Field glossary · method
Static pressure reset
Static pressure reset changes the target that the fan's pressure loop follows. In DOE's 2025 training example, the target can trim downward by 0.04 in. w.c. every five minutes within a 0.5 to 1.5 in. w.c. envelope. Trend the target separately from measured pressure and fan speed. A target held high by terminal requests is a different fault from a fan unable to achieve its current target.
Trim-and-respond logic that lowers the duct pressure setpoint to the minimum that still serves the hungriest zone
Two control loops operate on different time scales
DOE FEMP's 2025 Advanced Building Automation training shows a reset example with an initial target of 0.75 in. w.c., a 0.5 in. minimum and a 1.5 in. maximum. Those settings define the reset envelope for that training example. The fan's pressure controller still acts inside that envelope to follow the current target.
The same DOE example uses a five-minute reset time step with a -0.04 in. w.c. trim. With no qualifying requests, moving from 0.86 to the 0.50 in. floor takes nine such steps, or 45 minutes. That deliberate progression should not be diagnosed as a slow fan-speed controller: the reset target and the fan response are separate trends.
A request needs a named terminal and a reason
DOE's example shows a +0.06 in. w.c. response parameter and a +0.15 in. w.c. maximum response, along with the current requesting zone and its accumulated driver time. These points make pressure demand traceable. A target parked at its upper limit is not enough information to decide whether the system needs more fan pressure.
Compare a persistent request with that terminal's airflow setpoint, measured flow, damper position and sensor condition. A jammed damper, incorrect airflow calibration or unrealistic setpoint can keep asking for pressure the fan cannot usefully deliver. DOE's building re-tuning guidance specifically identifies the duct-pressure sensor and functioning VAV terminals as dependencies of fan static-pressure reset. Tie each persistent pressure request to the terminal's commissioned airflow and damper record, so the request can be tested against actual delivery.
Name the current sequence and prove its limits
ASHRAE lists Guideline 36-2024 as the published edition superseding Guideline 36-2021, and its addenda catalog includes 2026 updates. Record the project sequence revision and incorporated addenda when accepting a reset implementation. The DOE training example's numerical settings are not a substitute for that adopted sequence.
Demonstrate a trim, a response and both saturation limits while trending measured duct pressure and the changing setpoint. Include fan mode, VFD output and zone requests so the trace distinguishes a clamped target from a controller that cannot meet it. Keep the hard high-pressure protection identified separately from the energy-control logic in the air-distribution guide.
On a trend where the target is 1.3 in. w.c. but measured pressure is 0.7 in. w.c., first distinguish an unmet pressure target from excessive reset demand. DOE's training graphic shows both values together for this reason. A high target does not prove the duct actually has high pressure.
Distinctions
- Fixed pressure control
- The fan varies output to maintain one target. Fan modulation alone does not establish that the pressure target is being reset.
- High-static safety
- Protective shutdown or limiting action for an excessive pressure condition. Reset optimizes normal operation and does not replace that protection.
Frequently asked questions
Why is the pressure target stuck at maximum?
Find the terminals generating requests, their driver time and the reason for each request. Then compare actual airflow and damper behavior with the demand.
Can I prove reset just by watching fan speed?
No. Trend the pressure setpoint itself, the measured pressure and terminal requests. Fan speed also changes while following a fixed target.
Sources checked
- U.S. DOE FEMP: Advanced Building Automation, August 6, 2025, PDF page 26 / slide 28, duct-static reset graphic
- U.S. DOE FEMP: Screening a Building for Re-tuning Potential, fan reset dependencies
- ASHRAE: Guideline 36-2024 published edition, purpose and scope
- ASHRAE: published Guideline 36-2024 addenda through November 5, 2026
Also defined as
- Resetting the air handler's duct static setpoint to the lowest pressure that still lets the boxes make airflow