Field glossary · material
Corrosion inhibitor
A corrosion inhibitor is a chemical treatment that slows metal loss in circulating water or coolant. For iron and steel in closed cooling water above pH 7.0, Veolia publishes a nitrite residual of 600 to 1,200 ppm as NO2-. The reporting basis matters: 900 mg/L as sodium nitrite is about 600 mg/L as nitrite ion. Residual testing measures the treatment present; coupon results and metal trends supply separate performance evidence.
A chemical such as nitrite or molybdate that forms a protective film on the loop metal and is held to a target residual
Which metals does the inhibitor target cover?
Veolia's Water Handbook gives 600 to 1,200 ppm as NO2- for nitrite protection of iron and steel in closed cooling water when pH is above 7.0. The stated metals matter: the same chapter describes different treatment needs for steel-copper couples and aluminum-containing systems. Record the covered metallurgy with the target rather than transferring a steel-only range to a mixed-metal loop.
Veolia's closed-loop molybdate discussion gives a separate control range of 200 to 300 ppm as MoO4^2-, with pH normally 7.0 to 9.0. A 250 ppm molybdate result and a 250 ppm nitrite result belong to different acceptance bands. Name the measured ion and the covered metallurgy on the hydronic sampling record; a blended product's feed concentration is another quantity again.
Why 900 ppm can mean 600 ppm
Hach's nitrite test instructions convert a result expressed as NO2- to the sodium-nitrite basis, NaNO2, by multiplying by 1.5. Converting in the opposite direction means dividing by 1.5. Write the chemical formula after mg/L on the sample sheet, the laboratory report and the controller target.
A laboratory reports 900 mg/L as NaNO2. Division by 1.5 gives 600 mg/L as NO2-, at the lower end of Veolia's published iron-and-steel range. Reading the unconverted 900 against an NO2- target would overstate the nitrite-ion concentration by 50%. This is a reporting conversion; it does not calculate the volume of a commercial treatment product to add.
Preserve the laboratory's original value beside the converted value. When a treatment supplier changes the reporting basis, convert the historical series before interpreting a sudden rise or fall. A change in units should not become a chemical-feed adjustment.
Test range and reagent strength both affect the result
Hach Method 8351, April 2015 Edition 8, measures 100 to 2,500 mg/L as NaNO2 in cooling-tower waters using ceric-acid titration. With its 10 mL sample, 200 titrator digits multiplied by 2.15 gives 430 mg/L as NaNO2. Applying the 5 mL sample's 4.31 multiplier to those same digits would report 862 mg/L. Record sample volume, multiplier and reporting formula together. Use the coolant formulation's specified analytical method for glycol and specialty fluids.
Hach Method 8351 says to verify ceric-titrant normality before use and recommends monthly standardization because its strength can decrease during storage. Its separate accuracy check uses a known sodium-nitrite solution to verify the combined procedure, reagents, apparatus and technique. A repeatable endpoint does not correct an inaccurate titrant strength or sample-volume multiplier.
Separate dilution from loss of active nitrite
Draining 20% of a well-mixed loop and refilling that volume with inhibitor-free water reduces a 1,000 mg/L residual to 800 mg/L before chemical consumption is counted. Compare the measured decline with the logged drain-and-refill volume. This mass balance helps distinguish ordinary dilution from a loss that needs another explanation.
Veolia identifies microbial oxidation of nitrite as a cause of falling inhibitor levels and biological fouling. A declining residual with little replacement water therefore deserves a biological result alongside the chemistry history. In a technology-cooling loop, retain the coolant-specific tests and acceptance limits rather than interpreting every additive through the nitrite example.
Distinctions
- Conductivity
- Conductivity responds to the combined dissolved ionic content. A nitrite result identifies one treatment constituent; the two readings serve different acceptance checks.
- Scale inhibitor
- Corrosion control limits metal loss; scale control limits mineral deposits. Veolia's open-system handbook treats these as separate functions even when a treatment package combines them. A clean heat-transfer surface and a low corrosion-coupon loss establish different results.
- Concrete corrosion inhibitor
- A concrete admixture is specified and dosed through the concrete mixture. Use the concrete admixtures guide for that application; circulating-water residual units do not describe its dosage.
Frequently asked questions
Does an inhibitor residual inside its target prove corrosion has stopped?
A residual establishes the measured chemical concentration. Veolia's Water Handbook identifies corrosion coupons, corrosion-rate instruments and iron or copper trends as measures of corrosion performance. Pair the residual with that performance record; an in-range assay alone does not demonstrate low metal loss.
How long can a nitrite sample wait before testing?
Hach Method 8351 calls for prompt analysis; when that is impossible, it specifies storage at or below 6 degrees C for no more than 24 hours, followed by warming to room temperature before analysis.
Sources checked
- Veolia Water Handbook, chapter 32: Closed Recirculating Cooling Systems, nitrite residuals and metallurgy
- Hach DOC326.97.00102: nitrite reporting conversions, page 29
- Hach DOC316.53.01178: Method 8351, April 2015 Edition 8, range, standardization and sample storage
- Veolia Water Handbook, chapter 31: separate corrosion and deposit control, corrosion coupons and metal monitoring
Also defined as
- Datacenter: The additive package that passivates the loop metals, such as azoles for copper, matched to the metallurgy and consumed over time