ANVILFIELD Try FieldOS

Electrical

Cable reel receiving and remainder log for the wire yard

Verify the put-up against the footage markers, log the heat number, and keep a running balance on every reel so the field finds the wire instead of re-buying it.

Cable ReelWire YardMaterial ControlReel RemainderFootage VerificationElectrical

Direct answer

Cable reel receiving is the inspection and footage verification you run when a reel of conductor arrives; remainder tracking is the running balance you keep after each pull. Verify the put-up against the printed sequential footage markers, log the heat or lot number, and track every reel's balance by ID and location. Manufacturer markings and project material control govern.

On this pageReel receiving and remainder tracking, and where the money leaksWhat is on a cable reel tag?How do you verify reel footage?Reading the print legendWhat if the tag and the markers disagree?Damage on receiptStorage in the wire yardThe remainder problemHow do you estimate a reel remainder?The reel ID system and the yard mapPull history and the auditable balanceWhen is a reel remainder too short to use?How the pull plan and the reel balance work togetherCopper price, theft, and yard securityField example: reconciling a 1000 ft reelHow do you track reel remainders across a big job?What to documentCommon mistakesField checklistStandards and referencesUnits, terms, and conversions

Key takeaways

  • Verify reel footage off the printed sequential footage markers on the jacket, not the tag put-up; markers are commonly printed every 2 ft.
  • When the tag and the printed markers disagree, act on the markers and document the gap as a receiving exception before signing the freight bill.
  • The heat or lot number is the traceability back to the production run, and is what a claim, recall, or as-built record hangs on.
  • Give every reel a unique ID tied to a conductor spec, yard location, and live balance so the field pulls from partials instead of re-buying wire.
  • Estimate a remainder three ways in order of trust: read the marker at the cut end (~2 ft accuracy), subtract logged pulls from put-up, or weigh it.

Reel receiving and remainder tracking, and where the money leaks

A cable reel arrives with a stated footage on the tag, and that number is the start of a money trail that runs the length of the job. Verify the footage on receipt, then keep a running balance every time you pull off the reel. Do neither and you bleed cash two ways. You pay for wire that was never on the reel, and you re-buy wire you already own because nobody knows the 240 ft you need is sitting on a partial reel in the back of the yard.

On a data center job the conductor is one of the largest material lines on the whole project. We are talking thousands of feet of large copper feeder at a price that moves with the commodity market. A 1 percent error in footage across a job that size is real money, and the errors are rarely as small as 1 percent. Reels come in short of the tag. Partial reels get pushed behind a Conex and forgotten. Two crews cut off the same reel and nobody logs it.

The fix is not complicated, but it has to be a discipline, not a good intention. Every reel gets received against its tag and its markers. Every reel gets an ID and a yard location. Every pull comes off a known reel and gets logged against that reel's balance. That is the whole system, and the jobs that run it do not re-buy wire they already paid for.

What is on a cable reel tag?

The reel tag is the conductor's birth certificate, and it is the first thing you read before the forklift even sets the reel down. It states the put-up, which is the manufacturer's stated length on that reel, along with the conductor size in AWG or kcmil, the metal, the insulation type and its voltage rating, the color, and the manufacturer. On most reels the UL certification mark lives on the tag or the flange, and that mark, not the print on the jacket, is the means of identifying UL coverage. The surface print is a supplemental marking.

The number that earns its keep on the tag is the heat or lot number. That is the traceability back to the production run, and it is what a claim or a recall hangs on. If a batch of conductor has a problem, the heat number is how you find every reel from that run before it goes in the pipe.

Receiving is not done when you confirm the tag is legible. It is done when the tag matches two other documents: the purchase order and the approved submittal. The PO says what you ordered. The approved submittal says what the engineer accepted. A reel that matches the PO but not the approved submittal is the wrong wire with correct paperwork, and it becomes your problem the day the inspector pulls the submittal.

How do you verify reel footage?

Verify reel footage off the printed sequential footage markers on the jacket, not off the tag alone. Most building wire is marked at a regular interval, commonly every 2 ft, with a running number printed in the legend. There are two systems and you have to know which one you are reading. Descending markers count down from the put-up toward the core, so a number like 0250 means roughly 250 ft remain toward the core end. Ascending markers count up from the start, so the number tells you how many feet were produced to that point, and you subtract from the put-up to get what is left.

On a full reel you cannot unspool the whole thing to count, so you read the two ends. The outer end of a descending reel should read at or near the full put-up, and the inner end at the core reads near zero. If the outer end of a 1000 ft put-up reads 0600, that reel is not full, whatever the tag says. Read both ends, write down both numbers, and you have bracketed the footage without rolling out a single foot of wire.

The markers are the ground truth because they are printed continuously down the conductor. The tag is a human-entered summary, and humans transpose digits. When the two disagree, the markers win, and the next section is what you do about it.

Reading the print legend

The print legend is the line of text printed or embossed along the cable jacket, and it repeats every few feet down the whole length. It carries the manufacturer name, the conductor size, the metal, the insulation type, the voltage rating, the temperature rating, and usually the sequential footage marker. On a 500 kcmil THHN feeder the legend reads something close to the size, CU or AL, THHN or THWN-2, 600 V, the temperature columns, the maker, and the UL marking, all in one running line.

Read the legend to confirm the conductor is what the tag and the submittal say it is. The tag can be swapped or wrong. The legend is printed into the product at the factory and travels with the wire, so it is the harder thing to fake and the better thing to trust on the spec. A reel tagged THHN with a jacket legend that reads something else is a reel you set aside, not pull.

One caution that catches people: the UL letters printed on the jacket are a supplemental mark and are not by themselves proof of UL coverage. The certification is carried by the mark on the reel, the flange, or the tag. So you read the legend for the spec and you read the reel mark for the listing, and you need both.

What if the tag and the markers disagree?

When the reel tag and the printed footage markers disagree, the markers are the number you act on, and the gap is the number you document. The markers are printed continuously as the conductor runs through the line, so they track the real length. The tag is keyed in by a person and is the thing that gets transposed, rounded, or carried over from the wrong reel.

So read the ends, take the marked footage, and if the markers say the reel holds less than the tag claims, you have a short reel. That is a receiving exception, and it goes on the receiving report with the reel ID, the tag put-up, the marked footage at both ends, and a photo of the legend. Catch it on the dock and it is the supplier's problem. Sign for it clean, cut into it, and discover the short two weeks later, and it is your problem to prove, which you usually cannot.

There is a real-world wrinkle. Markers can carry their own small errors, and a reel can have a splice the factory allows within limits, which throws off the simple end-to-end read. For receiving you are not chasing a single foot. You are catching the reel that is 80 ft short on a 1000 ft put-up, because that size of error is common enough and large enough to matter. Bracket it, document it, move on.

Damage on receipt

Inspect every reel for damage before you sign the freight bill, because the signature is where your standing on a claim is won or lost. The carrier's and the supplier's claim window starts at delivery, and a clean signature on damaged freight is a waiver you will regret.

Look at the conductor first. Jacket nicks and gouges from rough handling, flat spots where the reel was dropped and the wire crushed against the flange, and abrasion from a reel that shifted in transit. On insulated conductor a nick into the insulation is a fault waiting for the megger or the energization. Look at the reel itself next: a cracked flange, a bent arbor hole, a reel that will not spin true, all of which turn into a pull problem and a damage risk later.

Then the ends. The conductor ends should be sealed, with end caps or heat-shrink, to keep moisture out of the strands. An open end that sat in the rain wicks water down the conductor, and on a long reel that contamination travels farther than you would think. Note water staining on the reel, evidence of standing water, and UV chalking on a reel that sat in someone's yard before it reached you.

Photograph anything you find, write it on the receiving report and the delivery receipt, and note it before you sign. The claim window is short and it does not reopen because you found the damage when you finally pulled the reel.

Storage in the wire yard

Store reels on their flanges, off the ground, ends sealed, out of standing water and direct sun. A reel laid flat on its side bears the conductor's weight on the bottom wraps and flat-spots them, and it lets water pool in the wraps. Standing on the flanges, the reel carries its load through the flange and the wire stays round.

Off the ground matters because the yard floods. Dunnage, racks, or pallets keep the bottom of the reel out of the mud and the standing water that shows up after every rain. Keep the ends sealed the whole time the reel sits, because an end that loses its cap in storage wicks moisture for weeks before anyone pulls it. UV degrades the jacket on conductor that sits outside for months, so the long-lead reels you stage early are the ones that need cover.

Now the blunt part. A wire yard full of copper is a target. Copper theft tracks the commodity price, and a data center job stages large copper feeder months ahead of the pull, which is exactly the high-value, low-attention inventory thieves go after. The reels that sit longest are the ones nobody is watching, and they are the most expensive ones on the site. Storage and security are the same problem on a copper job.

The remainder problem

After a pull, the reel has a balance left on it, and that balance is the part of the job that quietly loses money. A 1000 ft reel that gives up a 620 ft feeder still has roughly 380 ft of good conductor on it. That remainder is an asset. Track it and it is the next feeder. Lose track of it and it becomes scrap, or worse, it becomes a reorder for wire you already own.

The expensive version plays out every day on jobs that do not track balances. The field needs 240 ft of 500 kcmil. There are three partial reels in the yard that together hold 900 ft of exactly that conductor, but nobody knows what is on them, so a new reel gets ordered, delivered, and pulled, and the partials sit until they are scrapped. You paid for the new reel and you threw away the old ones.

Remainder tracking is the discipline that closes that gap. Every reel has a known balance, and that balance is searchable, so the question is not whether you have the wire. The question is which reel has it and where it is parked. On a big job that single capability, knowing what is on the partials, is the difference between buying conductor once and buying it twice.

How do you estimate a reel remainder?

Estimate a reel remainder three ways, in rough order of how much you should trust them: read the markers, subtract the measured pulls from the put-up, or weigh it. Each has a place and an error band.

Reading the printed footage marker at the cut end is the most direct. After a pull, the marker on the conductor left on the reel tells you the balance straight off, descending or ascending. This is the best field method when the end is reachable and the marker is legible, and it is good to within the marker interval, a couple of feet.

Subtracting pulls from the put-up is the bookkeeping method. Start from the verified received footage, subtract every measured pull logged against the reel, and the running difference is the balance. It is only as good as your pull measurements and your discipline in logging them. Miss one pull and the balance is wrong from then on, which is why the log has to be live.

Weighing is the fallback for a reel with no legible marker. Net weight, which is gross weight minus the reel tare stamped on the flange, divided by the conductor's published weight per foot, gives length. It is the least precise because tare varies, yard scales are rough, and the per-foot weight has to be the manufacturer's actual figure for that conductor. For 500 kcmil bare copper that is roughly 1.5 lb per foot, but use the published number for the exact wire. Weighing tells you about 300 ft, not 305.

MethodHowAccuracy
Read the footage markerRead the printed marker at the cut endBest; within the marker interval (~2 ft)
Put-up minus pullsSubtract logged measured pulls from verified footageGood if every pull is measured and logged
Weigh the reelNet weight divided by published weight per footRoughest; tare and scale error

The reel ID system and the yard map

Tag every reel with a unique ID the day it is received, and tie that ID to a conductor spec, a location, and a balance. The ID is what everything else hangs on. Without it you have a yard full of look-alike reels and no way to say which 500 kcmil reel has the 240 ft. With it, every pull, every balance, and every move references one number.

The yard map is the other half. A reel ID with no location is a balance you cannot find, and on a multi-acre site that is the same as not having it. Give the yard zones, mark where each reel sits, and update the location when a reel moves. The crew that needs 240 ft should be able to look up the conductor, see which reel has it, and read the row and zone where it is parked, without walking the whole yard reading tags.

This is exactly the kind of running ledger the reelremainderlog tool is built to keep, with the reel ID, the spec, the verified footage, the location, and the live balance in one place the field can search. The point is not the tool. The point is that the ID, the location, and the balance live together and stay current, whether that is an app or a clipboard that someone actually maintains.

Pull history and the auditable balance

Log what comes off each reel, by feeder or circuit, every time. The pull history is what makes the balance auditable instead of a guess. A reel that started at 1000 ft and reads 210 ft today should have a list of pulls that add up to the 790 ft that left, each tied to the feeder it became. When the numbers do not reconcile, the log tells you a pull went unrecorded, and you find it before it becomes a mystery shortage.

The pull history also feeds the as-built. The conductor that is in feeder F-12 came off a specific reel with a specific heat number, and that linkage is what supports the record when someone asks, a year later, what is actually in that raceway. On a job with insulation testing and commissioning, tying the installed conductor back to its reel and heat number is the kind of traceability that turns a question into a lookup.

Keep the log live, at the point of the pull. A pull measured and logged when the crew cuts it is accurate. A pull reconstructed from memory at the end of the week is fiction with a number on it. The discipline is the same one that makes the whole system work: record it when it happens, against the reel ID, or do not bother having a system at all.

When is a reel remainder too short to use?

A remainder is too short to use when it cannot reach the shortest run left on the job plus the waste you need for terminations and slack. That cutoff is a job decision, not a fixed number, and you set it from the schedule of remaining pulls. If the shortest feeder left is 150 ft, anything under that plus tails and pulling waste is scrap, and pretending otherwise just clutters the yard.

Set the cutoff and apply it. Remainders above the cutoff stay in inventory as usable stock and get pulled before you order new conductor. Remainders below it get cut from the active list and staged for scrap, because a 40 ft piece of 500 kcmil is not going to become a feeder and it is taking up a reel and a yard space.

The scrap is not nothing. Copper scrap carries real value that tracks the commodity price, and on a big job the accumulated short ends add up to a meaningful credit. The discipline is to scrap deliberately, weigh it, and capture the value, not to let partials disappear off the back of the yard where the only person who profits is whoever hauls them. A controlled scrap program turns the unavoidable waste into a recovery instead of a loss.

How the pull plan and the reel balance work together

The pull consumes the reel, so the pull plan and the reel balance are two views of the same conductor. The pull plan sizes the run, sets the tension, and tells you how much conductor the feeder needs. The reel balance tells you which reel can give it up without coming up short in the middle of a pull. Run them together and you never stop a pull at a pull box because the reel ran dry 40 ft from the end.

Coming up short mid-pull is one of the worst outcomes on a feeder job. You have conductor in the conduit, tension on the line, and not enough reel to finish, so now you are splicing where you should not, or pulling it all back out. The reel balance check before the pull is what prevents that. Confirm the reel holds the planned length plus waste before the head goes in the pipe.

The tension card covers the mechanics of the pull, the calculated tension and sidewall pressure that keep you from damaging the conductor. The reel balance covers the inventory side, whether the reel has the length. The cable pull planning tension card guide handles the first. This guide handles the second. On a real pull you need both answered before you rig the tugger, and the voltage drop field guide is where the conductor size that drives all of it gets decided.

Copper price, theft, and yard security

Copper is priced as a commodity, so the value of the conductor staged in your yard moves every day the market moves. That has two consequences nobody likes. The first is that re-buying wire you already own costs more than it did when you first bought it, so a lost remainder is not a wash. It is a loss at today's higher price. The second is that the staged copper is a theft target proportional to its value.

Theft on copper jobs is organized and it tracks the price. Thieves go for the staged, long-lead, high-value reels that sit unwatched, and a data center job stages exactly that kind of inventory months ahead. Lock the yard, light it, watch the cameras, and account for the reels by ID so a missing reel shows up as a discrepancy in the log and not as a surprise on pull day.

Inventory accuracy is itself a security control. A yard where every reel has an ID and a balance is a yard where a stolen or walked-off reel is visible fast, because the count does not reconcile. A yard with no tracking can lose a reel of 500 kcmil and not know until the crew goes looking for wire that is not there. The same ledger that saves you from re-buying remainders is the one that tells you when copper has gone missing.

Field example: reconciling a 1000 ft reel

A reel of 500 kcmil copper THHN is received with a tag put-up of 1000 ft. On receiving, the outer end marker reads 0998 and the inner read is not reachable, so the reel is accepted at the tag with the outer marker noted. It gets reel ID R-217 and a yard location of Zone C, Row 4.

Two pulls come off it. Feeder F-12 is measured and cut at 380 ft and logged against R-217. Feeder F-15 is measured at 410 ft and logged. By the bookkeeping method the balance is 1000 minus 380 minus 410, which is 210 ft. The crew then reads the printed marker at the current cut end and it shows 0205. The two methods agree within 5 ft, which is normal pulling waste and slack, so the balance is recorded as roughly 205 ft and R-217 stays in inventory as a usable partial.

Three weeks later a 180 ft run comes up. Instead of ordering a reel, the field searches the log for 500 kcmil, finds R-217 holding about 205 ft in Zone C Row 4, and pulls the 180 ft from it. That single lookup avoided a new reel order and turned a partial that most jobs would have scrapped into the exact conductor the run needed. The leftover 25 ft falls under the scrap cutoff and gets weighed into the copper recovery.

EventFootageRunning balance
Received, tag put-up1000 ft1000 ft (outer marker 0998)
Pull F-12minus 380 ft620 ft
Pull F-15minus 410 ft210 ft
Marker read at cut end0205~205 ft (agrees within 5 ft)
Pull 180 ft run from R-217minus 180 ft~25 ft (below scrap cutoff)

How do you track reel remainders across a big job?

Track remainders across a big job by making one ledger the single source of truth for every reel, and by keeping it live at the point of the pull. The ledger holds the reel ID, the conductor spec, the heat number, the verified received footage, the yard location, the pull history, and the current balance. Every crew reads from it and every pull writes to it. The moment there are two lists, a clipboard in the trailer and a different one in someone's truck, the balances diverge and the system is dead.

The hard part is not the format. It is the discipline of updating it when the wire is cut, not at the end of the shift. A balance updated live is a balance the next crew can trust. A balance updated from memory on Friday is a number that drifts a little every week until it is useless. The jobs that get this right treat the reel log like the inspection record it is, with the same expectation that it is current and correct.

Tie the reel ledger into the broader material control on the project so receiving, inventory, and the as-built all reference the same reel IDs. A tool like tradeos exists to keep that field record in one place across the crews and the office, but the principle holds with any system: one ledger, one source of truth, updated when it happens.

What to document

The reel record is what answers the question months later, when a feeder is in question or the audit asks what is in a raceway. If it is not written against a reel ID, it did not happen, and you will be reconstructing it from memory under pressure.

Capture, for every reel: the reel ID, the full conductor spec, the heat or lot number, the tag put-up, the verified footage from the markers, the yard location, every pull with its measured length and the feeder it became, and the current balance. Add the receiving date and any damage exceptions noted on the dock. That record is the inventory, the traceability, and the as-built backup in one place.

Field to recordWhy it matters
Reel IDThe identifier every pull, balance, and move references
Conductor spec (size, metal, insulation, voltage)Confirms the reel against PO and approved submittal
Heat or lot numberTraceability for claims, recalls, and the as-built
Tag put-up vs verified footageCatches the short reel and the receiving exception
Yard locationA balance you cannot find is a balance you do not have
Pulls, by feeder, measured lengthMakes the balance auditable and feeds the as-built
Current balanceTells the field what is available without a count

Common mistakes

  • Trusting the tag put-up over the printed footage markers when the two disagree.
  • Signing the freight bill clean on a reel with jacket damage, flat spots, or open ends.
  • Keeping no remainder balance, so partial reels become scrap or get re-bought.
  • Re-buying conductor you already own because nobody can find the partial that has it.
  • Storing reels on their sides on the ground, ends unsealed, in standing water and sun.
  • Logging pulls from memory at the end of the week instead of at the cut.
  • Letting partial reels and short ends walk off the yard instead of weighing them into scrap recovery.
  • Reading an ascending marker as remaining footage, or a descending marker as footage used.

Field checklist

0 of 10 complete

Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.

Standards and references

This is more a material control discipline than a code exercise, so most of what governs it is the manufacturer's marking practice and the project's own procedures, with the code controlling the conductor itself. Keep the citations to what actually applies and verify the rest.

The markings you verify against come from the manufacturer's print-legend and put-up practice. Sequential footage marking, commonly at a 2 ft interval in ascending or descending order, and the data on the reel tag are how the industry conveys length, size, and rating. That practice governs what you read on the jacket and the flange.

The conductor itself is marked under product safety standards. The NEC, NFPA 70, sets conductor marking requirements in its conductor article, Article 310, by topic, covering how size, insulation type, and rating are identified, while UL listing and the underlying UL and ASTM conductor standards govern the construction and the marking method. The UL certification mark on the reel, flange, or tag is the means of identifying UL coverage; the UL letters printed on the jacket are a supplemental mark, not by themselves proof of listing. Confirm the exact article and section against the adopted code edition, because the numbering shifts between cycles, and treat the ASTM and UL conductor standards by the conductor type you are actually receiving.

The rest is your company and project material control procedures: receiving, claim windows, inventory, and scrap. Those documents, not the code, govern how you receive, track, and reconcile a reel.

Units, terms, and conversions

The yard and the paperwork use a handful of terms that mean specific things, and mixing them up is how a balance goes wrong.

Footage is in feet on US reels and meters on imported conductor, so confirm the unit before you compare a marker to a tag. Conductor size is AWG for smaller conductors and kcmil for larger, where kcmil is thousands of circular mils and means exactly the same thing as the older MCM. Weight is in pounds per foot for the length-by-weight method, and the reel tare is stamped on the flange.

Put-up
The manufacturer's stated length of conductor on the reel, shown on the tag
Remainder / balance
The conductor left on a reel after one or more pulls
Print legend
The text printed along the jacket: maker, size, type, rating, and footage marker
Sequential footage marker
The running number printed every couple of feet, ascending or descending
Heat or lot number
The production-run identifier used for traceability and claims
kcmil / MCM
Thousand circular mils, the size unit for large conductors; the two terms are identical
Tare
The empty reel's weight, stamped on the flange, subtracted to get net conductor weight

Related tools

Next step: Follow planned feeder work

FAQ

How do I verify reel footage?

Verify reel footage off the printed sequential footage markers on the jacket, not the tag alone. Read the number at both reachable ends, since markers run ascending or descending at roughly a 2 ft interval. Compare the marked footage to the tag put-up, and if they disagree, trust the markers and document the gap.

What is a print legend?

A print legend is the line of text printed or embossed along a cable jacket that repeats every few feet. It carries the manufacturer, the conductor size, the metal, the insulation type, the voltage and temperature rating, and usually the sequential footage marker. Read it to confirm the conductor matches the tag and the approved submittal.

How do I track reel remainders?

Track reel remainders by giving every reel an ID, a yard location, and a running balance in one shared ledger. Update the balance live at each pull, subtracting the measured length from the verified footage. Then any crew can search the conductor spec, find the reel that holds it, and pull from a partial instead of ordering new wire.

What if the tag and the markers disagree?

When the reel tag and the printed markers disagree, act on the markers and document the gap. The markers are printed continuously as the conductor runs, so they track real length, while the tag is keyed in by hand and gets transposed. A reel that reads short on the markers is a receiving exception; note it before you sign the freight bill.

How do I estimate how much wire is left on a reel?

Estimate the remainder three ways: read the footage marker at the cut end, subtract logged pulls from the verified put-up, or weigh the reel. The marker is most accurate, within a couple of feet. Weighing is roughest: net weight divided by the conductor's published weight per foot, after subtracting the reel tare.

When is a reel remainder too short to use?

A remainder is too short when it cannot cover the shortest remaining run plus terminations and pulling waste. That cutoff is set from your schedule of pulls, not a fixed number. Remainders above it stay as usable stock; shorter ends get scrapped. Copper scrap holds real value, so weigh and capture it rather than losing it.

How do I store cable reels in the yard?

Store cable reels standing on their flanges, off the ground on dunnage or racks, with the conductor ends sealed and out of standing water and direct sun. Lying a reel flat flat-spots the bottom wraps and pools water. An unsealed end wicks moisture down the strands, and UV degrades the jacket on reels staged for months.

What is the put-up on a cable reel?

The put-up is the manufacturer's stated length of conductor on the reel, printed on the reel tag. It is the starting number for footage verification, but it is human-entered and not always right. Confirm it against the printed sequential footage markers on receipt, because the markers, not the put-up, are the ground truth for length.

Why does reel remainder tracking save money on a data center job?

Reel remainder tracking saves money because conductor is one of the largest material costs on a data center job, and untracked partials get re-bought or scrapped. When every reel's balance is searchable, the field pulls the 240 ft it needs from a partial it already owns instead of ordering a new reel at the current copper price.

How do I match a reel to the submittal on receipt?

Match a reel by reading the tag and the jacket print legend, then checking both against the purchase order and the approved submittal. The PO confirms what you ordered; the submittal confirms what the engineer accepted. A reel that matches the PO but not the approved submittal is the wrong conductor with correct paperwork, and it fails at inspection.

People also ask

Codes cited in this guide

This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.