Field glossary · equipment
Micron gauge
A micron gauge reports evacuation pressure on an absolute scale, but its display resolution does not establish measurement accuracy. Fieldpiece rates the SVG3 at ±30 microns when indicating 500 microns, despite a 1-micron display step. Interpret the reading with the instrument specification, sensor cleanliness and connection arrangement. A separate pump-and-gauge check helps distinguish instrument leakage from the behavior of the refrigeration system.
Electronic vacuum gauge with a thermistor sensor that reads deep vacuum in microns; the manifold gauge cannot
One-micron resolution does not mean one-micron accuracy
Fieldpiece specifies SVG3 accuracy as ±(5% of reading + 5 microns) between 50 and 1,000 microns. At an indicated 500 microns, that specification gives a ±30-micron instrument band. A 500 versus 510 comparison is therefore smaller than the stated accuracy band, even though the display can resolve the difference.
The SVG3 manual specifies 1-micron resolution from 50 to 2,000 microns, then larger display steps at higher pressures. Resolution describes what the screen can show. It does not tighten the accuracy specification. On an evacuation record, identify whether the reported uncertainty comes from the gauge specification or from pressure still changing in the system.
A contaminated sensor changes the result
Fieldpiece's SVG3 sensor-cleaning instructions call for isopropyl alcohol, gentle swirling for about 15 to 30 seconds, and drying with the fitting facing downward. Appion's 2026 AV760 manual instead specifies quick-drying electronic cleaner and prohibits spraying it directly onto the sensor. Cleaning chemistry and access follow the gauge model, not a shared shop habit.
Appion also identifies the removable fitting, oil-catch filter and O-ring as maintenance points. Oil retained ahead of the sensing element can keep a cleaned sensor from producing a sound system reading. Inspect the entire connection path. A gauge that reads normally on a clean test setup but erratically on one hose assembly directs the repair toward that assembly.
Prove the gauge assembly separately from the system
Appion's AV760 maintenance procedure finishes by connecting the gauge to a vacuum pump and operating it until the indication is 100 microns or less, followed by an isolation check when needed. That is an instrument-maintenance check. It does not supply the equipment manufacturer's evacuation acceptance limit.
Record the gauge model, pressure units and fitting arrangement with the result. Repeatability after cleaning helps distinguish a gauge problem from system outgassing; agreement between two contaminated gauges does not. Log the separate pump-and-gauge check in the instrument maintenance record before interpreting a system decay test.
Distinctions
- Micron
- Here micron means one micrometer of mercury-column pressure, not the size of a refrigerant particle or a filter opening.
- Maximum overpressure
- A survivable positive-pressure specification does not establish a recommended operating condition for a vacuum sensor. Isolate the instrument during charging as its manual directs.
Frequently asked questions
Why do two micron gauges disagree at 500 microns?
Compare their stated accuracy, locations, seals and sensor condition. The SVG3 accuracy calculation alone allows a 30-micron band at that indication.
Can I clean every vacuum gauge with rubbing alcohol?
Use its maker's specified cleaner. The SVG3 and AV760 instructions name different cleaning agents and different sensor-access steps.