ASHRAE 188: program applicability and Legionella testing evidence

ASHRAE 188-2021 establishes risk-management requirements for building water systems across construction, commissioning and operation. Start by identifying whether the building or an aerosol-producing device needs a water management program, then assign the controls, response duties and records for that scope. Legionella testing supports a program decision. When the team selects laboratory testing for validation, Addendum e adds method-specific accreditation and annual proficiency requirements; that annual interval belongs to the laboratory, not the building's sampling calendar.

Current edition: ANSI/ASHRAE Standard 188-2021 (2021), with published Addendum e
Updated

Official publisher page

Applies to

A mixed-use property can place the domestic water plant under the building owner and a tenant's aerosol-producing equipment under a separate operator. Assign program responsibilities by water circuit, rather than ordering a building-wide sample package under one address. Standard 188 reaches potable and nonpotable systems, so the domestic-water agreement needs a defined boundary with the tenant's process-water responsibilities.

Standard 188 is a consensus standard whose mandatory use follows incorporation into applicable rules or project requirements. ASHRAE explains that the 2021 revision replaced permissive wording with enforceable language to make code and regulatory adoption more practical. The edition incorporated into a requirement and the publisher's latest edition are separate entries in the program's reference register. ASHRAE 188-2021 publisher overview

Key topics

Building screening and device screening produce different scopes

CDC's toolkit for implementing ASHRAE 188 flags buildings with more than 10 stories, counting basement levels, and buildings with multiple housing units and centralized hot water for a building water management program. Its screening also flags overnight patient care, people with chronic or acute illness or weakened immunity, and buildings primarily housing adults older than 65. CDC identifies cooling towers, hot tubs not drained between uses, decorative fountains and centrally installed aerosol-producing devices for device programs even when building screening is negative. Its building-program screen excludes single-family homes and small multifamily residences such as duplexes. CDC building and device screening

Selecting a laboratory for program validation

ASHRAE 188-2021 Addendum e requires the laboratory selected for program-validation testing to be accredited to ISO/IEC 17025 or another nationally or internationally recognized laboratory accreditation standard and to demonstrate competence to an accreditation body. Request the certificate and its scope together. Accreditation for unrelated microbiological work leaves the proposed Legionella method unqualified for this requirement. Laboratory validation conditions

Method coverage and annual proficiency are separate checks

Under Addendum e to ASHRAE 188-2021, the Legionella method used for validation must appear within the laboratory's accreditation scope. ASHRAE 188-2021 Addendum e requires at least annual Legionella proficiency testing acceptable to the accrediting body for a laboratory method used to validate a water management program. The annual interval concerns laboratory proficiency, not the frequency for sampling a building's water. Confusing the two assigns a laboratory quality requirement to the wrong activity.

A result needs a location and a response decision

Connect each sample to the current water-system diagram, collection point, test method and intended program decision. Preserve the report's units and detection information. A result from a tower basin does not describe a distant domestic hot-water return; separate circuits and sampling objectives need separate identification. The program team needs enough context to decide whether the evidence supports its control strategy.

How it is used in the field

At laboratory procurement, request the current certificate, the scope naming the proposed method and the relevant proficiency-testing evidence. Put the method identity into the sampling agreement. If a laboratory proposes a different method during the contract, route that change through the program team before results are placed into an existing trend.

A laboratory report of 10 CFU/mL and another of 10,000 CFU/L express the same concentration. Preserve the original units and reporting limit before normalizing a trend; otherwise, a unit change looks like a thousandfold change in the water. Addendum e also calls attention to method sensitivity, detection limit and specificity, so carry those method details into decisions about comparing reports.

Maintain a single change record when equipment, piping or operating schedules change. Update the system description and affected sampling locations together so an obsolete point name cannot silently remain on the laboratory order. A replacement cooling-tower cell and an abandoned domestic branch create different water-system changes, even when both are handled during the same shutdown.

Give each departure from a control limit its own record linking the affected circuit, measured condition, assigned response and follow-up evidence. CDC's program guidance links these interventions to the selected control limits and calls for updates when the system or program changes. The cooling-tower operation guide supplies the equipment context; the program record establishes which loop and operating condition the response addressed.

Edition history

The base edition is 188-2021. Addendum e, approved September 30, 2021 and listed by ASHRAE in October 2021, establishes normative laboratory-validation requirements in Appendix B. ASHRAE Guideline 12-2023 supplies supporting system-specific guidance; it is a companion document, rather than a replacement edition of Standard 188.

Frequently asked questions

Does annual proficiency testing mean annual water sampling?

No. The Addendum e annual requirement applies to proficiency testing of the laboratory method. The building program must separately identify its sampling purpose, locations, frequency and response criteria, together with any applicable public-health requirements.

Is a laboratory accreditation certificate enough?

Obtain the scope naming the actual Legionella method and evidence of its proficiency testing. A certificate covering other microbiological services leaves the method-specific requirement unresolved. Keep all three records with the sampling agreement so a replacement laboratory is reviewed on the same basis.