Field glossary · measurement
Dry-bulb temperature
An air-temperature reading qualifies as dry-bulb when the sensing element is dry, exposed to representative air and shielded from radiation. Moisture on a supply probe can inflate the apparent cooling split: a true 26°C-to-16°C split is 10°C, but a wet probe reading 13°C reports 13°C. NIST converts the true 10°C interval to 18°F. Dry-bulb describes how temperature is sensed, rather than a low humidity condition.
The temperature an ordinary thermometer reads, the sensible temperature of the air, plotted on the horizontal axis
Keep the sensor dry and shielded
The National Weather Service defines dry-bulb temperature using a thermometer exposed to air but protected from radiation and moisture. A probe in direct sunlight exchanges heat with the sun as well as the air. Moving it into shade removes that radiant input; it does not mean the surrounding air suddenly became colder.
Water on the sensing element creates another error mechanism. Evaporation cools a wetted probe toward wet-bulb temperature. The National Weather Service states that wet-bulb and dry-bulb temperatures coincide at 100% relative humidity. Below saturation, a wet sensor generally reads lower than a dry one in the same air.
Check for coil droplets, rain, a damp probe sleeve or condensation after moving a cold instrument into warm humid air. Let the sensing element dry and stabilize before using it as the dry-bulb input. Mark that stabilized reading's location before entering it on the psychrometric chart; a mixed-air traverse and a single cabinet sensor can represent different air samples.
Separate location error from calibration error
Place a comparison probe beside the installed sensor without touching it or the surrounding metal. Sensors at different depths or on opposite sides of a mixing box can read different temperatures correctly. Agreement in one well-mixed location tests the instruments; disagreement between locations describes the airstream until shown otherwise.
A metal probe pressed against a cabinet measures a combination of air and surface influences. Sun-warmed housings, cold duct skins and warm electronics near the sensing element create repeatable bias that calibration alone will not remove. Record the sampling position as carefully as the displayed number.
For a temperature-split check, return air at 26°C and supply air at 16°C give a 10°C difference. If a wetted supply probe instead indicates 13°C, the apparent difference becomes 13°C, a 30% overstatement. The arithmetic is correct; the supply reading no longer represents dry-bulb temperature.
Carry units and time into the record
NIST SP 811 specifies a Fahrenheit temperature interval as 5/9 of a kelvin, so a 10°C difference equals 18°F, without adding 32. Convert actual temperatures and temperature differences separately. The return temperature of 26°C is 78.8°F; its 10°C difference from supply is not 50°F.
Take paired readings during the same operating period and allow both sensors to settle. A return reading before compressor startup and a supply reading after stabilization describe different conditions. Preserve sensor location, operating state and time with the value when comparing a service visit with commissioning.
Distinctions
- Dew point
- The saturation temperature associated with the air's water-vapor content; it is not a second name for a low dry-bulb reading.
Frequently asked questions
Does dry-bulb mean the air contains no moisture?
No. Humid and saturated air both have a dry-bulb temperature. The sensing surface remains dry so evaporative cooling does not alter that measurement.
Can an infrared thermometer measure dry-bulb air temperature?
An infrared thermometer reads radiation from surfaces in its field of view. Use an air-temperature probe to measure the moving airstream.
Sources checked
Also defined as
- The air temperature a standard thermometer reads, with no moisture effect