Dew point
Dew point is the water-vapor saturation temperature at a stated gas pressure, so a field record needs pressure as well as degrees. With room dew point at 15.0°C and a pipe surface at 17.5°C, the measured condensation margin is 2.5°C. A compressed-air sample expanded to atmosphere has a different dew point from the pressurized process, even without removing moisture.
The temperature at which room air condenses; the secondary supply is held above it, commonly with a margin, to stay dry
Calculate the surface margin from colocated readings
With a measured room dew point of 15.0°C and a pipe surface at 17.5°C, the measured surface margin is 2.5°C. Use conditions at the pipe, rather than a humidity sensor in another zone with a different moisture source. A colder fitting or valve body can govern even when the straight pipe remains dry.
Record uncertainty with the margin. If the dew-point reading is specified at ±0.5°C and the surface measurement at ±0.3°C, the 2.5°C difference has a worst-case lower bound of 1.7°C before spatial or time variation. Use colocated readings in the CDU condensation-control record, rather than comparing a local cold fitting with a distant room sensor.
Pressure dew point and atmospheric dew point
Vaisala’s dew-point measurement guidance states that increasing gas pressure increases dew point. A dryer outlet measurement at line pressure therefore cannot be compared directly with a sample expanded to atmosphere. Record the absolute pressure at the sensor and whether the reported value is pressure dew point or atmospheric dew point.
Vaisala’s compressed-air sampling note warns that measuring at a different pressure from the process can create a dew-point difference of several tens of degrees. Put a pressure-reducing device on the correct side of the sampling cell for the intended measurement. Otherwise the instrument can faithfully report the sample while the record mislabels it as the process.
Keep the sampling line from changing the moisture
Vaisala’s sampling guidance calls for a direct measurement or heated sampling line when the process dew point exceeds the surrounding temperature. Cooling a wet sample below that point deposits liquid in the tubing, removing vapor before it reaches the sensor.
The same note recommends metal sampling lines and identifies moisture absorption and diffusion through unsuitable hose materials as sources of error. A long rubber hose that has been open to humid room air can contaminate a dry sample. Include the sampling arrangement when investigating slow stabilization or disagreement between instruments.
Vaisala states that flows of 1 to 2 L/min are typically sufficient for high-quality dew-point sensors in its compressed-air sampling guidance. Raising flow is therefore not a substitute for correcting leaks, pressure errors or a wet sample line.
Distinctions
- Frost point
- Frost point uses saturation with respect to ice. Below freezing, identify which saturation reference the instrument reports.
- Refrigerant dew temperature
- A refrigerant blend’s dew temperature comes from its pressure-composition relationship. It is not the room-air moisture reading used to predict external condensation.
Frequently asked questions
Does heating dry air lower its dew point?
Sensible heating alone lowers relative humidity while leaving dew point essentially unchanged at constant pressure and moisture content.
Why does a portable meter disagree with the installed dryer sensor?
Compare sensor pressure, sample-line moisture, leakage and stabilization first. Expanding one sample to atmosphere creates a different measurement condition.