Field glossary · component
Grounded conductor
A grounded conductor belongs to the power circuit and has an intentional system connection to ground. The label includes both a wye neutral and a grounded corner of a delta winding. Those conductors serve different circuit arrangements, even when identification colors look alike. Establish the winding connection and actual current path before diagnosing a voltage reading; closeness to ground potential says little about the current the conductor carries.
The neutral, a current-carrying conductor, distinct from the EGC and bonded to it only at the service or derived source
When a grounded conductor is not a neutral
OSHA 1910.399 defines a grounded conductor by its intentional grounding, without limiting the term to a neutral. A neutral is associated with the system's neutral point. A grounded delta phase has no such neutral function, even though it meets the grounded-conductor definition.
On a 120/240 V center-tapped supply, the grounded midpoint serves the two 120 V legs. On a corner-grounded delta, a phase corner is grounded instead. Reading both arrangements as an ordinary neutral invites incorrect switching and equipment selection. Identify the winding connection on the electrical one-line before labeling the return conductor.
Identification and interruption are separate requirements
OSHA 1910.304(a)(1) requires identification that distinguishes the grounded conductor from the other conductors. For overcurrent devices, 1910.304(f)(1)(ii) requires simultaneous opening of all circuit conductors if the grounded conductor is interrupted, with an exception for motor running-overload protection. That provision addresses protective-device operation; it is not a complete rule for every neutral switching arrangement.
Identification is not a voltage test. Load current through conductor impedance produces a difference between neutral and the nearby bonding reference. For a return path of 0.10 ohm carrying 12 A, the calculated drop is 1.2 V. That result describes the assumed current and resistance, not an allowable neutral-to-ground voltage threshold.
Why an ordinary neutral can overheat without a phase overload
ABB's K-factor transformer paper identifies triplen harmonics as additive neutral current in a three-phase system. With 6 A of in-phase third harmonic from each phase, the neutral carries 18 A of that harmonic even when the fundamental phase loads balance. Record the harmonic component separately from the overall RMS reading so 'balanced phases' does not conceal neutral heating.
The feeder design guide addresses harmonic loading. The diagnostic distinction is to measure and record the neutral's actual RMS current and harmonic content, rather than infer it from balanced phase amperes. Keep that load-path investigation separate from locating an unintended connection to equipment metal. One concerns the grounded conductor's load; the other concerns an additional return path.
Distinctions
- Equipment grounding conductor
- The EGC connects equipment metal into the fault-return network. It is not the intended conductor for normal circuit current.
- Grounding electrode conductor
- The GEC reaches the electrode system. Grounded-conductor identification does not turn a neutral into an electrode conductor.
Frequently asked questions
Does zero voltage to ground prove the neutral is disconnected?
No. A connected neutral can be close to ground potential and still carry substantial current. The circuit and test arrangement establish isolation.
Does insulation color establish the conductor's function?
Read the identification together with the source winding and terminations. A grounded delta phase and a wye neutral both qualify as grounded conductors, but they serve different circuit roles.
Sources checked
Also defined as
- A system conductor intentionally grounded; often the neutral, but also a grounded phase conductor in some systems