Datacenter
How to qualify wetted materials for a liquid-cooling loop
A supplier qualification package for exact coolant/material combinations: controlled exposure, leachables, corrosion, mixed-metal tests and finished-assembly release.
Direct answer
Qualify every wetted material against the exact coolant formulation, concentration and operating conditions, then test the assembled components before release. OCP's September 2026 propylene-glycol guidance gives a starting point of six weeks at 65 to 85 °C for polymer exposure and 336 hours at 88 °C for its modified metal-corrosion screen. Record the material identity, fluid changes, mechanical changes and separate mixed-metal results in a qualification file, then carry the approved combination into commissioning and supplier change control.
On this page
How do you qualify wetted materials for a liquid-cooling loop?Build a wetted-material register before ordering testsWhich OCP guidance and acceptance rules govern?What conditions belong in a coupon test?How much polymer change is acceptable?How do you measure coolant elastomer leachables?What metal-corrosion screen should you specify?How do you qualify mixed-metal and plated combinations?What must pass on the finished assembly?Which changes require requalification?What changes after installation?How long does qualification take, and what belongs in the estimate?Release record and citationOpen the related tool for the calculation, checklist, or packet.
HydroTest DCPressure-test package math, hold timing, thermal drift verdicts, witness signatures, and PDF/CSV records.How do you qualify wetted materials for a liquid-cooling loop?
Define the boundary before requesting evidence. This guide covers the single-phase aqueous technology cooling system (TCS), from the CDU secondary wetted surfaces through hoses, valves and cold plates. The hydraulically separate facility water system has its own material-fluid combination; immersion and two-phase refrigerants require different compatibility regimes. The direct-to-chip cooling guide explains those interfaces.
Identify the combination, review supplier reports, screen individual materials, evaluate relevant metal pairs, and validate finished assemblies. Keep three evidence packages, following OCP September 2026 §§8-9 and its cold-plate qualification paper:
| Stage | Object and retained evidence | Decision |
|---|---|---|
| Material screening | Named compound/alloy and fluid; exposure, controls, physical changes and fluid analysis | Advance, investigate or reject the combination |
| Assembly qualification | Finished wetted construction; exposure and functional results | Release the assembly within its tested envelope |
| Commissioning and operation | Installed loop; baseline, pressure records and fluid trends | Accept installed condition and manage chemistry |
A satisfactory pressure test establishes the tested pressure boundary. Keep both alongside the liquid-cooling commissioning record.
A compatibility claim must name the fluid trade name and revision, concentration basis, material grade or compound, supplier, manufacturing condition, temperature, duration, exposed area, fluid volume and acceptance source. Accept when all agreed material, fluid and assembly criteria pass; reject demonstrated failure; hold missing identity, controls, analytical capability or duty coverage. Each hold needs a named missing document or retest before purchase release.
Build a wetted-material register before ordering tests
Split each assembly into its wetted constituents. A copper cold plate also contains joining material; a hose assembly includes its liner, seals and fittings; a filter includes its binder, support and end seals. The register follows the actual fluid-contact surface, including temporary test hoses, fill carts, lubricants and service replacements.
| Location / material entry | Identity to retain | Evidence to request |
|---|---|---|
| Cold plate / C11000 copper | Finish, joining process, lot | Metal screen, pairs, finished-plate exposure |
| Manifold / 316L stainless | Weld, passivation, residual cleaner | Final-condition corrosion and cleanliness |
| Hose liner / peroxide-cured EPDM | Compound code, cure, fillers, cleaning | Mechanical changes and fluid purity |
| Connector seal / FKM | Exact compound and static/dynamic duty | Exposure and aged sealing function |
| Plated connector / nickel-chromium over brass | Substrate alloy, coating, wear condition | Worn-surface exposure and pair test |
| Braze / BCuP-2 | Nominal 93% copper, 7% phosphorus in OCP Table 3; filler lot and residues | Production joint and assembly test |
| Threaded joint / cured sealant | Product, cure schedule, applied condition | Fluid and particle compatibility |
| Filter / polypropylene medium | Binder, supports, seals, finish | Whole-element compatibility and shedding |
These entries define evidence requests, not approved products. Add supplier/site, part revision, drawing/BOM identifier, lot, loop location, wetted area, temperature range, peak and cleaning-fluid exposure, report identifier and procurement disposition to every row. A controlled supplier compound code preserves confidential formulation identity while allowing changes to be traced. OCP September 2026, §§6.2-6.5; OCP Cold Plate Development and Qualification.
OCP's September 2026 guideline recommends peroxide-cured EPDM and warns that sulfur-cured EPDM can introduce sulfate into the coolant, making the cure system part of the wetted-material qualification record. Cure agents, catalysts, plasticizers and other additives distinguish compounds within one polymer family. Parker identifies a peroxide-cured EPDM tube in its 627 cooling hose; that identifies a construction feature, while the exact coolant still needs compatibility evidence. Parker cooling-system product page; manufacturer 627 product description.
Which OCP guidance and acceptance rules govern?
Use OCP's Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks, Revision 2.0, Version 1.0.0, September 15, 2026. The OCP Cold Plate project index also links older contributions.
Vertiv SL-80056 Rev A, February 2025, expressly gives individual product manuals precedence over its general deployment guide. Establish the purchased equipment's limits first, then use OCP guidance to define evidence within that envelope. Conflicting fluid and equipment requirements need a written resolution accepted by affected suppliers and the design authority. Vertiv deployment guideline.
OCP's material lists are representative guidance, not product certification, a warranty or universal fluid approval. A PG25 designation identifies glycol concentration without identifying the entire inhibitor formulation. Water-based fluids follow the same evidence sequence with water-specific criteria; the PG exposure conditions below do not prescribe a water test.
| Issue | Source distinction | Practical rule |
|---|---|---|
| Material lists | OCP September 2026 §6 permits qualification; Vertiv Rev A §5.4 requires both its listed materials and the ASHRAE TCS list it references | A general listing does not amend equipment requirements |
| PTFE | OCP recognizes solid PTFE; Vertiv distinguishes contamination and prohibits threaded-joint PTFE tape | Qualify solid parts; exclude tape where prohibited |
| Sealant | Vertiv Table 5.3 names Loctite 564; §7 also mentions 567 | Specify the exact cured product; preserve product numbers |
| Cleaning | OCP §10 provides controlled cleaning; Vertiv §6.1 retains a new-fluid-supplier exception | Record the equipment/fluid-approved procedure |
| Hardness | OCP §8.12 mixes percent labeling with durometer change | Agree scale and point-change acceptance before testing |
| Rubber edition | OCP bibliography says D471-23; ASTM lists D471-16a(2021) | Record the discrepancy and verified method edition |
| Fluid stage | OCP water-based Table 1: treated fluid below 1,500 µS/cm at 25 °C; September 2026 PG Table 12: flush water below 25 µS/cm | Neither value is a universal operating-PG limit |
The treated-water value comes from the OCP water-based-fluid guideline, Table 1; the flush-water value comes from the September 2026 PG guideline. Keep fluid and stage attached to each limit.
The verified publisher methods are ASTM D471-16a(2021) for rubber, D543-21 for plastics, D8040-18(2023) for heat-transfer-fluid glassware corrosion, G1-25 for specimen cleaning, G31-21(2025) for immersion design and G71-81(2024) for galvanic testing. Their public scopes establish applicability; obtain the selected procedures for laboratory execution.
OCP's undated cold-plate paper cites D2570 without a year; ASTM lists D2570-26 for automotive circulating-coolant testing. Its public scope permits agreed component substitutions outside the engine-coolant specification qualification it identifies, so a TCS adaptation needs its own documented scope and agreement. ASTM rubber scope; ASTM D2570-26.
What conditions belong in a coupon test?
OCP's September 2026 propylene-glycol guideline gives six weeks at 65 to 85 °C as typical polymer-compatibility exposure conditions, with a room-temperature fluid blank and a matched heated fluid blank for evaluating changes in fluid purity. Select the final exposure for the material and application, and record every departure from the method. OCP §8.7.
Fix formulation, batch, concentration, actual immersed area, liquid volume, headspace, vessel, closure, holder, temperature history and preparation. ASTM G31-21(2025) identifies solution volume, gas exposure, temperature and specimen support as influential variables in immersion tests. Match vessel and support contact in the heated blank so their contribution is not assigned to the material. ASTM G31 scope.
| Element | OCP September 2026 PG guideline condition | Laboratory instruction |
|---|---|---|
| Rectangle, §8.3 | Approximately 50 × 25 mm; commonly 2 mm rubber thickness | Measure faces, edges, holes and covered area |
| Counts, §§8.3, 8.6 | Minimum three coupons per material/fluid/temperature/duration combination; five unexposed tensile controls | Coupon count is not independent-jar count; allocate destructive endpoints separately |
| Rubber tensile, §8.3 | Die C, 3.0 ± 0.3 mm described preparation | Do not substitute the rectangular specimen |
| Preparation, §8.4 | Least aggressive suitable cleaning; complete drying | Record cleaner, rinse, cure and cut-edge condition |
| Controls, §8.7 | Room-temperature and heated fluid blanks; same fluid volume | Match batch, vessels, closures and supports |
| Endpoint, §8.8 | Cool; condition in fresh room-temperature test fluid for 30 to 60 minutes; rinse with high-purity water and blot | Preserve exposure fluid; measure promptly, preferably within two hours of test end |
| Ready-to-use metal fluid, §9.3 | PG25/PG55 without further dilution; specified challenge-salt preparation | Follow the ready-to-use method branch |
| Concentrate metal fluid, §9.3 | Intended-use dilution; NaCl 110, Na2SO4 99, NaHCO3 92 mg/L | Salt masses, not ion masses; laboratory challenge only |
Three coupons sharing a jar produce one independently exposed fluid sample. Destructive tensile endpoints need their own specimens, and endpoint handling needs enough staff and equipment to meet the measurement window. Stagger exposure endings rather than leaving cooled samples waiting unrecorded.
For loaded rigid plastics, add the applicable stress-and-reagent exposure under ASTM D543-21; unloaded immersion can miss environmental stress cracking. Static jars also leave oxygen ingress, flow, pressure and thermal cycling for assembly validation. Report modified exposures as modified methods, and test production-finished surfaces separately from cleaned coupons. Temperature accelerates different reactions differently: assign field-equivalent years only through a validated model.
How much polymer change is acceptable?
OCP's September 2026 §8.12 gives general starting bands of minus 10% to plus 10% volume change and minus 30% to plus 30% tensile-strength and elongation change, subject to functional condition and component-specific acceptance. Write the purchased seal's acceptance sheet before exposure, including whether each result is a release limit or a report-only measurement. OCP polymer interpretation.
| Endpoint | Starting criterion / record | Decision |
|---|---|---|
| Volume | OCP band: -10% to +10%; before/after volume | Apply component-specific limit and function |
| Hardness | OCP §8.12 describes -10 to +10 durometer change under a percent heading | Record raw scale values and point change; resolve units |
| Tensile strength | OCP band: -30% to +30%; geometry, units, controls | Reject unacceptable hardening or functional loss |
| Elongation | OCP band: -30% to +30%; controls and failure condition | Reject embrittlement or functional loss |
| Mass | Conditioned before/after mass and handling record | Interpret with volume and fluid results |
| Finished seal | Purchased leak, movement and retention requirements | A functional failure prevents release |
Read mass, volume, hardness, tensile behavior and visible condition together. Swelling and extraction can occur simultaneously, leaving little net mass change even while the compound changes. A seal inside a screening band still needs its actual static or dynamic sealing duty tested; ASTM D471-16a(2021) provides comparative liquid-effect evidence, not automatic service equivalence.
How do you measure coolant elastomer leachables?
Measure identified constituents in the actual coolant and compare exposed fluid with both controls. Leachables enter the intended fluid under the specified exposure; an aggressive extraction study identifies possible compounds under its own conditions. Its concentrations do not predict an operating loop. The undated OCP cold-plate paper §1.3.3.2 identifies inductively coupled plasma (ICP) metal analysis, ion chromatography, and gas/liquid chromatography (GC/LC) as complementary analytical routes.
A single “leachables ppm” result cannot settle compatibility. Glycol-rich fluid already contains organic carbon, so total organic carbon (TOC) is not a selective polymer-leachables assay; conductivity likewise does not identify the released constituent. Set formulation-specific limits with the coolant and component suppliers.
| Question / target | Analytical route | Required interpretation |
|---|---|---|
| Sulfate from cure chemistry; chloride contamination | Matrix-validated ion chromatography, mg/L | Compare both blanks and supplier fluid limits |
| Cu, Zn, Fe, Ni or other metals | ICP; distinguish filtered from total/digested | Correlate with surface damage and deposits |
| Additives or degradation products | Targeted GC/LC with suitable detection | Identify compounds; verify recovery in coolant |
| Inhibitor loss | Supplier-qualified assay or targeted chromatography | Separate uptake, fluid aging and corrosion demand |
| Glycol concentration | Fluid-specific refractive correlation or laboratory method | Check evaporation and dilution |
| pH / reserve alkalinity | Fluid-specific methods | Interpret by inhibitor technology |
| Solids and shedding | Turbidity, particles and deposit identification | Separate material debris, precipitation and corrosion |
Record sample ID, exposure, collection time, container, preservation, holding time, custody, analytical method, units, dilution, matrix recovery and uncertainty. Report each independent jar and both blank results, the blank-adjusted difference, the reporting limit in the original coolant after dilution, and the decision criterion. Keep replicate spread visible rather than releasing a combination from a favorable average. A water-method reporting limit before glycol dilution does not establish coolant detection capability.
Anvilfield's analytical decision rule applies absolute fluid limits to the exposed sample and material-change criteria to its blank-adjusted result. Blank correction cannot subtract away an absolute fluid failure.
A non-detect is not zero. Preserve its reporting-limit qualifier, retain signed differences and hold any decision that dilution or blank variability prevents resolving. Repeat contaminated blanks or inadequate recovery before assigning cause.
How should leachables be normalized?
Subtract the matched heated-blank concentration from the exposed concentration, multiply by recovered fluid volume, then divide by exposed material area. With concentration in mg/L, volume in L and area in cm², the result is mg/cm²; multiply by 1,000 for µg/cm².
Anvilfield reporting calculation: q = (C_exposed − C_heated blank) × V / A.
Use this expression only for verified matching endpoint volumes. With matched starting volumes but different endpoint volumes, calculate each jar's analyte mass from its own recovered volume before comparing masses. Retain raw values and blank uncertainty; comparisons require matched fluid, time, temperature, geometry and surface-to-volume ratio.
Worked example: interpret a sulfate result
Use selected report inputs of 3.0 mg/L sulfate in exposed fluid, 0.4 mg/L in its heated blank and 0.3 mg/L in its room-temperature blank. Each jar contains 0.10 L at the endpoint; the exposed specimen area is 28 cm². All three results exceed the selected 0.1 mg/L reporting limit, and the 2.6 mg/L exposed-minus-heated difference is resolved by the analytical method.
| Calculated quantity | Result | Decision use |
|---|---|---|
| Blank-adjusted concentration | 2.6 mg/L | Compare with the material-change criterion |
| Net excess sulfate in recovered fluid | 0.26 mg | Concentration difference times 0.10 L |
| Area-normalized net excess | 9.3 µg/cm² | Divide 0.26 mg by 28 cm² and convert units |
| Selected absolute fluid ceiling | 5.0 mg/L | Exposed fluid meets this limit |
| Selected material-change ceiling | 2.0 mg/L above heated blank | Combination fails this criterion |
Anvilfield estimates the net mass and area-normalized result using the reporting calculation above. The two acceptance ceilings are selected project inputs for this worked example. Meeting the absolute fluid ceiling does not override the material-change failure; investigate the compound and confirm the independent jars before release. Area normalization reports net excess remaining in the fluid, while adsorption, deposits and unidentified species require separate evidence.
| Evidence pattern | Cause to test | Discriminating follow-up |
|---|---|---|
| Blank and exposed jars change together | Fluid aging or vessel/support contribution | Compare unheated blank and qualified vessel controls |
| Additional ions/organics in material jars | Cure, additives or processing residue | Confirm independent jars and retained production lot |
| Glycol and several constituents rise | Evaporation or handling concentration | Review recovered volume, seals and concentration assay |
| Inhibitor falls with little identified leachable | Uptake, adsorption, demand or degradation | Compare heated blank, recovery and surface evidence |
| Low dissolved metals but deposits or pits | Precipitation or localized attack | Analyze solids/total metals and inspect surfaces |
Inhibitor uptake can accompany an apparently sound polymer; low dissolved metal can accompany deposited corrosion products. Resolve the lost protection or physical damage before accepting a favorable bulk-fluid result.
Area-normalized jar results do not predict loop concentration or an allowable hose count. Representative component exposure and assembly evidence must address release over time, inhibitor demand and the installed fluid-to-surface ratio.
What metal-corrosion screen should you specify?
OCP's September 2026 modified ASTM D8040 metal screen uses three separate beakers at 88 °C for 336 hours with continuous aeration and electrically insulated coupons, so it does not establish compatibility of electrically connected metal pairs. Record intended-use fluid preparation, the salt challenge and every modification. OCP §9.3.
OCP September 2026 Table 10 sets copper C11000 and brass C26000 screen ceilings of 0.2 mpy and 5 mg coupon loss, and 304L/316L stainless ceilings of 0.1 mpy and 2 mg, within its specified test configuration. Here mpy means mils per year; one mil is 0.001 inch.
| Material | OCP rate / loss ceilings | Additional decision evidence |
|---|---|---|
| C11000 copper | 0.2 mpy / 5 mg | Retain replicate results and surface condition |
| C26000 brass | 0.2 mpy / 5 mg | Inspect pits and copper-colored surfaces consistent with dezincification |
| 304L or 316L stainless | 0.1 mpy / 2 mg | Inspect localized attack independently |
| Nonstandard alloy or plating | OCP Table 10 note suggests 0.2 mpy or less for nonstandard alloys, such as bronze | Custom bundle; agree alloy-specific criteria, coating condition and pair tests |
Use ASTM G1-25 preparation and cleaning controls; retain raw masses, cleaning correction, area, exposure duration and density. The mass and rate criteria are tied to the source configuration, not interchangeable for arbitrary coupon geometry. Inspect each coupon before and after cleaning, retain photographs and record any localized attack.
A low average loss cannot clear unexplained pits or coating damage. OCP's nonstandard-alloy note supplies no plating-adhesion or exposed-substrate acceptance criterion.
ASTM D8040-18(2023) treats glassware corrosion results as screening evidence that cannot, by itself, establish satisfactory corrosion inhibition in service. ASTM D8040 scope and significance. ASTM D1384-24 similarly addresses engine-coolant screening. OCP notes limited copper-test discrimination around 0.1 to 0.2 mpy; use that resolution when comparing fluids, and do not calculate wall life from the screen.
How do you qualify mixed-metal and plated combinations?
ASTM G71-81(2024) addresses galvanic testing of dissimilar metals in electrical contact under low-flow electrolyte conditions. Identify the coolant, electrical connection and exposed areas, including paths through fittings or bonding. ASTM G71 scope.
OCP's undated Cold Plate Development and Qualification paper §1.2.1.3 gives a 0.15 V design recommendation for metal interfaces alongside integrated corrosion qualification. It supplies neither a universal reference-electrode procedure nor a galvanic-current pass limit. Do not convert that design number into a field voltmeter acceptance test. OCP cold-plate paper.
| Pair / condition | Reproduce | Evidence and decision |
|---|---|---|
| Copper / 316L | Actual electrical connection and area ratio | Coupling current where appropriate, individual losses, localized attack |
| Copper / brass | Exact brass alloy and connection | Pair evidence plus dezincification inspection |
| Worn nickel-plated brass | Exposed substrate after defined wear | Coating damage and Cu/Zn/Ni release; hold unresolved attack |
| Copper / aluminum | Alloy, inhibitor formulation and electrical path | New coupled/uncoupled qualification; no borrowed copper limit |
| Uncoupled counterparts | Matched fluid, geometry and temperature | Separate baseline corrosion from coupling contribution |
| Small substrate / large cathode | Actual unfavorable exposed-area ratio | Inspect concentrated local damage; equal-area test insufficient |
OCP September 2026 §6.3 favors stainless quick connects and recommends avoiding nickel/chromium-plated connectors until demonstrated satisfactory. Mating wear can expose the substrate, so include the qualified worn condition and the finished-connection leak response.
Anvilfield's pair-test record names the alloy and finish on each side, exposed areas, electrical connection, coolant batch and concentration, temperature, oxygen/flow conditions, duration, uncoupled comparators and agreed loss, pitting and functional limits. Where coupling current is recorded, retain its direction and time history along with post-test damage.
Electrolyte, oxygen, passive films, temperature, flow and crevices influence pair behavior. Include stagnant or flowing duty where relevant, explicitly adapting G71's low-flow scope when necessary.
A dielectric fitting provides galvanic isolation only when parallel conductive paths are absent, and each isolated metal still needs corrosion protection. Adding aluminum to a copper-containing loop reopens both fluid/material and pair evidence.
Vertiv SL-80056 Rev A §6.3 calls for proper grounding and bonding to be identified and followed. Preserve those protective connections when designing galvanic isolation.
What must pass on the finished assembly?
Test the purchased hose, connector, valve, cold plate and manifold construction after material screening. Finished surfaces introduce brazes, sealants, residues and geometry that a clean coupon omits. OCP's cold-plate paper and rack-manifold qualification paper treat component validation as its own evidence package.
Measure leak tightness, pressure integrity, seal movement/retention, relevant connect/disconnect duty, pressure drop and thermal performance against the purchased specification. Establish hydraulic and thermal baselines, then repeat at the same coolant, flow, temperature and mounting condition. Changed viscosity or setup can resemble fouling. Record cold-plate pressure drop and thermal resistance separately; changed thermal resistance with unchanged pressure drop also needs a mounting/contact check.
Include filled storage, stagnant operation and expected service cycles when they differ from continuous duty. Log actual fluid, pressure, temperature, flow and cycles; retain post-exposure fluid, deposits and surface observations. Exterior salt spray addresses exterior durability, not internal coolant compatibility.
Retain the hydro-test pressure-boundary record separately from material approval. The CDU commissioning guide covers operational handoff; redundancy and concurrent maintenance establishes the service and isolation duty the assemblies must support. Use their system procedures with the assembly supplier's actual pressure and cycling requirements.
Which changes require requalification?
Reopen qualification when composition, manufacturing condition, fluid or operating duty changes. A new lot of an unchanged approved product needs traceability and incoming verification; it does not automatically need another six-week exposure. Use Anvilfield's change gate below.
| Change | Evidence required | Action before release |
|---|---|---|
| Unchanged new lot | Certificate, identity and lot trace | Verify existing coverage |
| Compound, cure or plasticizer | Updated identity; mechanical/fluid-purity exposure | Hold substitution; targeted polymer tests |
| Alloy, braze or plating | Register revision; corrosion, pairs, finished part | Expand material and assembly evaluation |
| Supplier or production site | Process, cleanliness and traceable equivalence | Hold until equivalence or retest accepted |
| Fluid brand, formula, concentration or top-up mix | New specification and affected interactions | Reassess exposed materials set |
| Cleaner, sealant or filter | Residue, shedding and compatibility | Targeted exposure and cleanliness review |
| Higher temperature or changed duty | Comparison with proven envelope | Extend affected qualification |
| Contamination or failure trend | Retained samples, lot/BOM and cause evidence | Reopen approval and disposition stock |
Treat changed inhibitors, mixed-brand top-up and added biocide as fluid-formulation changes even when nominal glycol percentage stays constant. Require affected suppliers' compatibility evidence and the corresponding tests. Changes to existing infrastructure also need the liquid-cooling retrofit scope review.
The owner/design authority accepts the project combination; component and fluid suppliers substantiate their limits. Tie the signature to BOM, coolant revision, methods, criteria, reports and resolved exceptions.
Purchase terms should require advance notice of material, site or process changes, an unchanged-configuration declaration, lot traceability and permission before substitution. Preserve superseded approvals so failures can be traced to installed lots. Apply OCP September 2026 §§6, 8-9 within the purchased component requirements.
What changes after installation?
Establish the installed-fluid commissioning baseline and transfer approved identities, limits and retained-sample locations into the water-treatment and chemistry program. Laboratory qualification selects a material-fluid combination; operating surveillance detects changes in the installed system. Salt-challenged laboratory corrosion exposure is not an installed-loop procedure.
OCP September 2026 §11.2 calls for annual qualified-laboratory testing of each TCS loop and gives the following risk-based schedules, with separate representative-sampling guidance for similar small rack loops. Record the scenario assumptions with the selected schedule. OCP sampling guidance.
| OCP scenario | Required assumptions | Schedule |
|---|---|---|
| Low risk | Inline pH/refractive monitoring; acceptable materials; familiar user | Baseline, then annually; optional six-month first-year sample |
| Medium risk | No inline monitoring; acceptable materials; unfamiliar user | Baseline, six-monthly for 18 months; annual option after stability |
| High risk | No inline monitoring; mostly acceptable materials; unfamiliar user | Baseline, quarterly for 18 months; six-monthly option after stability |
| Comparable loops below 100 gallons | Same rack-loop construction | Every rack: startup pH/glycol; representative laboratory subset at least six-monthly; rotate racks |
“Mostly acceptable” is OCP's scenario language, not permission to install an unapproved component. Investigate changed metal, sulfate, inhibitor or particle trends against the material register and retained samples. Increase rack-sampling coverage after anomalies, and investigate inline sensor anomalies that remain unresolved after on-site checks or sensor calibration.
Collect a representative circulating-fluid sample using the approved sample port and procedure. OCP §11.2 also recommends retaining labeled as-received fluid samples from deliveries and batches for at least six months; record their locations and batch numbers at handoff.
Record flush and test-fluid contact as well. Vertiv SL-80056 Rev A §6.1 says to avoid chemical cleaners/detergents unless following the new heat-transfer-fluid supplier's guidance; OCP September 2026 §10 describes controlled cleaning and rinsing. Preserve that exception and the product-manual precedence in the approved cleaning procedure. Vertiv cleaning guidance.
How long does qualification take, and what belongs in the estimate?
Allow six weeks of exposure when the selected polymer and metal screens run in parallel, or eight weeks when they run sequentially. These Anvilfield schedule estimates use OCP's September 2026 starting conditions; preparation, analytics, pair testing, assembly validation and review need additional scheduled time.
For an order covering three polymer formulations, multiply formulations by temperatures by independent jars, then add matching fluid controls. The selected scope uses one inhibited PG25 formulation and batch, identified peroxide-cured EPDM, FKM and HDPE formulations, and exposures at 65 °C and 85 °C. Order three independent jars per material/temperature combination; the isolated metals are C11000 copper, C26000 brass, 304L stainless and 316L stainless. Share controls only when fluid batch, volume, container and thermal run match.
| Order item | Calculation / result | Basis |
|---|---|---|
| Material jars | 3 × 2 × 3 = 18 | Three independent exposures per combination |
| Fluid controls | 2 heated + 2 room-temperature = 4 | Paired to the two temperature sets |
| Polymer/control jars | 18 + 4 = 22 | Same fluid formulation |
| Metal coupons | 4 types × 3 beakers = 12 | One coupon/type/beaker |
| Polymer specimens | 18 rectangles + 90 exposed tensile + 15 controls = 123 | One rectangle and five tensile/jar; five controls/formulation |
| Endpoint fluid streams | 22 + 3 = 25 | Additional QA and method-specific aliquot bottles separately |
| Exposure schedule | 42 days parallel; 42 + 14 = 56 sequential | Capacity determines overlap |
| Rectangle area | 25 cm² faces + 3 cm² edges = 28 cm² | 50 × 25 × 2 mm, before holes |
| Selected 0.5 L salt batch | NaCl 55 mg; Na2SO4 49.5 mg; NaHCO3 46 mg | Concentrate-test branch only |
Anvilfield estimates these quantities from OCP's September 2026 exposure conditions and the selected scope above. Five exposed tensile specimens per jar is the order's choice; the laboratory confirms destructive endpoints, conditioning and material-specific geometry.
Use the table's rubber geometry for the rubber rectangles; OCP describes plastic tensile preparation separately through its ASTM D638 reference. Five unexposed controls per formulation are shared only with identical baseline conditioning and material lot.
Adding the rectangle's cut edges increases face-only area by 12%; omitting them understates total area by about 11%. In a selected 100 mL jar, that rectangle contributes 0.28 cm²/mL; add all tensile-specimen areas and subtract holes or covered surfaces to obtain the actual ratio.
For the salt batch, multiply each published salt mass per liter by 0.5 L final solution. Use qualified stock preparation when direct weighing is outside suitable balance capability. Set beaker fill volumes and ready-to-use-fluid preparation through their respective method branches.
| Line | Selected scope | Quote boundary |
|---|---|---|
| Polymer work | 22 jars; 123 specimens; six weeks | Preparation, controls, exposure, mechanical endpoints and handling |
| Metal work | 3 beakers; 12 coupons; two weeks | Modified screen, cleaning, measurements and surface inspection |
| Fluid analysis | 25 endpoint streams before QA | Analytical panels, matrix preparation, reporting limits and aliquots |
| Pairs | Installed alloy/finish combinations and uncoupled comparators | Area ratios, electrical paths, exposure and damage assessment |
| Assemblies | Purchased hose, connector, plate and manifold BOM | Functional duty, hydraulic/thermal baselines and replacement specimens |
| Reporting and repeats | Traceable raw data, release file and defined retests | Methods, QA review, failed-test repeats and report ownership |
Request separate laboratory quotation lines for these quantities, endpoint methods, detection capability, handling capacity, pair conditions and assembly duty. Name who supplies specimens, owns reports and funds agreed retests. Obtain the selected ASTM procedures and agree every TCS modification before testing.
A public cooling bid needs clear responsibility for test specimens, laboratory reports and retests; estimators use PorchRocket's Bid Control to find the HVAC and refrigeration contracts where they price that scope.
Field checklist: release the material combination
- Mark the TCS boundary and temporary fluid contacts; hold incomplete scope.
- Record part, revision, compound/alloy, cure, coating, lot and process; hold unnamed formulations.
- Name fluid product, revision, batch, concentration and thermal envelope; resolve conflicts.
- Match supplier reports to the actual combination; document equivalence or order tests.
- Approve geometry, area, volume, controls, independent jars and analytical limits.
- Agree mechanical units and limits; allocate destructive specimens and endpoint handling.
- Retain raw results and analytical QA; hold unusable blanks or inadequate detection.
- Inspect pits, dezincification, coating damage and deposits; resolve localized attack.
- Map electrical paths and area ratios; test uncovered pairs.
- Complete finished-component duty; hold functional failures despite coupon passes.
- Sign the exact BOM/fluid release and change triggers; block unreviewed substitutions.
- Transfer baseline, sampling schedule and retained samples; assign trend-review responsibility.
Release record and citation
Keep one signed cover record for the approved combination: register revision; purchased part/BOM revisions and lots; coolant product, revision, batch and concentration; allowable exposure envelope; report IDs and specimen identities; accepted criteria; disposition of deviations; approving owner/design authority; supplier change-notification terms; and the operating baseline. Link it to raw measurements, retained samples, photographs and assembly results so a service replacement can be checked against the same approval.
Anvilfield. Sources checked and reviewed: 2026-11-05. Update log, 2026-11-05: clarified alloy-screen scope and acceptance records; added a worked leachables decision; revised the quotation scope and operating handoff.
How to cite this page: Anvilfield, How to qualify wetted materials for a liquid-cooling loop, 2026, https://anvilfield.com/field-guides/datacenter/coolant-material-leachables-qualification/
FAQ
How are liquid-cooling wetted materials qualified for corrosion and leachables?
Identify the exact material-fluid combination, test physical and fluid changes under controlled exposure, then validate relevant metal pairs and finished assemblies.
Can EPDM leach into coolant?
Yes. OCP's September 2026 PG guidance warns that sulfur-cured EPDM can introduce sulfate and recommends peroxide-cured EPDM as the starting choice.
Does an OCP listing approve a material for every coolant?
No. OCP's September 2026 material lists are representative; formulation and application still require confirmation.
How long is an OCP polymer compatibility screen?
The September 2026 PG guideline gives six weeks at 65 to 85 °C as typical starting conditions, selected for the material and application.
What swelling limit does OCP suggest?
OCP's September 2026 PG guidance gives minus 10% to plus 10% volume change as a general starting band, subject to component performance.
Does a metal coupon pass prove mixed-metal compatibility?
No. OCP's modified D8040 screen electrically isolates coupons; connected pairs require separate evaluation.
Can conductivity alone reveal elastomer leachables?
No. Combine fluid-condition measurements with targeted ion, metal or organic analyses and matched controls.
Does a hydrostatic test prove coolant compatibility?
A hydrostatic test documents pressure integrity under its specified conditions. Chemical and long-term material interactions require separate qualification evidence.
Must every production lot repeat six weeks of testing?
Anvilfield's change gate uses traceability and incoming verification for unchanged approved products; composition, processing or exposure changes reopen qualification.
What belongs in a laboratory qualification quotation?
Request separate lines for the worked package of 22 jars, 123 polymer specimens, 12 metal coupons and 25 endpoint fluid streams, plus QA, pair tests, assembly duty, reporting and retests. These are Anvilfield estimates for the selected scope.
Does six weeks at 85 °C prove years of service?
No. OCP's September 2026 guidance uses short exposures as screening; representative duty, longer testing and field evidence add service coverage.
Can qualification cover another glycol brand or a water loop?
Only accepted evidence covering the exact material-fluid combination and exposure supports transfer. Changed inhibitors, concentration, additives or water chemistry require scope review and affected tests.
People also ask
Codes cited in this guide
This guide is written and reviewed against the published standards below. Always confirm the current adopted edition with the authority having jurisdiction.
Sources checked
- S1. Open Compute Project, Guidelines for Using Propylene Glycol-Based Heat Transfer Fluids in Liquid Cooled Racks, Revision 2.0, Version 1.0.0, September 15, 2026. Primary PG exposure, acceptance and sampling guidance, §§6, 8-11. Sources checked: 2026-11-05.
- S2. Vertiv, Guidelines for Deployment of Single Phase Technology Cooling System, SL-80056_REVA_02-25, ©2025. Product-manual precedence, acceptable materials, sealants and conditional cleaning instructions. Sources checked: 2026-11-05.
- S3. Open Compute Project, White Paper: Cold Plate Development and Qualification, undated public edition at the opened URL. Undated public edition; integrated corrosion, analytical methods and assembly qualification. Sources checked: 2026-11-05.
- S4. Open Compute Project, Guidelines for Using Water-Based Transfer Fluids in Single-Phase Cold Plate-Based Liquid-Cooled Racks, undated final public PDF. Undated final public PDF; water-specific chemistry and scope. Sources checked: 2026-11-05.
- S5. ASTM D471-16a(2021), Standard Test Method for Rubber Property: Effect of Liquids. Public scope and active rubber-method edition; OCP bibliography has a differing designation. Sources checked: 2026-11-05.
- S6. ASTM D543-21, Standard Practices for Evaluating the Resistance of Plastics to Chemical Reagents. Public scope and stressed-plastic exposure. Sources checked: 2026-11-05.
- S7. ASTM D8040-18(2023), Standard Test Method for Corrosion Test for Heat Transfer Fluids in Glassware. Public scope and screening limitations. Sources checked: 2026-11-05.
- S8. ASTM G1-25, Standard Practice for Preparing, Cleaning, and Evaluating Corrosion Test Specimens. Public scope and specimen preparation, cleaning and damage evaluation. Sources checked: 2026-11-05.
- S9. ASTM G31-21(2025), Standard Guide for Laboratory Immersion Corrosion Testing of Metals. Public scope, immersion variables and localized-attack limitations. Sources checked: 2026-11-05.
- S10. ASTM G71-81(2024), Standard Guide for Conducting and Evaluating Galvanic Corrosion Tests in Electrolytes. Public scope, electrical contact and low-flow galvanic testing. Sources checked: 2026-11-05.
- S11. ASTM D2570-26, Standard Test Method for Simulated Service Corrosion Testing of Engine Coolants. Public scope, automotive circulating-coolant application and substitutions. Sources checked: 2026-11-05.
- S12. Parker, Data Center Cooling Thermal Management System, undated manufacturer product/application page. Undated manufacturer cooling-system page; linked HOSE627.js product description confirms peroxide-cured EPDM tube construction. Sources checked: 2026-11-05.
- S13. Open Compute Project, Cold Plate subproject, live index checked 2026-11-05. Live index; document discovery and cold-plate workstream. Sources checked: 2026-11-05.
- S14. ASTM D1384-24, Standard Test Method for Corrosion Test for Engine Coolants in Glassware. Public scope and engine-coolant glassware-screen limitations. Sources checked: 2026-11-05.
- S15. Open Compute Project, White Paper: Guidelines to Rack Manifold Requirements and Qualification, undated public PDF at filename v3. Undated public PDF with v3 filename; manifold component qualification. Sources checked: 2026-11-05.