scheme. Reconcile those requirements explicitly instead of treating a dashboard value as the complete submission.

Sources checked

Field guides that apply ISO/IEC 30134

Browse all codes and standards