Measure single-ply distress, calculate separate membrane and flashing indexes, reconcile inspectors, and preserve a repair-ready survey record.

ROOFERRoof condition ratingSingle-ply roofsDistress surveyFacility management

Direct answer

Rate each single-ply roof section separately by recording distress type, severity and quantity, converting those quantities to the densities defined in USACERL's April 1993 ROOFER manual, and applying its deduct-value and correction curves. Subtract each component's maximum corrected deduct value from 100 to obtain the membrane condition index, MCI, and flashing condition index, FCI. Keep the measured repair quantities beside both scores and resolve inspector disagreements against the same defect definitions before issuing the rating.

On this pageWhat does a USACE ROOFER roof condition rating measure?How do you define the roof section and its denominators?How do you survey the entire roof, including ballasted seams?How do you classify membrane and flashing distress severity?What goes in a measured-distress worksheet?How do you calculate MCI and FCI from distress density?Where do current manufacturer instructions differ from the 1993 method?Worked example: 3,462 square feet, MCI 62 and FCI 67How do two inspectors compare and reconcile their ratings?How do you turn a condition score into repair quantities?How much survey time should you allow?How often should you inspect and repeat the rating?Field checklist for a checked ROOFER worksheet
Need to run this in the field?

Open the related tool for the calculation, checklist, or packet.

What does a USACE ROOFER roof condition rating measure?

Rate each single-ply roof section separately by recording distress type, severity and quantity, converting those quantities to the densities defined in USACERL's April 1993 ROOFER manual, and applying its deduct-value and correction curves. Subtract each component's maximum corrected deduct value from 100 to obtain the membrane condition index, MCI, and flashing condition index, FCI. Keep the measured repair quantities beside both scores and resolve inspector disagreements against the same defect definitions before issuing the rating. [S01, pp. 17 to 21]

USACERL Technical Report FM-93/11, April 1993, produces separate 0 to 100 indexes for observable membrane and flashing condition. Its distress deductions address component function, maintenance need and waterproof integrity. A deduct value is the penalty read from a distress curve; a corrected deduct value adjusts combined penalties using the component's correction graph. [S01, pp. 7 to 10, 20]

Here FCI means flashing condition index. It is distinct from the facility-management ratio of deferred maintenance cost to replacement value. The report discusses EPDM, PVC and Hypalon; it neither names TPO nor provides a TPO-specific validation dataset. Identify the material before choosing a historical score or a documented modern-system adaptation. [S01, pp. 7 to 8]

What each evidence layer answers
LayerInputRetained result
MembraneMapped distress; section areaMCI; membrane scope
FlashingMapped distress; flashing lengthFCI; detail scope
InsulationMoisture survey; core analysisSeparate insulation assessment
InfraredThermal data; verificationWet-insulation locations
Electronic scanCompatible assembly; calibrated scanBreach locations

FM-93/11 directs insulation and combined roof-condition evaluation to M-90/04; averaging MCI and FCI does not produce that overall ROOFER index. ERDC's current ROOFER description evaluates insulation through moisture surveys and gravimetric core analyses. Enter untested insulation as not assessed. [S01; S02, FM-93/11 p. 8]

ASTM C1153-23 covers nighttime infrared location of wet insulation above the deck and in contact with waterproofing, with invasive verification; moisture location does not establish its entry point. ASTM D8231-24a addresses electronic breach detection alongside other inspection methods. Keep those results with the visual rating and use electronic leak detection for the compatible assembly. Carry the resulting work scope into commercial roof capital planning. [S07; S08]

How do you define the roof section and its denominators?

USACERL FM-93/11 recommends sections of 25,000 to 40,000 square feet for large roofs without obvious physical divisions. First separate different levels, systems, construction dates and materially different conditions beneath the roof. Combine similar small canopies only when age, construction, structural system and conditions below the roof match. [S01, p. 10]

Measure the whole section area and complete flashing length, including curbed projections, penthouses and courtyards. Using only distressed runs in the flashing denominator inflates density. The roof measurement guide explains takeoff geometry; a roofing square equals 100 square feet, while this calculation uses square feet. [S01, ch. 3]

Draw a scaled plan with north, boundaries, dimensions, details and access. Keep section IDs and plan revisions stable across surveys.

FM-93/11 Figure 7: section header
FieldPublished value
Asset / surveyBuilding 97, Section B / 1992-07-27
Area3,462 sq ft
Flashing271 ft perimeter + 70 ft curbs = 341 ft
Manufacturer / attachmentNot identified
Scoring editionFM-93/11, April 1993

Keep inspector and recorder roles, material, attachment, installation history, warranty identifier, applicable manufacturer details, weather and visibility exclusions in the header. Mark each quantity as directly measured or expanded from sampling. Figure 7 supplies the historical header above; its July 27, 1992 survey date stays distinct from this page's November 5, 2026 review date. [S01; S03; S05]

How do you survey the entire roof, including ballasted seams?

USACERL FM-93/11 calls for at least two people, an inspector and a recorder, with membrane coverage in strips 10 to 15 feet wide. The recorder assists measurements and observes safety; that role does not establish the roof's fall-protection arrangement. Plan authorized access and protection using the roof fall-protection guide before walking the section. [S01, pp. 14, 16]

Survey perimeter flashing, other flashings and penetrations, then the membrane. Assign each finding a plan location, defect number, severity and quantity; Anvilfield adds a photograph showing the measurement. Postpone the rating walk when snow or extensive ponding conceals the section, and mark inaccessible areas as uninspected. [S01, pp. 14 to 17]

FM-93/11 coverage and sampling
ConditionCoverageExpansion
Exposed membraneWhole section; 10 to 15 ft stripsNone
Uniform distressRepresentative sample; map populationPopulation / sample extent
Initial ballasted seamsFive 5-ft exposuresNone from screening alone
Defect found; sheets ≤10 ft wide2% seam length×50
Defect found; sheets >10 ft wide4% seam length×25
Embedded metal beneath ballastEvery fourth joint×4; joint split = 1 scoring ft

USACERL's April 1993 ballasted-roof procedure begins with five 5-foot seam checks and, when a defect is found, expands to 2% seam sampling for sheets up to 10 feet wide or 4% for wider sheets. With no defects in the initial checks, the manual treats the remaining field seams as satisfactory. The systematic sample uses 2-foot exposures every 100 seam feet for sheets up to 10 feet wide, or every 50 seam feet for wider sheets. Keep screening observations separate from the systematic sample totals. Record actual sampled length and defect length before applying the matching expansion factor; restore the ballast afterward. [S01, pp. 16 to 17, 57]

Selecting only suspect seams does not create a representative density. For broadly uniform distress, the manual permits representative samples, such as 1,000 square feet of membrane or 100 feet of flashing. Map both the sample and the affected population so the expansion can be checked. [S01, p. 16]

Walk the interior and exterior too, recording occupant leak reports, ceiling marks, exterior staining and drainage observations. Connect them to the plan without assigning an unseen membrane defect from a ceiling stain. For exposed-roof seams, Carlisle's June 26, 2026 pre-inspection guide calls for all-seam inspection and additional TPO/PVC probing; keep its installation guidance and the single-ply seam QA procedure distinct from historical ballast sampling. [S01; S12]

How do you classify membrane and flashing distress severity?

Classify the location first: field-sheet distress affects MCI; defects in edge and curb flashings, flashed penetrations and drains affect FCI. Use the named defect and its measurement rule, then assign severity. USACERL FM-93/11 uses the highest severity of the same distress within a localized area; entering that area again at a lower severity duplicates the finding. Preserve the defect number so another inspector can trace the classification. [S01, pp. 14, 17]

Identify the attachment system before classifying securement; system type and edge distance change its thresholds.

Selected FM-93/11 severity triggers, printed pp. 23 to 78
Code / locationSeverity triggerQuantity
SP, field splitHigh only: through crack/tearft
HL, mechanical damageLow scuff; medium thickness loss; high penetrationCount isolated defects; group those <1 ft apart; cuts >1 ft by length; abrasion sq ft
DS, field seamLow: seam open <1/2 in.; medium: ≥1/2 in. without water path; high: opening through the seamft
SS, fully adheredLow ≤2 sq ft; medium above 2 below high thresholdUnattached sq ft
SS, adhered field / perimeterHigh: ≥100 sq ft in field; ≥25 sq ft within 10 ft of edgesq ft
SS, ballastLow bare area ≤4 sq ft; medium above 4 below 100 field/25 perimeter; high at those thresholdsBare sq ft
SS, mechanical attachmentMedium isolated failure; high adjacent failuresEffective unsupported sq ft
MD, deteriorationLow crazing; medium exposed layer/thickness loss; high through-weatheringsq ft
PA, field patchDissimilar permanent: low minimum; temporary: medium minimum; high distress: highPatch sq ft; high distress counted here
PD, ponding >48 hrLow general; medium from folds/bowed substratesq ft
BF, base flashingLow: top <6 in. above membrane; medium: unbonding without water entry; high: through-openingft
DR, drain/scupperMedium missing/broken strainer; high blocked drain/missing clampEach, highest severity
PP, pitch panLow minimum; medium coating loss; high cracked/separated sealer or sealer below rimEach, highest severity
EQ, equipment supportLow improper support; medium displacement or sealed bolt penetration; high puncture or unsealed penetrationsq ft; each dimension ≥1 ft

For DS, water entry through the seam makes the defect high even when the visible opening is narrow. Three location rules prevent common miscoding. A compatible repair in membrane base flashing is BF low, while a similar-material field repair is not PA. A hole within 2 feet of a drain or roof-level scupper is included in DR high; use the specific detail definition before selecting HL. [S01, pp. 23, 45, 71]

Partially adhered securement distinguishes isolated failed attachment points, medium, from adjacent failed points, high, and measures effective unsupported area. The historical 10-foot perimeter zone in the securement definition is a distress-classification zone. Current wind-design zones and current flashing-height requirements require their own governing details. [S01, p. 65]

Separate splits from mechanically caused cuts, membrane support from securement, and coating loss from membrane loss. Use the full defect lists at the linked curve pages for conditions omitted from the summary table. Record rainfall timing when classifying ponding, and use the penetration-flashing guide to identify the physical detail that needs repair. [S01, pp. 50, 54, 61, 63, 69, 78]

What goes in a measured-distress worksheet?

Keep observation, method quantity and repair quantity in separate columns. A split over an embedded-metal joint contributes one scoring foot, but repair dimensions come from the actual detail. A distressed drain contributes a count divided by total flashing length, rather than a fraction of the roof's drain count. [S01, pp. 36, 45 to 46]

For defective field seams, USACERL FM-93/11 divides distressed seam length in feet by roof-section area in square feet and multiplies by 100, rather than dividing by total seam length. The manual's density label includes mixed units as well as area percentages. Sum entries by component, code and severity only after preserving each mapped raw finding. [S01, pp. 57 to 58]

FM-93/11 quantity dictionary
CodesMethod quantityDenominator
BF membrane base / BC coated-metal base / MC metal capDistressed ft; specific discrete defects as scoring ftTotal flashing ft
EM embedded edge metalDistressed ft; joint split = 1 scoring ftTotal flashing ft
FP flashed penetrationsSmall penetration = 1 scoring ft; metal curb/duct perimeter >1 ft: distressed perimeter ftTotal flashing ft
PP pitch pans / DR drains and roof-level scuppersDistressed units, eachTotal flashing ft
SP splits / RG ridges / DS seamsDistressed ftSection sq ft
HLDefined count, cut length or abrasion areaSection sq ft
SC surface coating / MD membrane deterioration / SS securement / MS support / PA patching / DV debris and vegetation / PD pondingAffected sq ft; identify category mechanismSection sq ft
EQ equipment supportsSupport area; minimum 1 ft each dimensionSection sq ft
Copyable section worksheet
RecordFill-in fields
Section headerID ___; date ___; edition ___; material/attachment ___; area ___ sq ft; perimeter ___ ft; curbs ___ ft
Distress item, repeat as neededLocation/photo ___; code/defect ___; severity ___; measured quantity/unit ___; sample fraction ___; method quantity ___
Component calculationCode/severity totals ___; densities ___; curve/page ___; deductions ___; successive sums/q/CDVs ___
ResultMCI ___; FCI ___; bands ___; urgent findings ___; exclusions ___
Reconciliation and follow-upOriginal A/B records ___; changed item/reason ___; final measurement ___; repair/detail ___; next survey ___

Use separate statuses for not inspected, not applicable, observed and clear, and measured zero. These are Anvilfield export conventions. Keep distress_code DV, debris and vegetation, separate from deduct_value so the two uses of DV cannot collide in a spreadsheet.

Copyable CSV header

section_id,survey_date,edition,roof_area_sq_ft,total_flashing_ft,item_id,location,component,distress_code,defect_number,severity,raw_quantity,raw_unit,sample_fraction,expansion_factor,method_quantity,density,curve_page,deduct_value,repair_quantity,repair_unit,repair_detail,photo_id,disposition

Convert metric measurements before historical curve lookup. NIST SP 811, 2008 Appendix B, defines the international foot as exactly 0.3048 metre. Keep full conversion precision in the calculation and round displayed measurements to two decimals. [S19]

Anvilfield estimates the published 15-foot DS entry's density as 0.43 using 3,462 square feet. Entering the equivalent 4.57 metres and 321.63 square metres directly gives 1.42, the wrong numeric input for that historical curve. Method note: the area conversion is exactly 0.3048 squared, or 0.09290304 square metre per square foot. Compare 100 times length divided by area in each unit system; length/area ratios change numerically with units. [S01; S19]

Keep density numeric, without an extra spreadsheet percentage conversion.

How do you calculate MCI and FCI from distress density?

Multiply distress quantity by 100 and divide by its dictionary denominator, then read the matching type-and-severity curve in FM-93/11 Appendix A. Keep components separate.

Sort deductions from largest to smallest, then calculate successive groups: the largest alone, the largest two, and so on. For each group, retain the sum and q, the number of included deductions greater than one point. Read the corrected deduction from the component's correction graph; q counts deductions, not densities above 1%. [S01, pp. 20 to 21]

USACERL's April 1993 ROOFER manual calculates membrane and flashing condition indexes separately by subtracting each component's maximum corrected deduct value from 100. The maximum can occur before all deductions have been included. Subtracting the raw sum or keeping only the last corrected result changes the method. [S01, pp. 20 to 21]

density = 100 × Q / B
FCI = 100 − max(CDV_flashing)
MCI = 100 − max(CDV_membrane)

Q is the category quantity; B is section square feet or total flashing feet as the dictionary specifies. CDV is corrected deduct value.

Follow density vertically to its severity curve and read horizontally to the deduction axis. Distress-density axes are logarithmic; the correction plots have their own axes. Record graphical interpolation for q values between labeled curves, and retain the plot reference and reading. The published example supplies its own q = 3, 5 and 7 readings. [S01, Appendix A; Table 1]

Curve locator: printed pages in the full manual

Download FM-93/11 with Appendix A. Flashing: BF membrane base and BC coated-metal base, p. 81; MC metal cap and EM embedded edge, p. 82; FP penetrations and PP pitch pans, p. 83; DR drains/scuppers, p. 84; correction, p. 85. Membrane: SP splits and RG ridges, p. 86; HL holes/cuts/abrasions and DS seams, p. 87; SC coating and MD deterioration, p. 88; SS securement and MS support, p. 89; PA patching and DV debris/vegetation, p. 90; EQ supports and PD ponding, p. 91; correction, p. 92.

Some families lack one or more severity curves: SP is high only; RG low/high; SC, MS and PD low/medium; DV medium/high. Use the defined family without inventing a missing curve. An inspected component with no defined distress scores 100. Record inaccessible areas as uninspected, not defect-free; inputs beyond the plots need documented method/software handling. [S01, chs. 2, 4; Appendix A]

Descriptive condition bands and boundaries
Figure 1 bandBoundaries on the 0 to 100 scaleExample safely within band
Excellent85 and 10095
Very good70 and 8580
Good55 and 70MCI 62, FCI 67
Fair40 and 5550
Poor25 and 4035
Very poor10 and 2520
Failed0 and 105

Retain the numeric score when it falls exactly on a named band boundary. Figure 1 does not supply a precision convention for assigning that shared boundary. Its descriptive bands do not establish an automatic replacement score; the capital guide's approximate planning cutoffs serve a separate decision. [S01, Fig. 1]

Where do current manufacturer instructions differ from the 1993 method?

Keep historical scoring and current repair compliance in separate fields. An unchanged historical rating preserves its calculation basis; a modified taxonomy needs a named adaptation. For TPO, use the actual manufacturer's inspection criteria and identify any application of the 1993 taxonomy as an adaptation unless applicability has been established. [S01, pp. 7 to 8]

Modern EPDM tape and PVC edge instructions expose specific conflicts with the historical blanket sealant definition.

Historical method and current product crosswalk
Topic1993 scoringCurrent instruction
EPDM lap sealantMissing = DS lowCarlisle SAT discussion, 2020-10-14: butyl tape eliminates general need
EPDM detail sealantBlanket seam wordingCarlisle July 2025 §8C: tape overlaps, T-covers, metal intersections, Elastoform/reinforced cut edges
Sikaplan PVCMissing = DS lowSika 06/2025 brochure: unnecessary against absorption
SENTINEL PVCSame generic wordingSOPREMA, undated: seal non-factory cut edges against wicking
PondingPD after 48 hrCarlisle F0001 Rev 12/24: evaporate within 48 to 72 hr
Ponding warrantyNo coverage decisionSika, undated: Sarnafil warranties have no ponding exclusion

Use the named product detail and issued warranty for repairs. Sikaplan and SENTINEL have different edge-sealant instructions; transfer neither instruction across PVC products. [S15; S18]

Ponding likewise has three separate records: historical distress classification, drainage-maintenance action and actual warranty coverage. Use ponding diagnosis for the cause, roof warranty terms for coverage, and seam QA for the product's inspection technique. A historical low-severity entry alone does not order replacement of sound modern construction. [S01; S03; S06]

Sealant sources: FM-93/11 p. 57; Carlisle 2020 splice discussion; July 2025 EPDM guide, section 8C.

Worked example: 3,462 square feet, MCI 62 and FCI 67

In the published 3,462-square-foot ROOFER example, maximum corrected deductions of 38 for membrane and 33 for flashing produce MCI 62 and FCI 67, both rated good despite high-severity seam and drain findings. The underlying survey is Building 97, Section B, July 27, 1992, published in April 1993. [S01, Fig. 7; Table 1, pp. 19 to 21]

Published quantities and deductions with recalculated densities
Component and distressPublished severityPublished method quantityDenominatorRecomputed densityPublished curve deduction
Flashing, coated-metal base BCHigh20 scoring ft341 ft5.8722
Flashing, embedded metal EMHigh4 scoring ft341 ft1.1711
Flashing, embedded metal EMMedium2 scoring ft341 ft0.596
Flashing, membrane base BFMedium2 scoring ft341 ft0.594
Flashing, metal cap MCHigh1 scoring ft341 ft0.297
Flashing, drain/scupper DRHigh1 each341 ft0.2928
Flashing, pitch pans PPLow4 each341 ft1.174
Membrane, ponding PDLow40 sq ft3,462 sq ft1.164
Membrane, securement SSHigh50 sq ft3,462 sq ft1.4423
Membrane, defective seams DSMedium10 ft3,462 sq ft0.295
Membrane, defective seams DSHigh15 ft3,462 sq ft0.4332

Quantities and curve deductions above are the report's entries. Anvilfield estimates the displayed densities from those quantities and the 3,462-square-foot and 341-foot denominators, multiplying each ratio by 100. The source used its own rounded density entries for curve reading: 50 square feet produces 1.44 here and appears as 1.4 on the original form. [S01, Fig. 7]

Successive deduction groups and final indexes
Number of highest deductions includedFlashing included sequenceFlashing sum / q / corrected resultMembrane included sequenceMembrane sum / q / corrected result
12828 / 1 / 283232 / 1 / 32
228, 2250 / 2 / 3232, 2355 / 2 / 38
3Add 1161 / 3 / 33Add 560 / 3 / 37
4Add 768 / 4 / 33Add 464 / 4 / 34
5Add 674 / 5 / 32Complete at 4Not applicable
6Add 478 / 6 / 32Complete at 4Not applicable
7Add final 482 / 7 / 29Complete at 4Not applicable
Maximum correctionThird and fourth groups33Second group38
Final component index100 minus 33FCI 67, good100 minus 38MCI 62, good

The actionable record includes 15 feet of high-severity seams and one high-severity drain/scupper. Keep those mapped work items beside the good ratings. Figure 7 does not identify the securement system, so its 50-square-foot high SS entry remains the published classification without an inferred attachment mechanism. [S01, Fig. 7]

How do two inspectors compare and reconcile their ratings?

Give both inspectors the same boundaries, edition, reporting units and blank location grid. Each saves an independent detection, classification and measurement record before viewing the other's findings. Match IDs by location afterward, resolve the raw observations, then recompute both indexes. This independent-comparison workflow is Anvilfield's addition to the manual's definitions.

Compare detection, matched type/severity, quantity differences within common units, and final MCI/FCI point differences separately. Anvilfield's proposed issuance rule requires reconciliation of every through-opening disagreement, denominator mismatch and edition difference. A similar score can conceal a different water-entry work list.

Calculation-path reconciliation exercise
CheckA: checked pathB: one assigned error per caseIssued result
Flashing denominator271 + 70 = 341 ft271 ft perimeter only341 ft
BC high, 20 ftDensity 5.877.38; +25.83%5.87
DR high, 1 each1 / 341 ×100 = 0.29One of one = 1000.29
Flashing calculationMaximum CDV 33Raw sum 82; FCI 18FCI 67; 49-point correction
Membrane calculationMaximum CDV 38Raw sum 64; MCI 36MCI 62; 26-point correction
Final correction onlyUse maximumsFCI 71; MCI 6667 / 62; each 4 points lower

A and B are desk-exercise roles. Each row isolates one error while retaining the other published inputs; the score rows use the published deductions. Anvilfield estimates the 25.83% density increase by dividing 341 by 271, subtracting one and multiplying by 100. Changed densities require fresh curve readings before calculating new scores.

Anvilfield detection, severity and quantity exercise
Source row / AAssigned B inputReconciliation evidence
DS medium, 10 ft12 ft, mediumRemeasure endpoints; +2 ft / +20% relative to A
DS high, 15 ft15 ft, mediumSource retains high; field dispute requires through-path evidence
PP low, 4 pansOmitted as soundManual p. 42: every pan at least low; map pans
SS high, 50 sq ftSameField record needs attachment, boundary and edge distance

Anvilfield estimates detection overlap at 75%, three matched rows divided by the union of four assigned rows, and matched type/severity agreement at 66.67%, two exact matches divided by three matched rows. The four pans form one aggregated exercise row. For field comparisons, use mapped individual defects and state the matched and total counts.

Remeasure disputed endpoints, establish whether a seam has a through-water path, and restore omitted method entries. If access or evidence cannot settle a dispute, retain its unresolved status and the affected work item; issue the rating as provisional. Save both originals and each disposition. Resolve severity before recalculation rather than averaging low/medium/high labels or final scores. Shared marked ballast exposures compare classification; independently selected exposures also introduce sampling variation, so record which design was used.

How do you turn a condition score into repair quantities?

Mapped defects define work quantities; the index describes component condition. Carry direct repairs separately from investigation areas. The published 50 square feet of securement distress requires attachment diagnosis, while its 40 square feet of ponding requires drainage diagnosis; neither quantity establishes wet-insulation area. [S01, Fig. 7; pp. 65 to 66, 78]

Published findings to repair scope
FindingCarry-forward quantityAction / missing takeoff information
DS high / medium15 + 10 = 25 seam ftCompatible repair; actual material, strip width, overlaps
DR high1 unitIdentify defect; clear/repair and verify; drain parts
EM high / mediumSix 1-ft entriesRecover identities; joint/continuous geometry, sampling and repair dimensions
BC high20 scoring ftLocate affected termination; height and assembly
BF medium2 scoring ftLocate defect; count/length, height and detail
MC high1 scoring ftLocate cap defect; affected section and fixings
PP low4 pansCompatible filler maintenance; condition/volume
SS high50 sq ftIdentify attachment failure; substrate and repair design
PD low40 sq ftDiagnose drainage; elevations and depression cause

A method foot is not automatically a continuous repair foot. The EM worksheet contains six one-foot entries without establishing six damaged joints; BC and MC likewise need the original defect identities and repair geometry. Confirm flashing heights, termination, substrate and compatible materials through the actual flashing detail before ordering. [S01, Fig. 7; ch. 3]

For Carlisle's described improperly installed EPDM tape-splice repair, its July 2025 Field Guide section 8D.3 specifies a minimum 6-inch overlay centered over the splice edge. Anvilfield estimates 12.5 square feet of net strip coverage for 25 linear feet at that width, before end details, intersections and waste. Method note: multiply 25 feet by 0.5 foot; the actual segment layout determines order quantity. This is a separate Carlisle repair-detail calculation from the unidentified Building 97 membrane. [S17, p. 104]

Issue urgent defects beside the score. The owner sequences work by water entry and consequences; use capital planning for renewal economics, with moisture evidence where needed. A score alone determines neither load capacity nor remaining years.

How much survey time should you allow?

Anvilfield estimates eight person-hours for one rating of a small exposed-roof section: two people on the roof for three hours, plus two reporting hours. Two independent passes with reconciliation require 16 person-hours under the planning inputs below.

Anvilfield estimates: survey staffing and time, November 5, 2026
Planning inputOne ratingTwo passes and reconciliation
Field team2 people2 people per pass
On-roof allowance3 hours3 hours per pass
Field labor6 person-hours12 person-hours
ReconciliationNone2 person-hours
Reporting2 person-hours2 person-hours
Total labor8 person-hours16 person-hours

Method note: these Anvilfield estimates combine FM-93/11's two-person team with assumed field and reporting durations as of November 5, 2026. Multiply crew size by field hours, then add reporting and reconciliation labor. Each additional hour for the two-person team adds two person-hours. [S01, p. 14]

Set the allowance from access arrangements, detail count, ballast movement and the number of sections. Snow and standing water can defer observation; record rainfall timing for ponding and select comparable survey conditions. Scope moisture surveys, cores, repairs, lifts and laboratory work separately.

Define the survey territory and roof scope before setting route capacity. Group the survey territory by membrane material and building size with PorchRocket Ground Control so each route serves a defined roof-survey scope.

How often should you inspect and repeat the rating?

Carlisle's sample Care and Maintenance Guide F0001 Rev 12/24 calls for inspections at least every six months and after specified weather events. JM RS-7395 revision 3-26 specifies at least twice yearly or as the guarantee requires; Sika recommends spring/fall and severe-storm checks. Apply the roof's actual documents through its inspection and maintenance program. [S03; S04; S05]

Anvilfield proposes annual same-method condition scoring for a comparable owner trend, plus rerating after damage or major repair materially changes the section. This is a program choice separate from the OEM maintenance cadence. Keep geometry, edition, sample design and calculation basis consistent across rating dates.

Baseline and repeat-survey change log
Event / dateCondition or changeEvidence / next record
Baseline / 1992-07-27MCI 62; FCI 67; 3,462 sq ft; 341 ftFM-93/11 Figure 7; Table 1
Measurement correction / date ___Old quantity ___; revised quantity ___Reason, measurement and recalculated baseline
Repair closeout / unrecordedNo post-repair scoresWork order, detail, quantity, date, photo
Next rating / unrecordedNot measuredSame geometry/method; raw quantities and curves
Comparable change / pendingRequires second surveySecond minus first score; repaired/new quantities

Label measurement corrections, completed work and deterioration as different events. Correcting a denominator changes arithmetic rather than roof condition. Changed boundaries or interpretations require consistent recalculation of both dates before direct comparison.

Record as-found and post-housekeeping condition. FM-93/11 allows redistributed ballast and debris removed during inspection to affect the remaining scored distress; retain the action date and original observation. Calculate score change from comparable ratings, with repaired and new quantities beside it. Recalculate every density and correction after repair; nonlinear curve corrections mean that removing one defect does not add its original deduction directly to the score. [S01, pp. 65, 73]

Field checklist for a checked ROOFER worksheet

Deliver both indexes, unresolved findings, repair details and original notes together.

  • ☐ Confirm authorized roof access, protection and walking conditions; record areas that cannot be inspected.
  • ☐ Identify membrane, attachment, installed details and warranty; record FM-93/11, April 1993, as the scoring reference.
  • ☐ Draw and verify section boundaries, dimensions, north and fixed defect locations.
  • ☐ Measure section area and the complete flashing denominator, including curbed projections.
  • ☐ Assign an inspector and recorder; retain their roles with the survey record.
  • ☐ Complete the documented coverage and ballast-sampling sequence.
  • ☐ Record each mapped defect's type, defect number, highest applicable local severity, quantity and units.
  • ☐ Photograph the finding and measurement; preserve count, length and area separately.
  • ☐ For sampling, save sample locations, population extent, sample quantity and expansion factor; restore moved ballast.
  • ☐ Separate measured quantities, method scoring quantities and repair takeoff quantities.
  • ☐ Group by component/type/severity, calculate density and identify the exact Appendix A curve.
  • ☐ Retain successive sums, q counts and readings from the correct component correction graph.
  • ☐ Use the maximum corrected deduction and record both MCI and FCI with the survey date and condition bands.
  • ☐ Reconcile differing defect classifications, denominators and calculations; preserve the original entries.
  • ☐ Identify current OEM detail differences and separately scope urgent openings, drainage and attachment work.
  • ☐ Attach moisture or breach-location evidence where obtained; leave untested insulation unassessed.
  • ☐ Record repairs and remeasurements as separate dated events; schedule the next owner-program rating.

Survey and calculation checks follow FM-93/11 chapter 2 and Appendices A/B. Photographic IDs, independent comparison and revision conventions are Anvilfield additions. [S01; S02; S03; S05; S07; S08]

Review record and update log

By Anvilfield. Reviewed 2026-11-05 against the 14 primary sources listed below. Public ASTM scopes support the moisture and breach-detection descriptions; the full acquired FM-93/11 report supports the rating procedure.

2026-11-05: final article review. Rechecked source editions, severity and sampling rules, published calculations and manufacturer details; clarified inspector comparisons and repeat-survey records, and revised survey staffing estimates.

Cite the worked calculation or inspector comparison by its section anchor to preserve context.

How to cite this page: Anvilfield, How to rate a single-ply roof with the USACE ROOFER method, 2026, https://anvilfield.com/field-guides/roofing/roofer-roof-condition-rating-worksheet/

Related tools

Next step: Build a survey list

FAQ

What should a commercial roof condition rating worksheet include?

Section geometry, distress type/severity/quantity, density, curve deductions, corrected deductions, MCI/FCI, mapped repair quantities and the scoring edition.

What are the USACE ROOFER membrane and flashing condition indexes?

MCI and FCI separately subtract the component's maximum corrected deduct value from 100 under FM-93/11, April 1993.

How do you record roof condition survey severity and quantity?

Select the manual's specific defect and severity, then measure it using that category's count, length or area rule.

How do you improve roof condition rating inspector agreement?

Use common section geometry and definitions, preserve independent worksheets, and reconcile defect and calculation differences before issuing scores.

Is defective seam density based on total seam length?

The 1993 DS rating divides distressed seam feet by roof-section square feet and multiplies by 100.

Does a good ROOFER score mean there are no leaks?

No; the published example scores MCI 62 and FCI 67 while retaining high-severity seam and drain findings.

Do all single-ply seams need lap sealant?

Apply the named product detail; the 1993 blanket EPDM/PVC language differs from modern tape and PVC instructions.

How are seams checked on a ballasted roof?

FM-93/11 starts with five 5-foot seam exposures. A defect triggers 2% sampling for sheets up to 10 feet wide or 4% for wider sheets, followed by the corresponding expansion.

How often should a roof condition rating be repeated?

Anvilfield proposes annual same-method scoring and rerating after material damage or major repair. Follow the roof manufacturer's separate maintenance inspection schedule, commonly twice yearly in the cited guides.

Can MCI and FCI prove the insulation is dry?

No; ROOFER evaluates insulation separately using moisture-survey and core evidence.

Can I use square metres in a ROOFER spreadsheet?

Convert to the manual's feet and square feet before curve lookup; mixed length/area and count/length inputs do not stay numerically equal after a unit change.

Does a low roof condition index automatically mean replacement?

No; use the component's mapped repair scope, moisture evidence and consequences to make the repair or renewal decision; the historical bands are descriptive.