Field glossary · data center
Thermal envelope
In data-center specifications, a thermal envelope combines an inlet-temperature band with moisture limits and permitted temperature changes. ASHRAE's fifth-edition guidance recommends 18 to 27°C for classes A1 through A4, while manufacturer-designated H1 equipment has an 18 to 22°C recommended band. The wider allowable limits answer a different operating question. Identify the equipment class before applying a setpoint, then check humidity, elevation and temperature excursions at the same inlet.
The temperature and humidity range allowed at the IT equipment intake, per ASHRAE TC 9.9
Read the equipment class before choosing a setpoint
ASHRAE's Fifth Edition Revised and Expanded reference card gives H1 equipment a 15 to 25°C allowable inlet range. An H1 intake at 24°C is inside that allowable band but above its recommended 22°C ceiling. Label those two limits separately on the controls schedule; an A2 label on a neighboring server does not extend the H1 limit.
The equipment manufacturer's declared class and environmental specification determine which comparison belongs in its record. ASHRAE's recommended range is operating guidance, while a project acceptance requirement comes from the equipment and project specifications. A dashboard should identify the basis of its alarm rather than call every temperature outside the recommended band a failed equipment limit.
Apply dew-point and relative-humidity ceilings together
ASHRAE's Thermal Guidelines for Data Processing Environments, Fifth Edition Revised and Expanded, pairs a recommended upper dew point of 15°C with an RH ceiling determined by corrosion conditions. The published reference card permits 70% RH where silver and copper coupon corrosion rates remain below 200 and 300 angstroms per month, respectively; elevated corrosion calls for 50% RH or lower. Both moisture constraints apply.
At the upper moisture boundary, use whichever of the RH and dew-point limits permits less water vapor at the measured temperature. Both limits must be satisfied. Reaching the RH ceiling does not permit a higher dew point, and a dew point below its ceiling does not override excessive RH. Preserve both points in the control graphics and humidity-control record.
Derate the allowable temperature for elevation
ASHRAE's reference card reduces the maximum allowable dry-bulb temperature for classes A1 and A2 by 1°C for each 300 m above 900 m elevation. An A2 ceiling of 35°C therefore becomes 33°C at 1,500 m: the 600 m elevation increment removes 2°C. Compare that adjusted ceiling with the equipment's own published environmental specification.
The elevation adjustment belongs to the equipment class, so applying an A2 correction to every device in a mixed aisle loses information. Record class and elevation with the limit calculation. A setpoint copied from a sea-level site does not preserve the same allowable margin at a higher site.
Check temperature excursions with time windows
ASHRAE limits inlet-temperature change for non-tape IT equipment to 5°C within any 15-minute period and 20°C within an hour. The reference-card notes define change as the maximum inlet temperature minus the minimum within the specified window, rather than a fitted average slope.
An inlet rising from 22°C to 28°C in ten minutes spans 6°C and exceeds the 15-minute change limit even though both readings fit an A2 allowable temperature range at sea level. A report containing only hourly averages cannot demonstrate that the shorter window stayed within bounds. Retain sufficiently frequent inlet observations and evaluate rolling windows during a transfer or cooling-recovery event.
Distinctions
- Building thermal envelope
- In roofing and energy-code work, the thermal envelope is the building boundary controlling heat transfer. The data-center equipment envelope describes environmental conditions at IT intakes. It is not an insulation or air-barrier assembly.
Frequently asked questions
Why does an older H1 table show a 5°C lower allowable temperature?
ASHRAE's May 31, 2022 errata corrected the H1 allowable dry-bulb range from 5 to 25°C to 15 to 25°C. Use the corrected reference card when recording limits alongside the thermal-setpoint guide.
Sources checked
Also defined as
- The temperature and humidity box the IT equipment is held within