Field glossary · method
Hydrostatic test
Hydrostatic testing applies liquid pressure to a pipe system or vessel and evaluates leakage, strength or deformation under its governing test specification. A cylinder can hold pressure yet fail because it remains enlarged afterward: 49 CFR 180.205 condemns a DOT 3AA cylinder when permanent expansion exceeds 10 percent of total expansion. A piping pressure-hold sheet cannot substitute for that cylinder requalification evidence.
Periodic pressure test of the cylinder shell on an interval set by NFPA 10
Which extinguishers reach their hydrotest date?
OSHA 29 CFR 1910.157 Table L-1 assigns a 5-year hydrostatic test interval to carbon-dioxide extinguishers and a 12-year interval to stored-pressure dry-chemical extinguishers with mild-steel, brazed-brass or aluminum shells. Dry-chemical extinguishers with stainless-steel shells have a 5-year interval under the same table. The agent name alone does not select the cycle.
A mild-steel stored-pressure dry-chemical extinguisher last hydrotested in 2014 reaches its 12-year interval in 2026. A CO2 extinguisher last tested in 2021 also reaches its interval in 2026. Put shell material and the previous test date beside the next due date, rather than sorting the inventory only by extinguisher class.
NFPA's current portable-extinguisher standard is NFPA 10-2026. The extinguisher readiness guide covers placement and use; the hydrotest register adds equipment-specific retest history to that readiness record.
Which pressure belongs on an extinguisher test order?
OSHA 1910.157(f)(10) sets the CO2 extinguisher test pressure at five-thirds of the stamped service pressure. A cylinder stamped for 1,800 psi service therefore has a 3,000 psi test basis under that rule. Record the stamped service pressure and calculated test pressure in separate fields.
For stored-pressure extinguishers covered by 1910.157(f)(11), OSHA specifies the factory test pressure, capped at twice service pressure. The cap is not permission to select twice service pressure for every unit. OSHA requires trained testers with suitable equipment and facilities, and prohibits air or gas as the hydrostatic test medium.
A cylinder can retain pressure and still fail expansion
PHMSA's 49 CFR 180.205 generally requires cylinder pressure retesting by a method that measures expansion, together with internal and external visual inspection. Permanent expansion is the increase in cylinder volume remaining after test pressure is released. It measures deformation that a pressure-hold reading alone does not describe.
Under 49 CFR 180.205(j), a DOT 3AA cylinder is condemned when permanent expansion exceeds 10 percent of total expansion. A 20.0 mL total expansion with 2.4 mL remaining after depressurization is 12 percent permanent expansion and fails that criterion. The same calculation with 1.2 mL remaining gives 6 percent; the visual findings and other applicable acceptance requirements still belong in the result.
Cylinder markings identify the specification behind that decision. DOT 4E aluminum and special-permit cylinders have different expansion provisions, so record the actual specification or special-permit number with the measured volumes.
Keep the cylinder certificate separate from the pipe test package
OSHA 1910.157(f)(16) requires an extinguisher hydrotest certification record containing the test date, tester's signature and extinguisher serial number or other identifier. Retain it until the extinguisher is actually hydrostatically retested or taken out of service, whichever occurs first. Reaching the next due date alone does not end retention.
A plumbing pressure-test record or chilled-water test package instead identifies an installed piping boundary. Include the cylinder's specification, expansion result and serial number when reviewing the separate requalification certificate. OSHA 1910.157(f)(14) requires failed or unfit extinguisher shells and cylinders to be removed from service and the workplace.
Distinctions
- Proof-pressure cylinder test
- 49 CFR 180.203 defines proof-pressure testing as liquid pressurization without measuring expansion. Volumetric expansion testing supplies additional deformation data. The authorized requalification method follows the cylinder specification.
Frequently asked questions
Is the six-year dry-chemical maintenance the hydrostatic test?
OSHA 1910.157(e)(4) requires emptying and maintenance every six years for applicable stored-pressure dry-chemical extinguishers on the 12-year hydrotest cycle; nonrefillable disposable containers are exempt. Recharging or hydrostatic testing restarts that six-year maintenance period. Maintenance by itself does not restart the hydrotest interval, so record the work performed against both schedules.
Sources checked
Also defined as
- Datacenter: A pressure test using water (or another liquid), the safe default because water stores little energy and a failure does not let go violently
- Plumbing: A pressure test using water, the safe default because water stores almost no energy and a failure weeps instead of bursting