A UL 9540A report records how the tested battery configuration behaves during thermal runaway and fire exposure. Read it by edition and test level: the sixth edition, published March 13, 2026, adds a developed-fire installation test with pass-fail criteria, while edition five remains active. The report's equipment and test conditions define the evidence available for an installation review. UL 9540 product certification remains a separate determination.

Current edition: ANSI/CAN/UL 9540A, sixth edition (2026), published March 13, 2026; fifth edition also listed active
Updated

Official publisher page

Applies to

Battery manufacturers and laboratories use UL 9540A to characterize thermal-runaway fire and explosion hazards. Designers, fire officials, and owners use the results to support installation instructions and protection decisions. UL Solutions identifies the method in the 2024 IFC and 2026 NFPA 855 framework. The report must be read within the project's governing code and approval basis, including the application and chemistry covered by its test path. UL installation-code FAQ

Key topics

Identify edition five or six before comparing reports

UL Standards & Engagement lists editions five and six as active, with edition six published March 13, 2026. UL Solutions' transition article describes January 1, 2027 as a planned effective date to be established for edition six. That statement is a transition plan, not an installation-code adoption date. Identify the report's actual edition and the edition required by the governing approval basis. A fifth-edition unit-level result and a sixth-edition installation-level result describe different evidence even when a supplier labels both products 'UL 9540A tested.' Publisher edition status; UL transition explanation

Nonresidential testing no longer follows a mandatory unit-level stop

UL Solutions explains that the sixth-edition unit-level test is no longer required for nonresidential BESS; the applicable sequence proceeds from module testing to installation-level large-scale testing. Unit testing remains relevant for residential systems and certain evaluations of active propagation-prevention systems. Read the report's stated application and test rationale rather than rejecting a nonresidential package merely because it lacks the old sequence of four separately completed levels. The publisher's scope also identifies chemistry-specific exceptions to installation-level testing, so the documented test path matters. UL sixth-edition FAQ; Test-sequence scope notes

Post-deflagration openings change the fire exposure

UL Solutions identifies intentional ignition of vented battery gases as a sixth-edition large-scale fire-test change. Its explanation also considers the enclosure after deflagration, when openings affect ventilation and fire growth. The sixth-edition FAQ identifies Annex C as a large-scale deflagration test for BESS enclosures. In report review, find the documented enclosure condition, opening arrangement, and protection configuration used for the fire exposure. A photograph of an intact cabinet before testing cannot establish the configuration used during the developed-fire portion. UL fire-test explanation; UL Annex C summary

Pass-fail findings belong to the named test and configuration

UL Solutions states that the sixth-edition installation-level large-scale fire test has pass-fail criteria. Record the laboratory's conclusion against those criteria without converting it into a general statement that an ESS is listed or approved for every layout. For indoor equipment, the UL explanation highlights sprinkler density and ceiling height as important test evidence. Preserve those conditions when comparing the tested arrangement with the proposed room, and direct any changed arrangement through the project's design and approval review. UL performance-criteria discussion

How it is used in the field

Build the report index from the laboratory's equipment description, not the sales brochure: report number, edition, test level, cell and module identifiers, enclosure, and tested protection. Preserve the arrangement drawings with the laboratory's findings. A matching cabinet name with a changed cell or suppression arrangement leaves an evidence mismatch that the report summary alone will not expose.

Compare test conditions with design conditions in the same units. A report showing 1.0 m separation does not demonstrate the proposed 0.8 m arrangement; flag the 0.2 m reduction for the design and approval review. These are comparison inputs, not standard clearance limits. For indoor equipment, also compare sprinkler density and ceiling height, which UL identifies as consequential test conditions. Attach each accepted condition to the drawing that implements it.

At turnover, deliver the accepted report set and design comparison with the installed equipment register. Commissioning verifies the installed protective interfaces through the approved project tests. The destructive product fire test remains laboratory evidence; routine acceptance work should not recreate thermal runaway.

Frequently asked questions

Is a fifth-edition report automatically obsolete?

The publisher still lists edition five as active alongside edition six. Identify the test evidence required by the applicable code, certification, and project approval rather than deciding solely from the report's age.

What should replace the phrase 'UL 9540A passed'?

Name the edition, completed test level, equipment configuration, and reported result. That description lets a reviewer distinguish successful unit-level performance from the sixth-edition large-scale installation test and from UL 9540 product certification.