Plumbing
Hot water recirculation loop design and sizing field guide
Why the loop exists, how to pick the loop type, size the pump and the return, balance every riser, hold the return temperature, and control the energy without parking the loop in the Legionella band.
Direct answer
A hot water recirculation loop keeps heated water moving from the heater to the far fixtures and back, so hot water arrives fast instead of running cold down the drain. You size the pump to carry the loop's heat loss, size the return smaller than the supply, and balance each riser to hold temperature.
Key takeaways
- Recirculation flow comes from loop heat loss, not fixture draw: GPM equals loop BTU/hr divided by 500 and by the allowed temperature drop (commonly 10F to 20F).
- Size the hot water return one or two pipe sizes smaller than the supply, since it carries only the recirc flow.
- Hold copper recirculation velocity to roughly 2 to 3 ft/s above 140F (about 5 ft/s up to 140F) to prevent erosion-corrosion at fittings.
- Keep the loop return at or above roughly 124F (51C) so the coolest point stays out of the Legionella growth band.
- Insulating supply and return cuts loop heat loss by roughly 70 to 80 percent; never let an energy control park the loop cool. ANSI/ASHRAE 188 governs the water-management program.
The recirculation loop and the wait-time problem
A hot water recirculation loop is the supply-and-return circuit that keeps heated water moving through the building so it is already hot at the fixture when someone opens the tap, instead of sitting cold in a long branch. It is a separate problem from sizing the heater. Size the heater itself, its recovery, its storage, and its delivery temperature per the water heater sizing and selection guide. This guide is the loop: why it exists, how the pump and the return are sized, how it is balanced, and how it stays hot enough to be safe without burning energy around the clock.
The loop has two pipes doing two jobs. The supply runs hot water out to the fixtures the same as any distribution main, and the fixtures tap off it. The return is the second pipe that carries the cooled water from the end of the run back to the heater, so a small circulator can keep the whole circuit warm and ready. The return carries no fixture draw. It exists only to keep the loop hot, which is why it is sized and balanced on heat loss, not on demand.
Get the loop right and the far shower runs hot in a couple of seconds. Get it wrong and you have traded water down the drain, a cold complaint at the end of the building, or a lukewarm leg where bacteria grow. The rest of this guide is how each piece of the loop is decided, and why each one bites back when it is skipped.
Why do you need a hot water recirculation loop?
You need a recirculation loop when the run from the heater to the farthest fixture is long enough that the water sitting in the pipe goes cold between uses. Without a loop, every foot of branch holds a slug of cooled water, and the person at that fixture runs it down the drain until hot arrives. On a long run that is gallons of water and most of a minute of waiting, every draw, all day. On a metered building you pay for that water twice, once at the meter and again to reheat what you dumped.
The plumbing code reaches for circulation past a set distance from the source to the fixture, because a long uninsulated branch both wastes water and grows a cool zone where Legionella can establish. The exact trigger length and the developed-length method that measures it are set by the adopted code, IPC or UPC, and local amendments, so confirm the distance that forces circulation on the project before you assume a loop is or is not required.
A continuously circulated loop is not the only answer the code allows. A heat-traced supply line holds temperature with an electric trace cable along the pipe and no return at all, which suits a single long run where pulling a return pipe is impractical. A demand-controlled or point-of-use pump moves water only when it is called for, trading instant hot for the lowest energy. The dedicated loop is the common answer on commercial and multifamily work because it serves many fixtures off one circuit and balances cleanly across risers. Pick the approach to the building, then size it.
The loop types and where each one fits
Three approaches cover most recirculation, and they are not interchangeable. A dedicated hot-water return loop is the engineered answer. A separate return pipe runs from the end of the supply back to the heater, and a circulator keeps the whole loop hot. It is the system you design into new commercial and multifamily work because it holds every fixture and balances cleanly across risers. The cost is the second pipe and the space to run it.
A cold-water-return or comfort-valve system is the retrofit answer where there is no return pipe and no easy way to add one. A thermostatic crossover valve sits under the farthest fixture and bridges the hot line to the cold line. A pump at the heater pushes cooled hot water back through the existing cold piping until the valve senses hot and closes. It avoids opening walls for a dedicated return, but it warms the cold line, so the cold tap runs lukewarm for a moment after the pump runs, and the approach does not scale well to a large building with many branches pulling against each other.
A point-of-use on-demand pump is the most local answer. A small pump under a fixture runs only when a button, a motion sensor, or an occupancy signal calls it, pulling hot to that fixture through the cold line and shutting off when hot arrives at the sensor. It uses the least energy because it runs in short bursts and keeps nothing hot between calls, and it adds the longest first-draw wait for the same reason. Match the type to the building and the budget, not to whatever the last job used.
| Loop type | How it returns water | Best fit |
|---|---|---|
| Dedicated hot-water return | Separate return pipe from the far end back to the heater | New commercial and multifamily; holds and balances every fixture |
| Cold-return / comfort valve | Thermostatic crossover valve bridges hot to cold under the far fixture | Retrofit with no room for a return pipe; smaller buildings |
| Point-of-use on-demand pump | Local pump pulls hot through the cold line on a call, then stops | A single far fixture; lowest energy, longest first-draw wait |
Trunk-and-branch versus structured plumbing
How the supply is laid out decides how much uncirculated pipe sits between the loop and each fixture, and that is the wait-time the loop cannot fix. A trunk-and-branch layout runs a large main with branches teeing off to fixtures. The loop circulates the trunk, but each branch from the trunk to the fixture is a dead leg the loop never reaches, so the wait at the tap is the time to clear the cooled water in that branch, no matter how hot the trunk runs.
Structured plumbing flips the geometry. A central manifold or a continuous loop runs close to every fixture group, and the branch from the loop to each fixture is kept short, often a few feet of small-diameter pipe. Less water sits in the branch, so hot arrives at the tap faster and less water goes down the drain, even though the loop temperature is identical. The smaller branch also holds less cooled water to reheat, which trims the standing load.
The design lever here is branch length and branch diameter, not pump size. A short 3/8 in or 1/2 in branch off a circulated loop empties in a second or two. A long 3/4 in branch off a trunk can hold a quart of cold water that has to clear first, and no pump setting changes that. Keep the uncirculated branch short and small and you cut the wait at its source instead of throwing flow at it from the mechanical room.
How do you size a hot water recirculation pump?
You size a recirculation pump on two numbers: the flow it must move to carry the loop's heat loss, and the head it must overcome to push that flow around the longest circuit. Neither comes from any fixture draw. The recirc flow is set by the heat the piping sheds, not by gallons used at the tap, which is the single idea that separates loop sizing from heater sizing.
Flow first. The pump has to move enough gallons per minute to replace the heat the loop loses while holding the water above the minimum return temperature. The flow is the loop heat loss in BTU per hour divided by 500 and by the temperature drop you allow around the loop. Most designs allow a 10°F to 20°F drop from the heater out to the return, and the tighter the allowed drop the more flow it takes to hold it. The recirc flow is small. Many commercial loops run only a few gallons per minute, not the tens a fixture main carries.
The loop heat loss is the input you have to know, and it comes from the pipe size, the length, and the insulation. Insulate the hot and recirc piping and the heat loss drops by roughly 70 to 80 percent, which cuts the flow the pump must move and the energy the heater has to make up. Run the heat loss on the insulated condition, because that is what the loop will actually be.
Head second. Size the pump head off the friction of the loop at that flow, taken on the longest circuit through the piping, the fittings, and the balancing valves and back to the heater. A common planning figure is a couple of feet of head per 100 feet of circuit at the design flow, but run the actual length and fittings rather than leaning on the rule. A recirc loop is a low-flow, high-friction circuit, so the pump curve you want is one that holds head as the flow moves, not the flat high-flow curve of a pump meant for a fixture main. Read the curve at the design point, confirm the operating point lands in the middle third of the curve, and do not oversize. Push the velocity too high and you erode the copper. Undersize the head and the far riser never gets enough flow to stay hot.
GPM = Qloss / (500 × ΔT)- Q_loss
- Loop heat loss in BTU per hour, from the pipe size, length, and insulation
- 500
- Constant for water, roughly 8.33 BTU/gal/degF times 60 minutes per hour
- ΔT
- Allowed temperature drop around the loop, commonly 10°F to 20°F
Sizing the return piping
The return is sized smaller than the supply because it carries only the recirc flow, not any fixture demand. The supply main is sized to deliver peak fixture flow to the branches. The return only carries the few gallons per minute the pump moves to make up heat loss, so it is commonly one or two pipe sizes down from the supply it serves. A 2 in supply main may return through a 3/4 in or 1 in line. Oversize the return and the flow slows, the water cools more between the heater and the riser, and the loop loses temperature. Undersize it and the friction climbs until the pump cannot push the design flow.
Velocity is the limit that sets the floor on return size. Keep the return velocity in a range that moves the water without eroding the pipe. In copper, hot recirculating water above 140°F is commonly held to roughly 2 to 3 feet per second, and hot water up to 140°F to around 5 feet per second, because the thin oxide film that protects copper erodes under fast, hot, turbulent flow and the wall and elbows thin out over time. The damage shows up first at the fittings and the direction changes, where the turbulence is worst. It is called erosion-corrosion, and an oversized pump driving an undersized return is the classic cause.
On a loop with several return risers tying into one common return, the common pipe carries the sum of the branch flows, so it steps up in size as it nears the heater. Size each branch return for its own riser's heat-loss flow, then size the common return for the total it collects. The return that is right at the far riser is undersized once three more risers have joined it.
How do you balance a recirculation loop?
You balance a recirculation loop by setting the flow in each return branch so every riser gets enough circulation to make up its own heat loss, not just the branch nearest the pump. Water takes the path of least resistance. On a building with several return risers tying back to one common return, the riser closest to the pump with the least friction grabs most of the flow, and the far riser gets whatever is left, which is often not enough to hold temperature. That far riser is exactly where the cold-water complaint and the Legionella risk both show up.
The unbalanced-loop symptom is easy to read once you know it. The near fixtures run hot instantly, the far fixtures run cold or take a long wait, and the loop return at the heater reads warmer than the design because the far legs are barely circulating and the near legs short-cycle hot water straight back. Adding pump is the wrong fix. It pushes even more flow through the short path and erodes it, and the far riser is no better off.
The fix is a balancing valve on each return branch. Manual balancing valves are dialed in at commissioning with a thermometer on each riser, but they hold only the setting you gave them and drift as the building load changes or someone touches them. A thermostatic balancing valve senses its branch return temperature and modulates the flow to hold that branch at a setpoint, so each riser self-adjusts to stay hot. The thermostatic version stays balanced after the commissioning agent leaves, and it doubles as a Legionella control, because holding every branch above the minimum return temperature is the same thing that suppresses growth in the loop. Manual valves can do the same job, but only if someone re-balances them when the building changes, and on most jobs nobody does.
Keeping the loop hot: return temperature and insulation
The design return temperature is the number the whole loop is built to hold, and the biggest lever on it is insulation, not pump size or heater setting. The loop sheds heat through the pipe wall every foot of its length. The flow and the temperature drop you allow set how cool the water is by the time it returns. A common engineering target is to keep the return above roughly 124°F so no part of the loop falls into the bacteria growth band, with the supply leaving storage hotter to give the loop room to lose a few degrees and still arrive warm at the far riser.
Insulation is the cheapest performance on the whole system. Insulate the supply and the return and the heat loss per foot drops by roughly 70 to 80 percent. That single move cuts the flow the pump must carry, the energy the heater makes up, and the temperature the loop loses end to end. Leave the recirc line bare and it bleeds heat into the ceiling, the far riser runs cold, and the energy bill carries it for the life of the building. The insulation is also the input that sized the pump in the first place, so skipping it on the install makes every number on the calculation wrong.
Insulate the whole circuit, not the easy runs. The elbows, the hangers, the valve bodies, and the tank connections are where bare metal hides and the loss concentrates. A loop insulated everywhere except the fittings still loses heat at every fitting, and there are a lot of them. Continuous insulation, sealed at the seams, is what the heat-loss number assumes.
Does a recirculation loop cause Legionella?
A recirculation loop does not cause Legionella. A loop run too cool or balanced badly can grow it, and a loop run hot all the way through is one of the controls against it. The difference is whether every foot of the loop stays out of the bacteria growth band. The control in the recirculation context is specific: keep the whole loop hot through its full length, hold the return above the minimum return temperature, and do not let any leg sit lukewarm and slow. A common engineering floor is a return at or above roughly 124°F (51°C), so the coolest point in the circuit is still above the band.
The low-temperature dead leg is the risk the loop creates when it is done wrong. An uncirculated branch off the loop, a capped future connection left warm, or a riser the balancing starved all sit warm and still, which is the condition the bacteria want. Circulate what the loop can reach, keep the uncirculated branches short, and remove dead legs rather than leaving them capped and warm off a hot main.
Thermal disinfection of a loop is the periodic high-temperature flush some water management programs run, raising the loop temperature for a set time to knock back colonization. It only works if every leg actually reaches the target temperature for the full time, the unbalanced far riser included, which is one more reason the loop has to be balanced before anyone trusts a disinfection cycle. The storage temperature at the heater, the tempered delivery at the fixture, and the building water management program are covered with the heater in the sizing guide. For the loop, the rule is hot everywhere with no cool dead legs. The actual program is set by ANSI/ASHRAE Standard 188 and the facility's health authority, so treat these temperatures as the common control, not a substitute for the project's plan.
Control strategies and the energy trade-off
A recirculation loop runs against the clock all day, so how it is controlled is most of its energy cost. The loop pays to make up its heat loss every hour it circulates, plus the electricity the pump draws to move the water. The control strategy trades comfort, instant hot water at the tap, against that standing energy, and the right pick depends on how the building actually runs, not on a preference.
The simplest control is none: a pump running continuously, which keeps every fixture instantly hot and also pays to reheat the loop losses 24 hours a day. A timer shuts the pump off during hours the building is empty, simple where the schedule is predictable, but a dumb timer can let the loop cool into the growth band overnight if the off period runs long. An aquastat runs the pump only when the return temperature drops below a setpoint, so it makes up heat loss on demand instead of constantly, which saves energy and protects the return temperature at the same time. Demand-controlled recirculation starts the pump only when a fixture is called by a button, an occupancy sensor, or a learning control, which saves the most energy and adds the longest first-draw wait. Some newer pumps add learning controls that predict the building's draw pattern and pre-position hot water ahead of it.
Never let an energy control override the Legionella temperature. A timer or a demand control that lets the loop fall and sit cool is trading an energy line against a health line, and that is the wrong trade. Floor every control on the return temperature so the pump still runs when the loop drops toward the band, whatever the schedule says, and set the rest of the strategy to fit how the building lives.
| Control | How it runs the pump | Energy versus comfort |
|---|---|---|
| Continuous | Pump runs 24/7 | Instant hot everywhere; highest standing energy |
| Timer | On during scheduled occupied hours | Saves off-hours; can cool into the growth band if off too long |
| Aquastat / thermostat | Runs only when the return drops below a setpoint | Makes up heat loss on demand; protects the return temperature |
| Demand / on-demand button | Runs only when a fixture calls for hot | Lowest energy; longest first-draw wait |
Dead legs and the wait-time math
A dead leg is any length of pipe the loop does not circulate, and it is the only thing standing between a hot loop and an instant tap. The loop holds the trunk or the manifold hot, but the branch from the loop to the fixture is uncirculated, so the wait at the tap is the time to clear the cooled water in that branch. The math is plain. The volume of water in the branch divided by the flow rate at the fixture is the wait. A long, fat branch holds more water and waits longer.
Run the numbers and the branch size dominates. A 1/2 in copper branch holds roughly a pint per 12 feet; a 3/4 in branch holds more than double that per foot. So a 20 foot run of 3/4 in branch off the loop can hold close to half a gallon of cold water that has to clear before hot arrives, while a 6 foot 1/2 in branch clears in a second or two. The structured-plumbing answer is to keep the branch short and small, run the loop close to the fixture groups, and accept the small branch as the only uncirculated water in the system.
Capped future connections and abandoned branches are dead legs too, and they are worse, because they never flow at all, so they sit warm and stagnant off a hot main. On a remodel, cut abandoned branches back to the active pipe rather than leaving a capped stub hanging off the loop. The code limits the developed length of uncirculated branch for both the wait and the stagnation reasons, so confirm the branch-length limit against the adopted code on the project.
Heat loss, pump energy, and demand-control savings
The always-hot loop has a standing cost whether anyone draws hot water or not, and it has two parts: the heat the loop loses, which the heater makes back, and the electricity the pump draws to circulate. On a long, poorly insulated loop the heat-loss part is the bigger one by far, which is why insulation is the first move and the pump control is the second, in that order.
Cut the heat loss first. Insulating the supply and the return drops the loss by roughly 70 to 80 percent, which shrinks both the heater make-up energy and the flow the pump has to move. No control strategy beats simply not losing the heat in the first place. Heat traps on the tank connections and tight, continuous insulation on every elbow and hanger close the small leaks that add up to a real number over a year.
Then cut the run time. A continuous pump runs 8,760 hours a year and costs real money in both pump energy and the loss it keeps reheating. An aquastat or a demand control that runs the pump a fraction of those hours captures most of the savings without letting the loop go cold, and the energy codes increasingly call for a control rather than a continuous pump on new work. The honest version of the trade is that demand control saves the most and waits the longest, while an aquastat over well-insulated pipe is the balance most buildings land on.
Commissioning the loop
Commissioning is where the loop on paper becomes a loop that performs, and most callbacks on a new recirculation system are commissioning nobody finished, not a pump that failed. Start at the heater and read the loop return temperature with the system hot and circulating. If the return is below the design floor, the loop is losing too much heat or the pump is not moving the design flow, and you find that now, not from a tenant complaint in January.
Then walk the loop and verify each riser is hot. Read the return temperature at each branch and adjust the balancing valves until every leg holds above the minimum return temperature, not just the near ones. A manual valve gets dialed in here. A thermostatic valve gets its setpoint confirmed and then watched to see it actually modulates. Time the wait at the farthest fixture with a thermometer in the stream, not by hand. If hot takes a long time to arrive, the loop is unbalanced, the pump is undersized for the head, or the branch to that fixture is a long dead leg, and the three have different fixes.
Set the pump control last, after the temperatures hold. Confirm the aquastat setpoint, the timer schedule, or the demand trigger does what the design intended, and confirm it cannot let the loop fall below the Legionella floor on its own. Write down every reading: the return temperature at the heater, the temperature at each riser, the balancing valve settings, the far-fixture wait, and the control setpoints. The commissioning record is what the next person checks against when the loop drifts, and loops always drift.
What to document
A loop nobody documented is a loop nobody can troubleshoot or defend. When the far fixture runs cold two winters from now, or the health authority asks for the loop temperatures, the record is what answers it. Capture the design inputs and the as-set values, not just the pump cut sheet.
Record the calculated loop heat loss and the design flow, the pump model and head with the curve point it runs at, the design return temperature and the measured return at the heater, the temperature at each riser with its balancing valve setting, and the pump control type with its setpoints. Note the far-fixture wait time you measured. The next person reading the record needs to see what the loop was set to hold and why, because those are the values that quietly slip.
| Field to record | Why it matters |
|---|---|
| Loop heat loss and design flow (GPM) | The basis the pump was selected on |
| Pump model, head, and curve point | Confirms the pump was sized to the loop, not oversized |
| Design versus measured return temperature | Proves the loop holds out of the growth band |
| Temperature at each riser | Shows the loop is balanced, not just the near legs |
| Balancing valve type and settings | Lets the next person re-balance to the same basis |
| Pump control type and setpoints | The energy strategy and the Legionella floor it must hold |
| Far-fixture wait time | The wait the loop and the branch lengths actually deliver |
Common mistakes
- Oversizing the pump to chase a cold far riser, which drives the velocity past the copper limit and erodes the pipe at the fittings.
- Leaving the supply and return uninsulated, so the loop heat loss and the pump flow are both far higher than designed and the far end still runs cold.
- No balancing valves on a multi-riser loop, so the near riser hogs the flow and the far riser starves and runs cold.
- Running the return the same size as the supply, so the flow slows, the water over-cools, and the loop loses temperature.
- A timer or demand control set so the loop sits cool overnight, dropping the return into the Legionella growth band.
- Capped or abandoned branches left as warm dead legs off a hot main instead of being cut back to the active pipe.
- Long, fat uncirculated branches off the loop, so the tap waits no matter how hot the loop runs.
- Returning the cooled loop water into the top of the tank instead of low, mixing cool water into the hot delivery zone.
Field checklist
Want this checklist to run itself on every job — with photo proof and a signed record crews can hand the customer? That's FieldOS.
Standards and references
The plumbing code is the framework, and the adopted edition with local amendments controls. The International Plumbing Code and the Uniform Plumbing Code both address the circulation pieces: when a recirculation loop, a heat-traced line, or another approved means is required by the developed length from the source to the fixture; the limit on uncirculated branch length; and the insulation required on circulated piping. Confirm the section numbers against the edition the jurisdiction has adopted before citing them on a submittal.
For Legionella in the loop, ANSI/ASHRAE Standard 188 sets the legionellosis water-management framework for building water systems and ASHRAE Guideline 12 gives the supporting practice, with the CDC potable-water guidance treating temperature control as a primary defense. The energy side is governed by the energy code. ASHRAE Standard 90.1, Section 7, Service Water Heating, sets pipe-insulation and recirculation-control requirements on commercial work, and the adopted energy code and local amendments control which applies. The pump itself is sized and selected against the manufacturer's published curve and the engineer's loop calculation, not a rule of thumb.
Sizing the heater that feeds the loop, its recovery and storage, the storage and tempered-delivery temperatures, and the thermal-expansion control on the closed system are covered in the water heater sizing and selection guide. Cite the standard that controls the point, and let the project specification, the engineer's calculation, and the equipment listing override any rule of thumb in this guide.
Units, terms, and conversions
Recirculation work mixes a few units and a few names for the same thing, so the same value can read differently across a schedule, a cut sheet, and a spec.
Recirc flow is in gallons per minute, GPM, and it is small, often only a few GPM. Loop heat loss is in BTU per hour, and one gallon of water carries about 8.33 BTU per degree F, which is the 500 constant once you account for 60 minutes per hour. Pump head is in feet. Velocity is in feet per second, and copper recirculation is commonly held to roughly 2 to 3 feet per second above 140°F to keep erosion in check. Temperatures appear in Fahrenheit on most US drawings and in Celsius on Legionella references, so a 124°F return floor is about 51°C. A crossover or comfort valve is the thermostatic bridge used in a return-less retrofit, and a circulator is the small pump that drives the loop.
- Recirculation loop
- The supply-and-return circuit that keeps hot water moving so it is hot at the far fixture
- Dedicated return
- A separate return pipe from the end of the supply back to the heater
- Comfort / crossover valve
- A thermostatic valve bridging hot to cold under the far fixture in a return-less retrofit
- Balancing valve
- Valve on a return branch that sets each riser's recirc flow to hold temperature
- Return temperature
- The temperature of the water coming back to the heater, held above the growth-band floor
- Erosion-corrosion
- Wall thinning in copper from high-velocity hot water, worst at fittings and direction changes
- Dead leg
- An uncirculated branch the loop does not reach; the source of tap wait time and stagnation
- Demand-controlled recirculation
- A control that runs the pump only when a fixture calls for hot water
FAQ
How do you size a hot water recirculation pump?
Size the flow from the loop's heat loss divided by 500 and the allowed temperature drop, commonly 10°F to 20°F, which on most loops is only a few GPM. Then size the head to the longest circuit and fittings at that flow, reading the pump curve at the design point. Insulate the piping first to cut the heat loss.
What is the difference between a dedicated return and a comfort-valve system?
A dedicated return runs a separate return pipe from the far end of the supply back to the heater, so the whole loop stays hot and balances cleanly. A comfort-valve system has no return pipe; a thermostatic crossover valve under the far fixture pushes cooled water back through the cold line, which suits a retrofit but warms the cold tap.
How do you balance a recirculation loop?
Set a valve on each return branch so every riser gets the flow to make up its own heat loss, not just the branch nearest the pump. Manual valves are dialed in at commissioning with a thermometer on each riser; thermostatic balancing valves modulate to a return-temperature setpoint and stay balanced as the building load changes.
Does a recirculation loop cause Legionella?
No. A loop run hot through its full length is a Legionella control, not a cause. The risk is a loop run too cool, a starved far riser sitting in the growth band, or warm uncirculated dead legs. Keep the return above roughly 124°F, balance every leg, and remove capped warm branches. ASHRAE 188 and the AHJ govern the program.
Why does my far fixture still run cold with a recirculation pump?
Usually the loop is unbalanced, so the near riser grabs the flow and the far riser starves, or the branch from the loop to that fixture is a long uncirculated dead leg. Check the balancing valves and the return temperature at that riser first. Adding pump only erodes the short path; it does not feed the far leg.
How small should the return line be on a recirculation loop?
The return carries only the recirc flow, not fixture demand, so it is commonly one or two sizes smaller than the supply it serves. Size it for the heat-loss flow while keeping the velocity in range, roughly 2 to 3 feet per second in copper above 140°F, so the water moves without eroding the pipe at the fittings.
Should a recirculation pump run continuously or on demand?
It depends on the building and the energy code. Continuous keeps every tap instantly hot but reheats the loop losses all day. An aquastat runs the pump only when the return drops below a setpoint, and demand control runs it only when a fixture calls, saving the most energy. Never let the control park the loop in the growth band.
What return temperature should a recirculation loop hold?
A common design floor is a return at or above roughly 124°F (51°C) at the heater, so the coolest point in the loop stays out of the bacteria growth band. The supply leaves storage hotter to give the loop room to lose a few degrees end to end. Confirm the target against the project's water management program.
Why is my recirculation loop noisy or eroding the copper?
An oversized pump or an undersized return drives the velocity past the limit copper tolerates, roughly 2 to 3 feet per second for hot water above 140°F. The fast, hot, turbulent flow strips the protective oxide film and thins the wall at elbows and fittings. Size the pump to the loop and bring the velocity down.
People also ask
Codes cited in this guide
This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.