ANVILFIELD Try FieldOS

Electrical

Grounding vs bonding explained for electricians

The difference the whole trade confuses: bonding gives fault current a path back to the source to trip the breaker, grounding ties the system to earth, and the dirt clears nothing.

Grounding vs BondingBondingEquipment Grounding ConductorNEC 250Electrical

Direct answer

Bonding connects metal parts together so they sit at the same potential and gives fault current a low-impedance path back to the source, which is what trips the breaker. Grounding connects the system to the earth for lightning, surge, and voltage reference. The earth does not clear faults; the bonded path does.

Key takeaways

  • Bonding ties metal together for a low-impedance fault path back to the source, which trips the breaker; grounding ties the system to earth.
  • A ground rod cannot clear a fault: a 120 V fault across 25 ohms of soil drives under 5 A, far below breaker trip.
  • The equipment grounding conductor (EGC) is a bonding conductor sized from the overcurrent device (NEC 250.122), not from the earth or load.
  • Bond neutral to ground at exactly one place per system: the main bonding jumper at the service, a system bonding jumper at each separately derived source.
  • A second neutral-to-ground bond downstream creates objectionable current on the grounding system; NEC 250.6 and 250.24(A)(5) prohibit it.

What is the difference between grounding and bonding?

Bonding connects metal parts together so they sit at the same potential and so fault current has a low-impedance path back to the source. Grounding connects the electrical system to the earth. Those are two different jobs, and mixing them up is the most common misunderstanding in the trade, including among people who have wired for twenty years.

Hold onto one fact and the rest falls in line: the breaker trips on the bonding, not on the earth connection. A hot conductor shorts to a metal enclosure, the current runs back through the bonded equipment grounding conductor to the source, the amperage spikes, and the overcurrent device opens in milliseconds. The rod driven in the dirt does nothing useful in that sequence. Cut every ground rod off a building and a line-to-ground fault still clears, as long as the bonded path home is intact.

So what is the earth for? Lightning, surges, and a stable voltage reference. The earth connection gives a strike and a surge device somewhere to dump energy and holds the system near earth potential so the whole thing does not float around. Keep those two purposes apart and Article 250 stops being a pile of rules to memorize.

Why everyone confuses the two

The confusion is baked into the language. The NEC uses the word ground loosely across a dozen contexts, and the trade picked up the habit. We say go ground that out, ground the box, run a ground, check the ground, and we mean a different thing almost every time. Most of the time the thing we actually mean is bonding.

Then there is the green wire. In most people's heads the green or bare conductor is the ground, one thing, doing one job. It is not. That conductor is doing bonding work, tying metal together and carrying fault current home, and on the vast majority of circuits it never touches the earth at all. It runs back to the panel, to the main bonding jumper, and stops. Calling it the ground hides what it does for a living.

The deeper trap is that three different NEC conductors all carry the word grounding or grounded in their names, and they do three different jobs. The grounded conductor, the equipment grounding conductor, and the grounding electrode conductor are not interchangeable, and a crew that treats them as one fuzzy concept ends up sizing the wrong thing or bonding in the wrong place. The terms section later pulls those three apart on purpose, because that one distinction clears up most of the fog.

What bonding actually does

Bonding ties all the non-current-carrying metal in an installation together: enclosures, raceways, boxes, equipment frames, metal that could become energized. The NEC defines bonding in Article 100 as the permanent joining of metallic parts to establish electrical continuity and conductivity. In the field that means two specific outcomes, and they matter for two different reasons.

First, equal potential. When every piece of metal is tied together, there is no dangerous voltage difference between the things a person can touch at the same time. Touch the panel and the conduit beside it during a fault and both are at the same potential, so no current drives through the body. That is the touch-safety half, and it is why bonding is about more than just tripping a breaker.

Second, the fault path. Bonded metal forms a continuous low-impedance route from any point a fault could happen back to the source. That route is what lets enough current flow to operate the overcurrent device fast. Without it, the faulted enclosure just sits there energized, the breaker holding because the current is too small to trip it, waiting for the next person to become the path. Bonding is the difference between a fault that clears and a fault that lies in wait.

Is the equipment grounding conductor really a ground?

The equipment grounding conductor is misnamed. It is a bonding conductor wearing a grounding label, and understanding that is half the battle with Article 250. The EGC carries fault current back to the source to trip the overcurrent device. It has almost nothing to do with the earth.

Trace it. The EGC, whether it is a green wire, a bare conductor, or the metal raceway itself, runs from the equipment back to the panel, lands on the ground bar, and through the main bonding jumper ties to the grounded conductor and the source. On a fault, current flows hot to enclosure to EGC to neutral to source, and around it goes, hundreds or thousands of amps, and the breaker opens. The earth is nowhere in that loop. The NEC even recognizes metal conduit, EMT, and cable armor as equipment grounding conductors, which makes the point plain: a piece of steel pipe is not grounding anything to the planet, it is bonding the system together and carrying fault current.

Sizing follows the same logic. The EGC is sized from the overcurrent device protecting the circuit, commonly from the table at 250.122, because its job is to survive the fault current long enough for that device to trip. It is not sized from the earth or the load. Call it what it does and the sizing rule stops being arbitrary.

What grounding to earth actually does

Grounding, the connection to earth, does three real jobs and one job it cannot do. The real ones are spelled out in the system-grounding purposes at 250.4(A)(1). It stabilizes the voltage to ground during normal operation so the system rides at a known potential instead of floating. It limits the voltage imposed by lightning and line surges by giving that energy a path to earth. And it gives the system a common reference so separate parts of the installation sit at the same baseline.

The earth connection is made through the grounding electrode system: the concrete-encased electrode, ground rods, qualifying metal water pipe, building steel, a ground ring. The grounding and bonding of the electrode system field guide covers how those electrodes are chosen, bonded, and sized, so this guide stays on the concept and leaves the install detail there.

The one job grounding cannot do is clear a fault. The earth is too poor a conductor to pass the current a breaker needs to trip. People expect the rod to be the safety device, and it is not. Lightning, surge, and reference belong to the earth connection. Fault clearing belongs to the bonded path, every time.

Does a ground rod clear a fault?

No. A ground rod does not clear a fault, and believing it does gets people hurt. The reason is impedance, and the arithmetic is not close.

Earth is a high-resistance conductor. The resistance from a typical driven rod to remote earth runs from a few ohms in good soil to well over 100 ohms in dry or rocky ground. Put a 120 V fault across even 25 ohms of dirt and Ohm's law gives you under 5 A. No breaker trips on 5 A. A 20 A breaker needs many times its rating to open quickly, so the faulted metal just stays energized while a trickle leaks into the ground. The enclosure is live and the rod did nothing to stop it.

Now run the same fault through the bonded path. An equipment grounding conductor and the bonding jumpers present well under an ohm back to the source, so the fault drives hundreds or thousands of amps and the device opens fast. That is a factor of hundreds difference in current, which is the whole reason the code leans on metal and not on soil. The 250.4(A)(5) performance language says it directly: the earth shall not be used as the sole equipment grounding conductor or effective ground-fault current path. The dirt is for lightning and reference. The metal clears the fault.

The effective ground-fault current path

The effective ground-fault current path is the bonded metal route fault current takes back to the source, and Article 100 defines it as an intentionally constructed, permanent, low-impedance conductive path designed to carry fault current from the point of a fault to the source. Read the words. Intentionally constructed, not whatever the current happens to find. Low-impedance, not the earth. Back to the source, not to a rod.

This is the single idea that ties grounding and bonding together correctly. The path is built out of bonded parts: the equipment grounding conductor, the metal raceway where it qualifies, the bonding jumpers, the equipment enclosures, the main bonding jumper, and the source connection. Every one of those is a bonding element. The earth is deliberately left out of the definition because it cannot do the job.

When you walk a system, the question to carry is whether the effective fault path is continuous from the furthest device all the way back to the source with nothing relying on a connection that could open. A painted bonding surface, a missing bonding bushing on a concentric knockout, a loose locknut, a length of conduit nobody bonded at the fitting: any of those is a break in the path that looks fine until the day it has to carry a fault. The path either exists end to end or it does not, and there is no partial credit on the day it matters.

The grounding electrode system in one paragraph

The grounding electrode system is every qualifying electrode at a building, the concrete-encased Ufer, driven rods, metal underground water pipe, building steel, and any ground ring, all bonded together into one earth connection. The point of bonding them together is to hold the whole site at a single reference so no two grounded things sit at different potentials. Under the general rule at 250.50, the electrodes that are present have to be tied together; you do not get to land the Ufer and leave the rods floating.

That electrode system is the grounding half of the picture, the connection to earth for lightning, surge, and reference. It is not the fault-clearing path. The grounding and bonding of the electrode system field guide covers electrode selection, the Ufer timing trap, the two-rod rule, and grounding electrode conductor sizing in detail, so the depth lives there. Here it is enough to place it correctly: the electrode system grounds, the bonded metal clears faults, and the two meet at exactly one point at the service.

Where do you bond the neutral and ground?

The neutral bonds to ground at exactly one place: the service, through the main bonding jumper. That jumper connects the grounded conductor, the neutral, to the equipment grounding conductors and the service enclosure inside the service equipment, under the service-grounding rules at 250.24 and the main bonding jumper rules at 250.28. It can be a screw, a wire, or a busbar, and it is the single point where the system's two halves are tied together.

This connection is what makes the whole fault path work. Because the neutral and the equipment grounding system are bonded here and only here, a fault on any branch returns through the EGC, reaches the main bonding jumper, crosses to the neutral, and gets back to the source. Pull the main bonding jumper and you have an installation full of bonded metal that has nowhere to send the fault current. The bond at the service is the doorway between the bonding system and the source.

After the service, the neutral and the ground stay separate the rest of the way out. That is the rule rookies break in a subpanel, and the next section explains why bonding again downstream is a problem and not a redundancy.

Why the neutral-ground bond goes at one point only

Bond the neutral to ground at the service and nowhere else, because a second bond turns the equipment grounding system into a parallel neutral. That is the failure, stated plainly. It is not a safety upgrade and it is not redundancy. It is a code violation that puts current where it does not belong.

Here is the mechanism. The neutral carries normal load current every second the system runs. With one bond at the service, that current has one way home, the neutral conductor. Add a second neutral-to-ground bond in a subpanel, by leaving the bonding screw in or sharing a neutral and ground bar, and now normal neutral current has two parallel paths back: the neutral conductor and the equipment grounding conductors and metal raceway. Current splits across both. The code calls this objectionable current, and 250.6 requires installations to be arranged to prevent it.

Objectionable current is not harmless. It energizes raceways, equipment frames, and bonding jumpers that were never meant to carry working current, it heats connections that were not sized for it, and it makes a clamp meter read amperage on a ground conductor that should read zero. The load-side rule at 250.24(A)(5) prohibits reconnecting the neutral to ground past the service disconnect for exactly this reason. Subpanels get an isolated neutral bar and a separate ground bar bonded to the can, bonding screw out. The first thing an inspector checks in a subpanel is whether that screw is removed and the neutrals are floated off the can.

The system bonding jumper at a separately derived system

The main bonding jumper is the one neutral-to-ground bond for the service. A separately derived system gets its own version, the system bonding jumper, made at the new source. A transformer secondary and a generator whose transfer switch opens the neutral are separately derived systems: a new source with no direct electrical tie to the supply conductors of another system. Each one establishes its own ground reference and gets one neutral-to-ground bond, under the separately derived system rules at 250.30.

It is the same single-point logic as the service, just repeated at each new source. The system bonding jumper ties the new system's grounded conductor to the equipment grounding conductors at one location, and a grounding electrode conductor runs from there to a nearby electrode. One bond per source, no more and no less. Two bonds on a separately derived system creates the same objectionable-current problem as two bonds on a service.

The generator case is the one that trips people, and it turns entirely on the transfer switch. The grounding and bonding of the electrode system field guide and the separately derived system rules walk the 3-pole versus 4-pole transfer switch decision in detail. The concept to carry here is that a transformer or a neutral-switched generator is just another service as far as the single-point bond is concerned.

Equipment bonding: raceways, fittings, and jumpers

Equipment bonding is the day-to-day work of keeping the fault path continuous through every box, fitting, and length of pipe. The metal raceway often is the equipment grounding conductor. The NEC recognizes rigid metal conduit, intermediate metal conduit, EMT, and several other metallic raceways and cable types as equipment grounding conductors in the list at 250.118, which means the pipe carries the fault current if, and only if, every joint in it is tight and continuous.

The weak points are the fittings. A loose locknut, a coupling that backed off, a connector that was never tightened past hand snug, any of them is a high-resistance link in a path that has to be low-impedance to work. Concentric and eccentric knockouts are a specific trap: the rings left in the box wall make the connection to the enclosure unreliable for fault current, so a bonding bushing and a bonding jumper are required to carry the current around them. Reducing washers and painted enclosures are the same problem, a connection that looks made but cannot pass fault current.

Bonding jumpers fill the gaps the raceway cannot bridge. Expansion and deflection fittings break electrical continuity by design, so they get a bonding jumper across them. The same goes for any place the metal path is interrupted on purpose. The rule of thumb on a rough-in is simple: if fault current would have to jump a gap or trust a questionable mechanical joint, put a bonding jumper there and stop trusting it.

Bonding gas, water, building steel, and CSST

Metal piping and structural steel get bonded so that a fault energizing them has a path back to clear, instead of leaving the pipe or the frame live for someone to grab. Metal water piping is bonded under 250.104, and where the underground metal water pipe qualifies as an electrode it also becomes part of the grounding electrode system. Those are two roles in one pipe: a bonding requirement so it cannot stay energized, and an electrode role where it qualifies.

Interior metal gas piping that is likely to become energized is bonded too, usually through the equipment grounding conductor of the circuit that could energize it, which in practice means the appliance ground does the work. Structural building steel that qualifies gets tied into the bonded system. The grounding and bonding of the electrode system field guide covers the water-meter jumper and the steel bond in more depth, since those are the connections inspectors most often find missing.

Corrugated stainless steel tubing, CSST, deserves its own line because it is a known lightning-damage point. Traditional yellow-jacketed CSST is required to be bonded with a dedicated bonding conductor, commonly sized at least 6 AWG copper and clamped to a fitting at the point it enters, to bleed off the energy a nearby strike induces before it punctures the thin tubing wall. Some listed CSST products carry their own bonding instructions. Follow the manufacturer's listing, because that listing governs and the requirement has changed across editions.

Generators and transformers: grounding and bonding together

A separately derived system is where a clean service install gets undone downstream, because the installer treats grounding and bonding as one thing and bonds in the wrong number of places. A transformer secondary and a neutral-switched generator each need both jobs done: a grounding electrode conductor to a local electrode, which is the grounding half, and a single system bonding jumper at the source, which is the bonding half. Same two jobs as the service, repeated.

The mistake almost always shows up as the bond count. A generator with a 4-pole transfer switch that opens the neutral is a separately derived system, so it needs its own system bonding jumper. Leave that off and the system has no neutral-to-ground bond at all, so a fault on the generator side has no return path. A generator with a 3-pole switch that carries the neutral straight through is not separately derived, so its bond stays at the service. Add a bond at the generator on top of that and you have two, with the objectionable-current problem that follows.

On a transformer the system bonding jumper and the grounding electrode conductor land at the same point, the transformer or the first disconnect. A dry-type step-down transformer in an electrical room is a separately derived system every time. Walk each one and confirm the neutral-to-ground bond exists in exactly one place, because both zero bonds and two bonds are wrong and they fail in different ways.

Ground rings, lightning, and where they fit

A ground ring is a bare conductor, commonly at least 20 ft of 2 AWG copper, encircling a building in direct earth contact, and where one is present it is part of the grounding electrode system. It is a grounding element, not a bonding element. Its job is the earth connection: a low, stable reference around the whole footprint for surge and lightning energy to spread into, not a fault-clearing path.

Lightning protection is its own system and its own standard. A structural lightning protection system, air terminals, down conductors, and its own electrodes, is designed under NFPA 780, separate from the NEC power grounding. The two systems are not interchangeable, but they are required to be bonded together so they share one reference. If the lightning system and the power ground sat at different potentials, a strike would push one up relative to the other and the difference would arc across whatever bridges them, usually expensive equipment.

That bonding-together is the theme that keeps returning. Two separate earth connections at different potentials are a hazard and a damage path. One bonded system, with the lightning electrodes, the power electrodes, and the low-voltage systems all tied to a common reference, rises and falls together during a strike and protects what is connected across it.

Grounded conductor vs grounding conductor vs GEC

Three NEC conductors carry the word grounded or grounding, they sound alike, and they do three different jobs. Burning this distinction in clears up more confusion than any other single thing in Article 250.

The grounded conductor is the neutral. It carries normal load current back to the source every second the system runs. It is called grounded because it is intentionally connected to ground at the service, but it is a working, current-carrying conductor, not a safety ground. The grounding conductor, almost always meaning the equipment grounding conductor or EGC, carries no current in normal operation and exists only to carry fault current back to the source to trip the breaker. One works all the time, the other works only during a fault. Land them on the same bar downstream and you have created the two-bond objectionable-current problem.

The grounding electrode conductor, the GEC, is the third one, and it is the only one of the three whose job is the earth. It ties the service or the separately derived source to the grounding electrode system. It does not clear faults and it does not carry load current. It establishes the reference to earth. So the run of the three is: the grounded conductor carries load, the equipment grounding conductor carries fault current, and the grounding electrode conductor goes to earth. Three names, three jobs, and the only one actually about the dirt is the GEC.

Grounded conductor
The neutral, a current-carrying conductor bonded to ground at the service, carrying normal load current back to the source
Grounding conductor (EGC)
The equipment grounding conductor, a bonding conductor that carries fault current back to the source to trip the breaker, sized from the overcurrent device
Grounding electrode conductor (GEC)
The conductor tying the service or source to the grounding electrode system, the only one of the three whose job is the connection to earth
Grounding electrode system (GES)
All qualifying electrodes at a building bonded into one earth connection for reference, surge, and lightning

Signal reference and mesh bonding in sensitive spaces

In a data center or any space full of sensitive electronics, bonding picks up a third job beyond touch safety and fault clearing: holding the reference quiet so digital equipment is not chasing voltage differences between racks. The answer is a bonded plane, often a signal reference grid or a common bonding network, a mesh of conductors tying every rack, cabinet, raceway, and equipment frame to a low-impedance grid instead of running individual grounds back to one point.

The logic is the same potential idea pushed to its limit. Equipment that talks to other equipment over data cabling needs every chassis at the same reference, because a small voltage difference between two frames shows up as noise or errors across the link between them. A single-point ground that works fine for a panel cannot hold thousands of square feet of raised floor at one reference at high frequency, so the mesh ties everything together everywhere. It is bonding, not earthing, doing the work.

This is still bonding under Article 250, layered with the recommendations in standards like IEEE 1100, the Emerald Book, which covers powering and grounding electronic equipment. The fault-clearing path and the single-point neutral bond rules do not go away in a data center. The mesh sits on top of them to handle the signal-reference job that ordinary bonding does not need to worry about.

Keeping the terms straight on the record

Most grounding-and-bonding mistakes on paper are really naming mistakes. Someone writes ground where they mean bond, or sizes a grounding electrode conductor where the equipment grounding conductor was the question. The fix is to use the term that names the job, every time, on the drawing and in the field. The table below is the cheat sheet: what each element connects and what it is actually for.

When you note a connection, name which of the four it is. Wrote a 6 AWG to the rod? That is a grounding electrode conductor to an electrode, not a ground wire. Pulled a green wire with the feeder? That is an equipment grounding conductor for the fault path, sized from the breaker. The next person reading the record should be able to tell, without guessing, whether a given conductor goes to earth or carries fault current, because those two get sized and inspected by completely different rules.

TermWhat it connectsIts job
Bonding (general)Metal part to metal partSame potential and a fault path back to the source
Equipment grounding conductor (EGC)Equipment metal back to the serviceCarry fault current to trip the breaker
Main bonding jumperNeutral to ground at the serviceThe one place the two systems tie together
System bonding jumperNeutral to ground at a separate sourceThe single bond at a transformer or genset
Grounding electrode conductor (GEC)Service or source to the electrodesConnect the system to earth
Grounding electrode system (GES)All electrodes bonded togetherOne earth reference for surge and lightning

Common mistakes

  • Bonding the neutral to ground downstream of the service, in a subpanel or after a transfer switch, which puts normal neutral current on the equipment grounding system.
  • Relying on a ground rod to clear a fault, when the earth's resistance passes far too little current to trip a breaker.
  • Loose, painted, or corroded bonding connections that look made but cannot carry fault current when it counts.
  • An undersized equipment grounding conductor, or one left unchanged after the phase conductors were upsized.
  • A missing bonding jumper at a concentric knockout, an expansion fitting, or around a water meter, leaving a gap in the fault path.
  • Calling the equipment grounding conductor the ground and treating it like the earth connection, when it is a bonding conductor.
  • Confusing the grounding electrode conductor with the equipment grounding conductor and sizing the wrong one by the wrong rule.
  • Two neutral-to-ground bonds on a generator, or none, by missing whether the transfer switch makes it a separately derived system.

Field checklist

The concept reduces to a handful of yes-or-no checks you can walk through on any service or branch. The question behind all of them is whether each job, bonding and grounding, is done in the right place and the right number of times.

0 of 9 complete

Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.

Standards and references

The framework is the NEC, NFPA 70, Article 250, which covers grounding and bonding together because the two jobs are done in the same article. The performance requirements at 250.4 are the part worth reading first: 250.4(A)(1) gives the purposes of system grounding to earth, and 250.4(A)(5) requires an effective ground-fault current path of bonded metal back to the source and states the earth shall not be used as that path. Article 100 defines bonding and the effective ground-fault current path, and those two definitions carry most of the concept.

For the specifics: the main bonding jumper and service grounding live around 250.24 and 250.28, the load-side prohibition on re-bonding the neutral at 250.24(A)(5), objectionable current at 250.6, separately derived systems at 250.30, equipment grounding conductor types at 250.118 and sizing at 250.122, and bonding of other systems at 250.104. Section numbers move between code cycles, so confirm each against the edition the jurisdiction has actually adopted and any local amendments before citing it on a submittal.

Beyond the NEC, IEEE 142, the Green Book, covers grounding of industrial and commercial power systems and is where the low resistance targets people quote come from as recommendations, not NEC mandates. IEEE 1100, the Emerald Book, covers grounding and bonding of sensitive electronic equipment. NFPA 780 covers lightning protection as a separate but bonded system. The AHJ governs, and where the project specification or the equipment listing is stricter than the general code, the stricter requirement controls.

Units, terms, and abbreviations

Grounding and bonding carry a stack of acronyms that get used loosely across drawings, specs, and the field, and a few of them name parts that look alike but do different jobs.

Resistance to earth is read in ohms, anywhere from a few ohms in good soil to over 100 in dry ground, which is the whole reason the earth cannot clear a fault. Conductor sizes are AWG for smaller conductors and kcmil for larger. The shorthand below is the set worth keeping straight, and the one pair to burn in is the EGC versus the GEC: the equipment grounding conductor carries fault current back to the source, the grounding electrode conductor goes to earth.

Bonding
Permanent joining of metal parts to establish electrical continuity, for equal potential and a fault path back to the source
Grounding (earthing)
Connecting the system to earth for voltage stabilization, surge and lightning, and a common reference, not for clearing faults
EGC
Equipment grounding conductor, a bonding conductor carrying fault current to trip the breaker, sized from the overcurrent device
GEC
Grounding electrode conductor, the connection from the service or source to the grounding electrode system and the earth
MBJ / SBJ
Main bonding jumper at the service and system bonding jumper at a separate source, the single neutral-to-ground bond
Effective ground-fault current path
The intentionally constructed, low-impedance bonded metal route fault current takes back to the source
Objectionable current
Normal neutral current flowing on the equipment grounding system, caused by more than one neutral-to-ground bond

Related tools

Calculators and readiness checks for this work

Compare your options

FAQ

What is the difference between grounding and bonding?

Bonding joins metal parts so they sit at the same potential and gives fault current a low-impedance path back to the source. Grounding connects the system to earth for surge, lightning, and reference. The practical line: bonding clears the fault by tripping the breaker, while the earth connection never does.

Does a ground rod clear a fault?

No. A ground rod cannot clear a fault because the earth's resistance is too high to pass enough current. A 120 V fault across 25 ohms of soil drives under 5 A, far below what trips a breaker. The bonded metal path back to the source clears the fault, not the rod.

What is the equipment grounding conductor?

The equipment grounding conductor, or EGC, is a bonding conductor despite its name. It carries fault current from a faulted enclosure back to the source so the breaker trips. It rarely touches the earth, runs back to the panel, and is sized from the overcurrent device protecting the circuit, not from the load.

Where do you bond the neutral and ground?

At exactly one place per system: the service, through the main bonding jumper. A separately derived source like a transformer or neutral-switched generator gets its own single system bonding jumper. Bonding neutral to ground anywhere downstream creates objectionable current, putting normal neutral current on the equipment grounding conductors and metal raceway.

Is the green wire a ground or a bond?

Functionally it is a bond. The green or bare equipment grounding conductor ties metal together and carries fault current back to the source, and on most circuits it never reaches the earth. Calling it the ground hides its real job. It is a bonding conductor that clears faults, sized from the breaker.

Why can't you bond the neutral to ground in a subpanel?

A second bond turns the equipment grounding system into a parallel neutral, so normal load current splits between the neutral conductor and the ground path. That energizes raceways and frames never meant to carry current and heats connections. NEC 250.6 and 250.24(A)(5) prohibit it; the single service bond keeps current off the metal.

What is the effective ground-fault current path?

It is the intentionally constructed, permanent, low-impedance bonded metal route that carries fault current from the point of a fault back to the source, defined in NEC Article 100. It is built from equipment grounding conductors, raceways, bonding jumpers, and the main bonding jumper. The earth is deliberately excluded because it cannot carry enough current.

Do I still need a ground rod if bonding clears the fault?

Yes. The ground rod and the grounding electrode system do a different job: stabilizing voltage to ground and giving lightning and surge a path to earth. They are required even though they do not clear faults. Bonding handles fault clearing; the electrodes handle the earth reference. Both are needed, for different reasons.

What is the difference between the EGC and the GEC?

The equipment grounding conductor carries fault current back to the source to trip the breaker and is sized from the overcurrent device. The grounding electrode conductor connects the service or source to the earth electrodes and is sized from the service conductors. The EGC clears faults; the GEC references the system to earth.

Does bonding building steel and water pipe clear faults too?

Bonding metal piping and building steel keeps them from staying energized if a fault reaches them, giving that current a path back to clear. Where the underground water pipe qualifies, it also serves as an electrode. The bonding role keeps the metal safe to touch; the electrode role is a separate earth connection.

People also ask

Codes cited in this guide

This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.